PM-100 CERTISAFE™ PIPE MOUNT
MANUAL
852113 / 2021.1.1
7
Ø 7/8” or 1-7/64”
Ø 3/8”
4”
TANK PENETRATION FOR CABLE SUPPORT AND CORD GRIP
Note:
• The maximum
tank roof thickness accommodated by the tank penetration parts included is 1/8”.
•
Suggested measurements are based on a 24” square access hatch.
1.
Drill a 7/8” (or 1-7/64” for 10 AWG cable) clearance hole through the tank at a location conveniently reached from the tank hatch.
This is for the cord grip (S).
2.
Deburr both sides of the hole.
3.
Drill a 3/8” clearance hole about 4” from the hole drilled in step 1. This is for the eye bolt (N).
4.
Deburr both sides of the second hole.
5. From the tank exterior, pass the O-ringed side of the cord grip
(S) through the 7/8” hole, with the O-ring outside the tank roof.
6.
From the tank interior, fit the cord grip nut (T) on the threads
protruding into the tank.
7. Tighten the nut until snug, being careful not to over-tighten.
Steel tank roof
Steel tank roof
S
T
Tank hatch center point
Fig. 2
Fig. 3
Fig. 4