The master password is made up by the last three digits of the serial 

number of the controller added to the number 9000. 
As an example, for the equipment with serial number 07154321, the 

master password is 9 3 2 1. 

PROGRAMS OF RAMP AND SOAK 

This feature allows the creation of Ramp and Soak Setpoint Profiles 

(Programs). Up to 7 different profiles with 7 segments each can be 

programmed. Longer profiles of up to 49 segments can be created by 

linking 2 or more profiles together. 
The figure below displays a profile model: 

 

Figure 8 - Example of a Ramp and Soak program 

Once a profile is defined and selected for execution, the  controller 

starts to generate the SP profile automatically in accordance with the 

elaborated program. 
To execute a profile with fewer segments just program 0 (zero) for 

the time intervals that follow the last segment to be executed. 

 

SV 

Time 

T1 

T2 

T3 

SP0 

SP1 

SP2 

SP3 

T4=0 

 

Figure 9 - Program example with few segments 

The program tolerance “

ptol

” defines the maximum deviation 

between PV and SP for the execution of the profile. If this deviation is 

exceeded, the program will be halted until the deviation falls to within 

the tolerance band. 
Programming 0 (zero) in the “

Ptol

” parameter disables the program 

tolerance and the profile execution will continue regardless of the PV 

value (time priority as opposed to SP priority). 

LINK OF PROGRAMS 
It is possible to create a more complex program (up to 49 segments), 

joining  two or more programs. This way, at the end of a program 

execution the controller immediately starts to run the next one,  as 

indicated in the parameter “

LP

". 

To force the controller to run a given program or many programs 

continuously, it is only necessary to link a program to itself or the last 

program to the first. 

 

SV 

time 

T1 

T2 

T3 

T4 

T5 

T1 

T2 

T3 

T4 

SP0 

SP1 

SP2 

SP3 

SP4 

SP5 / SP0 

SP1  SP2 

SP3 

SP4 

Program 1 

Program 2 

 

Figure 10 – Example of interlinked programs 

EVENT 
The Event Alarm function associates the alarms to specific segments 

of a program. The information of which alarms are to be activated or 

deactivated is given in parameters “ 

PE1

“ to “ 

PE7

. Press the   and 

 keys until the desired alarm numbers are displayed. 

The Event Alarm requires that the Alarm function be configured as 

rS

 “. 

Notes

1.

 

If 

PtoL

 is different than zero, the controller will wait for the PV to 

reach the first program set point SP0 in order to start the 

program execution. Otherwise, it will start promptly. 

2.

 

Should any power failure occur, the controller resumes the 

program execution at the beginning of the segment where it was 

interrupted.   

DETERMINATION OF PID PARAMETERS 

During the automatic tuning the process is controlled in ON / OFF 

mode in the programmed SP. Depending on the process behavior, 

oscillations may occur above or below the Setpoint. The automatic 

tuning may take many minutes to the concluded, particularly in slow 

processes.  
When the parameter ATUN is altered to YES, the automatic tuning 

is immediately initiated by the controller (provided RUN=YES, 

otherwise it will wait until this condition becomes true).  
Some recommendations for the automatic tuning process are:  

 

avto

 = YES: make sure the controller is set for automatic control 

mode. 

 

Disable Ramp & Soak programs configuring 

Pr n

  = 0.  (the 

automatic tuning algorithm expects a stable Setpoint value) 

 

Select a  Setpoint  that is close or equal to the desired process 

Setpoint. 

 

Enable the automatic tuning (

atvn

 = YES). 

 

Enable outputs if not yet enabled (

rvn

 = YES). 

The “TUNE” indicator on the display stays lit until the completion of 

the automatic tuning process. 
For control output types relay or pulse, the automatic tuning 

calculates the longest suitable period (cycle time 

(t

) for the PWM 

output. The cycle time period may be reduced if  the process 

experiences some oscillation.  When driving a SSR, it’s 

recommended to set 

(t

 = 1 s. 

If the automatic tuning does not result in a satisfactory control, refer 

to Table 7 for guidelines on how to correct the behavior of the 

process. 

PARAMETER 

VERIFIED PROBLEM 

SOLUTION 

Proportional Band 

Slow answer 

Decrease 

Great oscillation 

Increase 

Rate of Integration 

Slow answer 

Increase 

Great oscillation 

Decrease 

Derivative Time 

Slow answer or instability 

Decrease 

Great oscillation 

Increase 

Table 7 - Guidance for manual adjustment of the PID parameters 

MAINTENANCE 

PROBLEMS WITH THE CONTROLLER 
Connection errors and inadequate programming are the most 

common errors found during the controller operation. A final revision 

may avoid loss of time and damages. 
The controller displays some messages to help the user identify 

problems. 

MENSSAGE 

DESCRIPTION OF THE PROBLEM 

----

 

Open input. No sensor or signal.   

Err1

 

Err6

 

Connection and/or configuration errors. 

Check the wiring and the configuration. 

Other error messages may indicate hardware problems requiring 

maintenance service. When contacting the manufacturer, inform the 

instrument serial number, obtained by pressing the key 

 

 for more 

than 3 seconds. 

 

 

Summary of Contents for N1100

Page 1: ...ts all available in the standard model Self tuning of PID parameters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmab...

Page 2: ...on of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starting from this same point when the digital input is closed Pr 1 Digital input with function to Execute Program 1 Defines the channel as Digital Input with the function of com...

Page 3: ...for retransmitting the PV and SP values in 0 20 or 4 20 mA This analog output is electrically isolated from other inputs and outputs The analog output signal is scalable with the output range defined by the values programmed in the parameters SPLL and SPkL It is possible to obtain a voltage output by installing a resistor shunt 550 Ω max to the current output terminals terminals 7 and 8 The actual...

Page 4: ...e USB in any other type of connection is possible but requires a careful analysis by the person responsible for installing it When MONITORING for long periods of time and with connected inputs and outputs we recommend using the RS485 interface which is available or optional in most of our products INSTALLATION CONNECTIONS The controller must be fastened on a panel following the sequence of steps d...

Page 5: ...hts continuously A1 A2 A3 and A4 indicators signalize the occurrence of alarm situation P P Key used to walk through the menu parameters Back Key used to retrocede parameters Increment key and Decrement key allow altering the values of the parameters When the controller is powered on its firmware version is presented for 3 seconds after which the controller starts normal operation The values of PV...

Page 6: ...as Bias function Allows adding a percentage value between 100 and 100 to the MV control output The value 0 zero disables the function ovll Output Low Limit Lower limit for the control output Minimum percentage value assumed by the control output when in automatic mode and in PID Typically configured with 0 0 ovkl Output High Limit Upper limit for the control output Maximum percentage for the contr...

Page 7: ...es the signal type for the remote SP 0 20 current of 0 20 mA 4 20 current of 4 20 mA 0 5 voltage of 0 5 V 0 10 voltage of 0 10 V Parameter displayed when remote SP is enabled rsll Remote SP Low Limit REMOTE SETPOINT LOW LIMIT used in conjunction with the rSxL scales the remote SP input defining the initial value in the remote SP indication range Parameter displayed when remote SP is enabled rskl R...

Page 8: ...FIGURATION The controller provides means for protecting the parameters configurations not allowing modifications to the parameters values avoiding tampering or improper manipulation The parameter Protection PROt in the Calibration level determines the protection strategy limiting the access to particular levels as shown by the table below Protection Level Protected Cycles 1 Only the Calibration le...

Page 9: ...t point SP0 in order to start the program execution Otherwise it will start promptly 2 Should any power failure occur the controller resumes the program execution at the beginning of the segment where it was interrupted DETERMINATION OF PID PARAMETERS During the automatic tuning the process is controlled in ON OFF mode in the programmed SP Depending on the process behavior oscillations may occur a...

Page 10: ...urrent output Read the current indicated on the current meter and adjust the parameter ovLC to indicate this current value use the and keys Select the screen ovxC Press the and keys for the controller to recognize the calibration process of the current output Read the current indicated on the current meter and adjust the parameter ovxC to indicate this current value Press the key in order to confi...

Page 11: ... s back panel ELECTROMAGNETIC COMPATIBILITY EN 61326 1 1997 and EN 61326 1 A1 1998 SAFETY EN61010 1 1993 and EN61010 1 A2 1995 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 mm FRONT PANEL IP65 polycarbonate UL94 V 2 CASE IP20 ABS PC UL94 V 0 PROGRAMMABLE CYCLE OF PWM 0 5 up to 100 seconds STARTS UP OPERATION after 3 ...

Reviews: