In order to operate appropriately, the controller needs a configuration 
that is the definition of each one of the several parameters presented 
by the controller. The user must be  aware of the importance of each 
parameter  and  for  each  one  determine  a  valid  condition  or  a  valid 
value.  

Note: 

Since many parameters depend on the input type chosen, 

it is recommended that the parameter 

TYPE

 be the first one to be 

configured.  

 

The parameters are grouped in levels according to their functionality 
and operation easiness. The 7 levels of parameters are:  

LEVEL  

ACCESS 

1 - Operation 

Free access  

2 - Tuning  

Reserved access  

3- R&S Programs 
4- Alarms 
5- Scale 
6- I/Os 
7- Calibration 

Table 5

 – Cycles of Parameters  

The parameters in the operation level have easy access through the 
key 

 

. The access deeper levels use the combination of keys:  

 

  (BACK) and  

 

  (PROG) pressed simultaneously  

Press 

 

 to advance or 

 

 to retrocede parameters within a level. At 

the  end  of  each  level,  the  controller  returns  to  the  operation  level. 
Keep pressing the 

 

 key to move fast forward in the level. 

Alternatively,  the  controller  returns  to  the  operation  level  after 
pressing the 

 

   key for 3 seconds   

All  configuration  parameters  are  stored  in  protected  memory.  The 
values are saved when the keys 

 

 or 

 

 are pressed after changing 

a parameter value. The value of SP is saved upon pressing the 

 

 

key or every 25 seconds.  

DESCRIPTION OF THE PARAMETERS  

OPERATION CYCLE 

To access the operation level parameters, press

 

 

 until the desired 

parameter is displays.

  

 

PV Indication 
(Red Screen) 

SP Indication 

(Green Screen) 

 

PV and SP indication

 – The upper display shows 

the current value  of PV. The lower  display shows 
the control SP value.  

(trl

 

Control

 

Control Mode: 

avto

 - Means automatic control mode.  

Man

 

– Means manual control mode.  

(bumpless  transfer  between  automatic  and  manual 
control modes).  

 

PV Indication 
(Red Screen) 

MV Indication 

(Green Screen) 

 

MANIPULATED  VARIABLE  VALUE  (MV):  The 
upper display shows PV value and the lower display 
shows the 

percentage

 of MV applied to the control 

output.  When  in  manual  control,  the  MV  value  can 
be manually changed by the 

 

 and 

 

 keys. When 

in auto mode the MV value can only be viewed. 
To distinguish the MV display from the SP display, 
the MV is shown flashing intermittently.

 

E pr 

Enable 

Program

 

Execution  of  Program

  -  Selects  the  ramp  and 

soak profile program to be executed.  
 

0

 -  does not execute program 

 

1 to 20

  number  of  the  program  to  be 

executed  
With  enabled  outputs  (RUN  =  YES),  the  program 
starts right after the program is selected. 

p.seg

 

Screen  for indication only. When a  ramp and soak 
program is active, this parameter shows the number 
of the segment under execution, from 1 to 9. 

t.seg

 

Screen for indication only. When a ramp and soak 
program  is  in  execution,  it  shows  the  remaining 
time to the end of the current segment, in units of 
time configured in the 

Pr.tb

 parameter.  

rvn

 

Enables control outputs and alarms.  

YES 

- Outputs enables.  

NO

    - Outputs not enabled.  

CYCLE OF TUNING  

Atvn 

Auto-tune 

Defines the control strategy to be taken:  

off

 

– Turned off. (no PID tuning)  

Fast 

– 

Fast 

automatic tuning.  

Full 

–More accurate automatic tuning.  

self 

– P auto - adaptative tuning 

rslf 

–Forces  one  new  precise  automatic 

p auto - adaptative tuning.  

T9kt

 - Forces one new precise aut auto 

- adaptative tuning when Run = YES or controller 
is turned on.  

pb 

Proportional 

Band 

PROPORTIONAL  BAND  -  Value  of  the  term 

P

  of 

the  control  mode  PID,  in  percentage  of  the 
maximum  span  of  the  input  type.  Adjust  of 
between  0  and  500.0  %.  Select  zero  for  ON/OFF 
control. 

ir 

Integral Rate 

INTEGRAL RATE - Value of the term 

I

 of the PID 

algorithm,  in  repetitions  per  minute  (Reset). 
Adjustable between 0 and 99.99.  
Displayed only if proportional band 

 0.  

dt 

Derivative Time 

DERIVATIVE  TIME  -  Value  of  the  term 

D

  of  the 

control mode PID, in seconds. Adjustable between 
0 and 300.0 seconds.  
Displayed only if proportional band 

 0.  

(t 

Cycle Time 

Pulse Width Modulation (PWM) period in seconds. 
Adjustable between 0.5 and 100.0 seconds.  
Displayed only if proportional band 

 0.  

kyst 

Hysteresis

 

CONTROL  HYSTERESIS  (in  engineering.  units): 
This parameter is only shown for ON / OFF control 
(Pb=0).

 

Adjustable  between 

0

  and  the 

measurement input type span.  

ACt 

Action

 

CONTROL ACTION: For Auto Mode only. 

re

  Control with reverse Action. Appropriate for 

heating

.  Turns  control  output  on  when  PV 

is below SP.  

dir

  Control  with  direct  Action.  Appropriate  for 

cooling

. Turns control output on when PV 

is above SP.  

Lbd.t 

Loop 

break 

detection time. 

Time  interval  for  the  LBD  function.  Defines  the 
maximum interval of time for the PV to react to a 
control command. In minutes 

bias

 

BIAS:  Offset  for  MV  (manual  reset).  Range:  -100 
% to +100 %. 
Allows adding a percentage value between -100 % 
and +100 %. to the MV control output  
The value 0 (zero) disables the function.  

ovll 

Output Low 

Limit 

Lower  limit  for  the  control  output  -  Minimum 
percentage  value  assumed  by  the  control  output 
when in automatic mode and in PID.  
Typically configured with 

0 %

. Default value: 0 %  

Summary of Contents for N1200

Page 1: ...meters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 20 setpoint profile programs with 9 segments eac...

Page 2: ...xecution of the selected setpoint profile program Available for I O5 or I O3 and I O4 when available Closed Enables execution of the program Open Interrupts freezes execution of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starti...

Page 3: ...th this feature enabled the controller uses for display and control a value that corresponds to the square root of the applied input signal Available only for the inputs belonging to the group of linear analogic signals 0 20 mA 4 20 mA 0 50 mV 0 5 V and 0 10 V ANALOG RETRANSMISSION OF PV AND SP The analog output when not used for control purposes is available for retransmitting the PV and SP value...

Page 4: ... your supervisory software to conduct the MONITORING process Follow the procedure below to use the USB communication of the equipment Download the NConfig software from our website and install it on your computer The USB drivers necessary for operating the communication will be installed together with the software Connect the USB cable between the equipment and the computer The controller does not...

Page 5: ... product specifications Figure 6a I O3 or I O4 with output pulse for SSR Figure 6b I O5 with output pulse for SSR I O3 I O4 and I O5 can also be configured as digital outputs I O3 and I O4 provide a 5 Vdc output signal whereas I O5 a 12 Vdc signal An example of usage is shown in Figure 6a for the I O3 and in Figure 6b for the I O5 I O5 is electrically isolated from the sensor input OPERATION The c...

Page 6: ...ed 0 does not execute program 1 to 20 number of the program to be executed With enabled outputs RUN YES the program starts right after the program is selected p seg Screen for indication only When a ramp and soak program is active this parameter shows the number of the segment under execution from 1 to 9 t seg Screen for indication only When a ramp and soak program is in execution it shows the rem...

Page 7: ...r up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 ALARM HYSTERESIS Defines the difference between the value of PV at which the alarm is xya2 xya3 xya4 triggered and the value at which it is turned off in engineering units A1t1 A2t1 A3t1 A4t1 Alarm Time t1 Defines the temporization time t1...

Page 8: ...l I O 3 according to the Table 2 Io 4 Function of the channel I O 4 Selection of the function used in the channel I O 4 according to the Table 2 Io 5 Function of the channel I O 5 Selection of the function used in the channel I O 5 according to the Table 2 CALIBRATION CYCLE All of the input and output types are calibrated in the factory If a recalibration is required this should be carried out by ...

Page 9: ...des the parameters on the protected levels If no password is entered the parameters of the protected cycles can only be visualized The Access Code is defined by the user in the parameter Password Change PAS present in the Calibration level The factory default for the password code is 1111 Protection of the access code The protection system built into the controller blocks for 10 minutes the access...

Page 10: ...itiated by the controller whenever the control performance is worse than the one found after the previous tuning In order to activate the performance supervision and auto adaptative tuning the parameter ATUN must be adjusted for SELF RSLF or TGHT The controller s behavior during the auto adaptative tuning will depend on the worsening of the present performance If the maladjustment is small the tun...

Page 11: ...ignal that corresponds to a value a little lower than the upper limit of indication f Access the parameter inLC With the keys and adjust the display reading such as to match the applied signal Then press the P key Note When checking the controller calibration with a Pt100 simulator pay attention to the simulator minimum excitation current requirement which may not be compatible with the 0 170 mA e...

Page 12: ...Vdc 24 Vac 10 20 Maximum consumption 9 VA ENVIRONMENTAL CONDITIONS Operation Temperature 5 to 50 C Relative Humidity 80 max 30 ºC For temperatures above 30 ºC reduce 3 for each ºC Internal Use Category of installation II Degree of pollution 2 altitude 2000 m INPUT T C Pt100 voltage and current according to Table 1 Internal Resolution 32767 levels 15 bits Resolution of Display 12000 levels from 199...

Page 13: ... Relay in I O3 DIO Digital I Os in I O3 and I O4 HBD Burnt Out Resistance detection C Digital Communication Blank basic version without serial communication 485 RS485 Modbus protocol D Power Supply Blank basic version 100 to 240 Vac dc input 24V 12 to 24 Vdc 24 Vac input voltage WARRANTY Warranty conditions are available on our web site www novusautomation com warranty ...

Reviews: