Novus N1200 Instruction Manual Download Page 2

Controller N1200  

NOVUS AUTOMATION 

2 / 13 

FUNCTION OF I/O  

CODE 

TYPE OF I/O  

Without Function  

OFF 

Output 

Output of Alarm 1  

A1 

Output 

Output of Alarm 2  

A2 

Output 

Output of Alarm 3  

A3 

Output 

Output of Alarm 4  

A4 

Output 

LBD - 

Loop break detection

 

Lbd 

Output 

Control Output (Relay or Digital Pulse)  

CTRL 

Output 

Automatic / Manual mode selection  

mAN 

Digital Input 

Run / Stop mode selection 

RVN 

Digital Input 

Remote SP selection 

RSP 

Digital Input 

Setpoint profile program HOLD (Freezes 
program execution) 

KPRG 

Digital Input 

Setpoint Profile Program 1 selection 

PR 1 

Digital Input 

 0 to 20 mA control output selection 

(.0.20 

Analogical Output 

4 to 20 mA control output selection 

(.4.20 

Analogical Output 

Retransmission of PV in  0 to 20 mA  

P.0.20 

Analogical Output 

Retransmission of PV in 4 to 20 mA  

P.4.20 

Analogical Output 

Retransmission of Sp in 0 to 20 mA  

S.0.20 

Analogical Output 

Retransmission of SP in 4 to 20 mA  

S.4.20 

Analogical Output 

Table 2

 - Types of functions for the I/O channels 

During the configuration of the I/O channels, only the valid options for 
each  channel  will  be  shown  on  the  display.  These  functions  are 
described below:  

 

off

 - Without function  

The I/O channel programmed with code 

off

 will not be used by the 

controller. Although without function, this channel is available through 
the serial communication as digital I/O (command 5 MODBUS).  

 

a1

a2

a3

a4

 – Alarm Outputs 

The  selected  channel  can  be  used  as  output  to  Alarms  1  to  4. 
Defines  that  the  programmed  I/O  channel  acts  as  alarm  outputs. 
Available for all the I/O channels.  

 

Lbd

 –Loop Break Detector function.  

Assigns  the  output  of  the  Loop  Break  Detector  alarm  to  an  I/O 
channel. Available to all I/O channels. 

 

(trL

 – PWM Control Output  

Defines the I/O channel to be used as the PWM control output (relay 
or digital pulse). Available for all the I/O channels. The digital pulse is 
available    on  I/O5  (standard)  or  on  I/O3  and  I/O4  (when  the  DIO 
optional is installed). Check the specifications of each channel.  

 

mAn

 - Digital Input with Auto/Manual function  

Defines the I/O channel as Digital Input with the function of switching 
the control mode between 

Automatic and Manual

. Available on I/O5 

(standard) or on I/O3 and I/O4 (when the DIO optional is installed). 

Closed

 = Manual control;  

Open

 = Automatic control 

 

rvn

 - Digital Input with 

RUN

 function 

Defines  channel  as  Digital  Input  with  the  function  of 
enabling/disabling the control and alarm outputs (“

RvN

”: 

YES

 / 

no

). 

Available for I/O5 or I/O3 and I/O4, when installed.  

Closed

 = outputs enabled 

Open

 = control and alarms output shut off 

 

rsp

 - Digital Input with Remote SP function  

Defines  channel  as  Digital  Input  with  the  function  of  selecting  the 
remote  SP  as  the  control  setpoint.  Available  for  I/O5  or  I/O3  and 
I/O4, when available.  

Closed

 = remote SP  

Open

 = uses main SP  

 

kprg

 - Digital Input with 

Hold Program

 function  

Defines channel as Digital Input with the function of commanding the 
execution of the selected setpoint profile 

program

. Available for I/O5 

or I/O3 and I/O4, when available.  

Closed

 = Enables execution of the program  

Open

 = Interrupts (freezes) execution of the program  

Note:

  Even  when  the  execution  of  the  program  is  interrupted,  the 

control output  remains active and controlling the process  at  the point 
(Setpoint) of interruption. The program will resume its normal execution 
starting from this same point when the digital input is closed. 

 

Pr 1

 - Digital Input with function to Execute Program 1  

Defines  the  IO  channel  as  Digital  Input  with  the  function  of 
commanding  the  execution  of  the  setpoing  profile 

program  1.

 

Available for I/O5 or I/O3 and I/O4, when available.  
Useful  function  for  switching  between  the  main 

setpoint

  and  a 

secondary one defined by the 

program 1

.  

Closed

 = selects program 1;  

Open

 = selects main 

setpoint

  

 

(.0.20

 –0-20 mA Control Output   

Available  for  I/O  5  only,  defines  the  channel  as  a  0-20  mA  control 
output. 

 

(.4.20 - 

4-20 mA Control Output  

Defines the channel as a 4-20 mA control output.  

 

P.0.20

 – 0-20 mA PV retransmission  

Available  for  I/O  5  only,  configures  the  channel  to  retransmit  the 
values of PV in 0-20 mA.  

 

P.4.20 

- 4-20 mA PV retransmission 

Available  for  I/O  5  only,  configures  the  channel  to  retransmit  the 
values of PV in 4-20 mA.  

 

s.0.20 – 

0-20 mA SP (Setpoint) retransmission  

Available  for  I/O  5  only,  configures  the  channel  to  retransmit  the 
values of SP in 0-20 mA.  

 

s.4.20 – 

4-20 mA SP (Setpoint) retransmission  

Available  for  I/O  5  only,  configures  the  channel  to  retransmit  the 
values of SP in 0-20 mA.  

CONFIGURATION OF ALARMS  

The  controller  has  4  independent  alarms.  These  alarms  can  be 
configured to operate with nine different functions, as shown in 

Table 3

 

off

 – Alarms turned 

off

.  

 

ierr

 – Open Sensor alarms - (

Loop Break

)  

The open sensor alarm acts whenever the input sensor is broken or 
badly connected.  

 

rs

 – Program Event Alarm 

Configures  the  alarm  to  act  in  (a)  specific  segment(s)  of  the 
programs of ramps and baselines to be created by the user. 

 

Rfai1

 – Burnt-out Resistance Alarm - (

Heat Break

Signals  that  the  heating  element  has  broken  up.  This  alarm  function 
requires the accessory Current transformer CT1.  Details for use of the 
option  “burnt-out  resistance”  are  found  in  the  specific  documentation 
that accompanies the product whenever this option is requested. 

 

lo

 – Alarm of Absolute Minimum Value 

Triggers when the value of measured PV is 

below

 the value defined 

for alarm Setpoint. 

 

ki

 – alarm of Absolute Maximum Value 

Triggers when the value of measured PV is 

above

 the value defined 

for alarm 

Setpoint

 

dif

 – Alarm of Differential Value 

In this function the parameters “

SPA1

”, “

SPA2

”,” 

SPA3

” and “

SPA4

” 

represent the Deviation of PV in relation to the SP.  
Using  the  Alarm  1  as  example:  for  Positive  SPA1  values,  the 
Differential  alarm  triggers  when  the  value  of  PV  is 

out

  of  the  range 

defined for: 

(SP – SPA1) to (SP + SPA1) 

For a negative SPA1 value, the Differential alarm triggers when the 
value of PV is 

within

 the range defined above:  

 

difl 

– Alarm of Minimum Differential Value

 

 

It triggers when the value of PV is below the defined point by:  

(SP – SPA1) 

Summary of Contents for N1200

Page 1: ...meters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 20 setpoint profile programs with 9 segments eac...

Page 2: ...xecution of the selected setpoint profile program Available for I O5 or I O3 and I O4 when available Closed Enables execution of the program Open Interrupts freezes execution of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starti...

Page 3: ...th this feature enabled the controller uses for display and control a value that corresponds to the square root of the applied input signal Available only for the inputs belonging to the group of linear analogic signals 0 20 mA 4 20 mA 0 50 mV 0 5 V and 0 10 V ANALOG RETRANSMISSION OF PV AND SP The analog output when not used for control purposes is available for retransmitting the PV and SP value...

Page 4: ... your supervisory software to conduct the MONITORING process Follow the procedure below to use the USB communication of the equipment Download the NConfig software from our website and install it on your computer The USB drivers necessary for operating the communication will be installed together with the software Connect the USB cable between the equipment and the computer The controller does not...

Page 5: ... product specifications Figure 6a I O3 or I O4 with output pulse for SSR Figure 6b I O5 with output pulse for SSR I O3 I O4 and I O5 can also be configured as digital outputs I O3 and I O4 provide a 5 Vdc output signal whereas I O5 a 12 Vdc signal An example of usage is shown in Figure 6a for the I O3 and in Figure 6b for the I O5 I O5 is electrically isolated from the sensor input OPERATION The c...

Page 6: ...ed 0 does not execute program 1 to 20 number of the program to be executed With enabled outputs RUN YES the program starts right after the program is selected p seg Screen for indication only When a ramp and soak program is active this parameter shows the number of the segment under execution from 1 to 9 t seg Screen for indication only When a ramp and soak program is in execution it shows the rem...

Page 7: ...r up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 ALARM HYSTERESIS Defines the difference between the value of PV at which the alarm is xya2 xya3 xya4 triggered and the value at which it is turned off in engineering units A1t1 A2t1 A3t1 A4t1 Alarm Time t1 Defines the temporization time t1...

Page 8: ...l I O 3 according to the Table 2 Io 4 Function of the channel I O 4 Selection of the function used in the channel I O 4 according to the Table 2 Io 5 Function of the channel I O 5 Selection of the function used in the channel I O 5 according to the Table 2 CALIBRATION CYCLE All of the input and output types are calibrated in the factory If a recalibration is required this should be carried out by ...

Page 9: ...des the parameters on the protected levels If no password is entered the parameters of the protected cycles can only be visualized The Access Code is defined by the user in the parameter Password Change PAS present in the Calibration level The factory default for the password code is 1111 Protection of the access code The protection system built into the controller blocks for 10 minutes the access...

Page 10: ...itiated by the controller whenever the control performance is worse than the one found after the previous tuning In order to activate the performance supervision and auto adaptative tuning the parameter ATUN must be adjusted for SELF RSLF or TGHT The controller s behavior during the auto adaptative tuning will depend on the worsening of the present performance If the maladjustment is small the tun...

Page 11: ...ignal that corresponds to a value a little lower than the upper limit of indication f Access the parameter inLC With the keys and adjust the display reading such as to match the applied signal Then press the P key Note When checking the controller calibration with a Pt100 simulator pay attention to the simulator minimum excitation current requirement which may not be compatible with the 0 170 mA e...

Page 12: ...Vdc 24 Vac 10 20 Maximum consumption 9 VA ENVIRONMENTAL CONDITIONS Operation Temperature 5 to 50 C Relative Humidity 80 max 30 ºC For temperatures above 30 ºC reduce 3 for each ºC Internal Use Category of installation II Degree of pollution 2 altitude 2000 m INPUT T C Pt100 voltage and current according to Table 1 Internal Resolution 32767 levels 15 bits Resolution of Display 12000 levels from 199...

Page 13: ... Relay in I O3 DIO Digital I Os in I O3 and I O4 HBD Burnt Out Resistance detection C Digital Communication Blank basic version without serial communication 485 RS485 Modbus protocol D Power Supply Blank basic version 100 to 240 Vac dc input 24V 12 to 24 Vdc 24 Vac input voltage WARRANTY Warranty conditions are available on our web site www novusautomation com warranty ...

Reviews: