Trinity Lx
│
Installation and Operation Instructions
Lx – WH Series
88
Table 17-3
Hold and Lockout Codes
Code
Description
Note
15
Internal fault: Safety relay test failed due to feedback ON
Lockout
16
Internal fault: Safety relay test failed due to safety relay OFF
Lockout
17
Internal fault: Safety relay test failed due to safety relay not OFF
Lockout
18
Internal fault: Safety relay test failed due to feedback not ON
Lockout
19
Internal fault: Safety RAM write
Lockout
20
Internal fault: Flame ripple and overflow
Hold
21
Internal fault: Flame number of sample mismatch
Hold
22
Internal fault: Flame bias out of range
Hold
23
Internal fault: Bias changed since heating cycle starts
Hold
24
Internal fault: Spark voltage stuck low or high
Hold
25
Internal fault: Spark voltage changed too much during flame sensing time
Hold
26
Internal fault: Static flame ripple
Hold
27
Internal fault: Flame rod shorted to ground detected
Hold
28
Internal fault: A/D linearity test fails
Hold
29
Internal fault: Flame bias cannot be set in range
Hold
30
Internal fault: Flame bias shorted to adjacent pin
Hold
31
Internal fault: SLO electronics unknown error
Hold
32
Internal fault: Safety Key 0
Lockout
33
Internal fault: Safety Key 1
Lockout
34
Internal fault: Safety Key 2
Lockout
35
Internal fault: Safety Key 3
Lockout
36
Internal fault: Safety Key 4
Lockout
37
Internal fault: Safety Key 5
Lockout
38
Internal fault: Safety Key 6
Lockout
39
Internal fault: Safety Key 7
Lockout
40
Internal fault: Safety Key 8
Lockout
41
Internal fault: Safety Key 9
Lockout
42
Internal fault: Safety Key 10
Lockout
43
Internal fault: Safety Key 11
Lockout
44
Internal fault: Safety Key 12
Lockout
45
Internal fault: Safety Key 13
Lockout
46
Internal fault: Safety Key 14
Lockout
47
Flame rod to ground leakage
Hold
48
Static flame (not flickering)
Hold
49
24VAC voltage low/high
Hold
50
Modulation fault
Hold
51
Pump fault
Hold
52
Motor tachometer fault
Hold
53
AC inputs phase reversed
Lockout
54
Safety GVT model ID doesn’t match application’s model ID
Lockout
55
Application configuration data block CRC errors
Lockout
56-57
RESERVED
58
Internal fault: HFS shorted to IAS
Lockout
59
Internal fault: Mux pin shorted
Lockout
60
Internal fault: HFS shorted to LFS
Lockout
61
Anti short cycle
Hold
62
Fan speed not proved
Hold
63
LCI OFF
Hold
64
PII OFF
N/A