Novus N1200 Instruction Manual Download Page 11

Controller N1200  

NOVUS AUTOMATION 

11 / 13 

The methods of 

automatic tuning

 and 

auto-adaptative tuning

 are 

appropriate for most of the industrial processes. However, there may 
be processes or even specific situations where the methods are not 
capable  to  determine  the  controller's  parameters  in  a  satisfactory 
way, resulting in undesired oscillations or even taking the process to 
extreme  conditions.  The  oscillations  themselves  imposed  by  the 
tuning  methods  may  be  intolerable  for  certain  processes.  These 
possible  undesirable  effects  must  be  considered  before  beginning 
the  controller's  use,  and  preventive  measures  must  be  adopted  in 
order to assure the integrity of the process and users. 
The “

TUNE

” signaling device will stay on during the tuning process. 

In  the  case  of  PWM  or  pulse  output,  the  quality  of  tuning  will  also 
depend on the cycle time adjusted previously by the user. 
If the tuning does not result in a satisfactory control, refer to 

Table 8 

for guidelines on how to correct the behavior of the process. 

PARAMETER 

VERIFIED PROBLEM 

SOLUTION 

Proportional Band 

Slow answer 

Decrease 

Great oscillation 

Increase 

Rate of Integration 

Slow answer 

Increase  

Great oscillation 

Decrease 

Derivative Time 

Slow answer or instability 

Decrease 

Great oscillation 

Increase 

Table 8 - 

Guidance for manual adjustment of the PID parameters 

MAINTENANCE 

PROBLEMS WITH THE CONTROLLER 

Connection  errors  and  inadequate  programming  are  the  most 
common errors found during the controller operation. A final revision 
may avoid loss of time and damages. 
The  controller  displays  some  messages  to  help  the  user  identify 
problems. 

MESSAGE 

DESCRIPTION OF THE PROBLEM 

----

 

Open input. No sensor or signal. 

Err1

 

Err6

 

Connection  and/or  configuration  errors.  Check 
the wiring and the configuration. 

Other  error  messages  may  indicate  hardware  problems  requiring 
maintenance  service.  When  contacting  the  manufacturer,  inform  the 
instrument serial number, obtained  by  pressing  the  key 

 

  for  more 

than 3 seconds. 

CALIBRATION OF THE INPUT 

All inputs are factory calibrated and recalibration should only be done 
by qualified personnel. If you are not familiar with these procedures 
do not attempt to calibrate this instrument. 
The calibration steps are: 

a)

  Configure the type of input to be calibrated. 

b)

  Configure  the  lower  and  upper  limits  of  indication  for  the 

maximum span of the selected input type. 

c)

  At  the  input  terminals  inject  a  signal  corresponding  to  a  known 

indication value a little above the lower display limit. 

d)

  Access the parameter “

inLC

”. With the keys 

 

 and 

 

 adjust the 

display reading such as to match the applied signal. Then press the 

 

 key. 

e)

  Inject a signal that corresponds to a value a little lower than the 

upper limit of indication. 

f)

  Access the parameter  “

inLC

”. With the keys 

 

 and 

 

 adjust 

the  display  reading  such  as  to  match  the  applied  signal.  Then 
press the 

 

 key. 

Note:

  When  checking  the  controller  calibration  with  a  Pt100 

simulator, pay attention to the simulator minimum excitation current 
requirement,  which  may  not  be  compatible  with  the  0.170  mA 
excitation current provided by the controller. 

ANALOG OUTPUT CALIBRATION 

 

Configure  I/O  5  for  the  current  output  to  be  calibrated,  be  it 

 control or retransmission. 

 

In the screen “

Ctrl

”, program manual mode (

man

). 

 

Connect a current meter to the analog output. 

 

Enter the calibration cycle with the correct password. 

 

Select  the  screen  “

ovLC

”.  Press  the  keys 

 

  and 

 

  for  the 

 controller  to  recognize  the  calibration  process  of  the  current 
 output.  

 

Read the current indicated on the current meter  and adjust the 

 parameter “

ovLC

” to indicate this current value (use the keys 

 

 

 and 

 

 

Select  the  screen  “

ovxC

”.  Press  the  keys 

 

  and 

 

  for  the 

 controller  to  recognize  the  calibration  process  of  the  current 
 output.  

 

Read the current indicated on the current meter and adjust the 

 parameter “

ovkC

” to indicate this current value  

 

Press  the  key

 

 

 

in  order  to  confirm  the  calibration  procedure 

 and return to the operating level. 

SERIAL COMMUNICATION 

The controller can be supplied with an asynchronous RS-485 digital 
communication  interface  for  master-slave  connection  to  a  host 
computer (master).  
The controller works as a slave only and all commands are started by 
the  computer  which  sends  a  request  to  the  slave  address.  The 
addressed unit sends back the requested reply. 
Broadcast commands (addressed to all indicator units in a multidrop 
network) are accepted but no reply is sent back in this case. 

CHARACTERISTICS 

 

Signals  compatible  with  RS-485  standard.  MODBUS  (RTU) 
Protocol.  Two  wire  connection  between  1  master  and  up  to  31 
(addressing up to 247 possible) instruments in bus topology. The 
communication  signals  are  electrically  insulated  from  the  rest  of 
the device;  

 

Maximum connection distance: 1000 meters. 

 

Time of disconnection for the controller: Maximum 2 ms after last 

byte

.  

 

Selectable  speed;  8  data  bits;  1 

stop

  bit;  selectable  parity  (no 

parity, pair or odd);  

 

Time  at  the  beginning  of  response  transmission:  maximum  100 
ms after receiving the command.  

 

There  is 

no  electrical  isolation

  between  serial  communication 

(RS485) and channel I/O5. 

The RS-485 signals are:  

D1  D  D +  B 

Bi-directional data line. 

 

Terminal 16 

D0 

 

D -  A 

Bi-directional inverted data line. 

 

Terminal 17 

Optional connection that improves the 

performance of the communication. 

 

Terminal 18 

GND 

CONFIGURATION OF PARAMETERS FOR SERIAL COMMUNICATION  

Two parameters must be configured for using the serial type: 

bavd: 

 Communication speed. 

prty: 

 Parity of the communication. 

addr:

  Communication address for the controller. 

 
 
 
 
 
 

D:

Summary of Contents for N1200

Page 1: ...meters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 20 setpoint profile programs with 9 segments eac...

Page 2: ...xecution of the selected setpoint profile program Available for I O5 or I O3 and I O4 when available Closed Enables execution of the program Open Interrupts freezes execution of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starti...

Page 3: ...th this feature enabled the controller uses for display and control a value that corresponds to the square root of the applied input signal Available only for the inputs belonging to the group of linear analogic signals 0 20 mA 4 20 mA 0 50 mV 0 5 V and 0 10 V ANALOG RETRANSMISSION OF PV AND SP The analog output when not used for control purposes is available for retransmitting the PV and SP value...

Page 4: ... your supervisory software to conduct the MONITORING process Follow the procedure below to use the USB communication of the equipment Download the NConfig software from our website and install it on your computer The USB drivers necessary for operating the communication will be installed together with the software Connect the USB cable between the equipment and the computer The controller does not...

Page 5: ... product specifications Figure 6a I O3 or I O4 with output pulse for SSR Figure 6b I O5 with output pulse for SSR I O3 I O4 and I O5 can also be configured as digital outputs I O3 and I O4 provide a 5 Vdc output signal whereas I O5 a 12 Vdc signal An example of usage is shown in Figure 6a for the I O3 and in Figure 6b for the I O5 I O5 is electrically isolated from the sensor input OPERATION The c...

Page 6: ...ed 0 does not execute program 1 to 20 number of the program to be executed With enabled outputs RUN YES the program starts right after the program is selected p seg Screen for indication only When a ramp and soak program is active this parameter shows the number of the segment under execution from 1 to 9 t seg Screen for indication only When a ramp and soak program is in execution it shows the rem...

Page 7: ...r up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 ALARM HYSTERESIS Defines the difference between the value of PV at which the alarm is xya2 xya3 xya4 triggered and the value at which it is turned off in engineering units A1t1 A2t1 A3t1 A4t1 Alarm Time t1 Defines the temporization time t1...

Page 8: ...l I O 3 according to the Table 2 Io 4 Function of the channel I O 4 Selection of the function used in the channel I O 4 according to the Table 2 Io 5 Function of the channel I O 5 Selection of the function used in the channel I O 5 according to the Table 2 CALIBRATION CYCLE All of the input and output types are calibrated in the factory If a recalibration is required this should be carried out by ...

Page 9: ...des the parameters on the protected levels If no password is entered the parameters of the protected cycles can only be visualized The Access Code is defined by the user in the parameter Password Change PAS present in the Calibration level The factory default for the password code is 1111 Protection of the access code The protection system built into the controller blocks for 10 minutes the access...

Page 10: ...itiated by the controller whenever the control performance is worse than the one found after the previous tuning In order to activate the performance supervision and auto adaptative tuning the parameter ATUN must be adjusted for SELF RSLF or TGHT The controller s behavior during the auto adaptative tuning will depend on the worsening of the present performance If the maladjustment is small the tun...

Page 11: ...ignal that corresponds to a value a little lower than the upper limit of indication f Access the parameter inLC With the keys and adjust the display reading such as to match the applied signal Then press the P key Note When checking the controller calibration with a Pt100 simulator pay attention to the simulator minimum excitation current requirement which may not be compatible with the 0 170 mA e...

Page 12: ...Vdc 24 Vac 10 20 Maximum consumption 9 VA ENVIRONMENTAL CONDITIONS Operation Temperature 5 to 50 C Relative Humidity 80 max 30 ºC For temperatures above 30 ºC reduce 3 for each ºC Internal Use Category of installation II Degree of pollution 2 altitude 2000 m INPUT T C Pt100 voltage and current according to Table 1 Internal Resolution 32767 levels 15 bits Resolution of Display 12000 levels from 199...

Page 13: ... Relay in I O3 DIO Digital I Os in I O3 and I O4 HBD Burnt Out Resistance detection C Digital Communication Blank basic version without serial communication 485 RS485 Modbus protocol D Power Supply Blank basic version 100 to 240 Vac dc input 24V 12 to 24 Vdc 24 Vac input voltage WARRANTY Warranty conditions are available on our web site www novusautomation com warranty ...

Reviews: