Master/Slave Mode .
400CP panels may be slaved to one another. Several panels may act as slaves to a master panel which contains
the programming. The slaves will mimic the master LED’s and will operate the scenes and fade times of the
master. This is ideal for installations with several panels in one room.
To make a panel into a master (factory default); set the Master\Slave ID to 0. To make a panel into a slave; set
the Master/Slave ID to the Network ID of the desired master to slave to.
To set Master/Slave ID number:
1.
Make sure that the 400CP is in the program mode as discussed.
2.
Press the zone 4 increase button and the BUSY LED will stop flashing
3.
Look up the necessary sequence of 1’s and 0’ for the ID number on the chart at the end of this section.
4.
Using the two buttons indicated below, enter the eight number sequence of 1’s and 0’s.
5.
The unit will exit this program mode at the release of the eighth press, and the BUSY LED will start flashing
again.
NOTE : All other programming (except network ID) will have no effect if unit is made into a slave. The
master unit willcontains the programming for all units slaved to it. Slave units must also still have a unique
Network ID number (see following section).
400CP REMOTE CONTROL PANEL
PROGRAMMING
Software Revision 3.00, Version C
Master/Slave Mode .
NSI CORPORATION
8