background image

Assigning dimmer channels to each scene.

Each of the zones of the 400CP must be programmed with the desired dimmer channel assignments.  Only the
dimmer channels assigned will be affected by each zone’s increase and decrease buttons.

In order to easily identify dimmer channels while programming, the system should have all installed lamps or loads
operational.  If this is not possible, the 400CP to be programmed should be temporarily connected nearby to the
dimmer units so that the control LEDs of the dimmers may be observed to verify channel selection.

To program each zone:

1.

Make sure that the 400CP is in the program select mode as discussed.  The BUSY LED should be flashing.

2.

Press the zone 2 increase button to select "dimmer assignment mode" and the BUSY LED will stop flashing.

3.

Press INCREASE button representing desired zone to be programmed.  At this point, all currently assigned
dimmers will come on.  The current dimmer selector will be set to one.

4.

Use the buttons marked as UP and DOWN in diagram to increment or decrement the dimmer channel selector.
Tap the buttons the required number of times to reach the dimmer channel to be assigned.

5.

Use the ADD and DELETE buttons to add or delete this dimmer from the zone.  The lamps connected  to
this dimmer channel will come on full when the ADD button is pressed.  Observe lamps or dimmer  LEDs
to verify correct channel has been selected.

6.

A new zone can be programmed at any time by pressing the appropriate zone INCREASE button. The dimmer
selector number will always return to one when changing zones.

7.

To exit this programming mode; press both the UP and DOWN buttons at the same time.  The BUSY LED
will start flashing again when both buttons are then released.

400CP REMOTE CONTROL PANEL

PROGRAMMING

Software Revision 3.00, Version C

Assigning dimmer channels to each scene.

NSI CORPORATION

6

Summary of Contents for LUMA-NET 400CP

Page 1: ...fade times Remote lockout capability is also included Installation is a snap with the simple 4 wire digital connection required IMPORTANT Programming differs from older 400CP panels prior to release 3...

Page 2: ...or components MOUNTING The 400CP will mount in any standard double gang electrical box with the 4 screws provided See below paragraph on system turn on before final mounting of panels SYSTEM TURN ON...

Page 3: ...re bad ID While programming the following actions are normal Quickly flashing Programming mode no mode selected Off Programming mode mode selected LOCKOUT Any 400CP may be disabled from operation with...

Page 4: ...down all ZONE 1 4 LOWER buttons while connecting terminal block Full Memory Clear Normally the 400CP will not require memory clearing Once the memory is cleared all parameters including fade rate must...

Page 5: ...e zone 1 increase button and the BUSY led will quit flashing 3 Press button representing desired number of dimmers as shown in the diagram 4 If more than 256 dimmers are required then press a second b...

Page 6: ...red zone to be programmed At this point all currently assigned dimmers will come on The current dimmer selector will be set to one 4 Use the buttons marked as UP and DOWN in diagram to increment or de...

Page 7: ...pressed If the factory default setting of 5 seconds is desired for each zone then this step may be ignored To program zone fade time 1 Make sure that the 400CP is in the program select mode as discus...

Page 8: ...m mode as discussed 2 Press the zone 4 increase button and the BUSY LED will stop flashing 3 Look up the necessary sequence of 1 s and 0 for the ID number on the chart at the end of this section 4 Usi...

Page 9: ...s without dipswitch 1 Make sure that the 400CP is in the program mode as discussed 2 Press the zone 1 2 3 4 increase buttons at the same time and the BUSY LED will stop flashing 3 Look up the necessar...

Page 10: ...1100 62 01111100 63 11111100 64 00000010 65 10000010 66 01000010 67 11000010 68 00100010 69 10100010 70 01100010 71 11100010 72 00010010 73 10010010 74 01010010 75 11010010 76 00110010 77 10110010 78...

Page 11: ...hannels assigned to the selected zone and decrease lighting levels at the programmed fade rate Release button when correct lighting levels are attained To restore control from a console Simply perform...