PROGRAMMING
Several parameters must be programmed into the 400CP for it to operate properly:
Maximum number of dimmers channels.
Dimmer channel assignments for each zone.
Fade time for each zone.
Master / Slave Mode.
Network ID number (IMPORTANT).
Optionally, the unit may be ordered preprogrammed from the factory. Any field modifications can be made if
necessary.
Factory Default Setting:
The 400CP is programmed at the factory for zone 1-4 to be set for channel 1-4 respectively. The fade rate ant
other parameters are also set to factory defaults. This may be acceptable for initial testing. If necessary to return
the 400CP panel to it’s factory default settings (except network ID), follow this procedure:
1.
Remove program jumper block and disconnect plug-in terminal block.
2.
Hold down all ZONE 1-4 LOWER buttons while connecting terminal block.
Full Memory Clear:
Normally, the 400CP will not require memory clearing. Once the memory is cleared, all parameters, including
fade rate, must be reprogrammed. Unless it is necessary to clear memory to remove a large or unknown programming,
skip these steps.
1.
Remove program jumper block and disconnect terminal block.
2.
Hold down all ZONE 1-4 RAISE buttons while connecting the terminal block.
Prepare the 400CP for reprogramming:
In order to program the 400CP, a jumper block must be removed from the program jumper pins (See diagram).
This will allow data to be stored in the eeprom memory. At this point the BUSY LED will start flashing, indicating
that you are in the program select mode.
IMPORTANT: After programming it is important to replace the programming jumper block so memory
will be protected.
400CP REMOTE CONTROL PANEL
PROGRAMMING
Software Revision 3.00, Version C
Factory Default Setting:
NSI CORPORATION
4