Novus N1100 Instruction Manual Download Page 11

N1100 Controller 

NOVUS AUTOMATION 

11/11 

All registers are 16 bit signed integers

.

 

Address  Parameter 

Register Description 

0000  Active SP  Read:  Active control SP (main SP, from 

ramp and soak or from remote SP). 
Write: to main SP. 
Range: from 

spll

 to 

spkl

0001 

PV 

Read: Process Variable. 
Write: Not allowed. 
In case of temperature reading, the value 

read is always multiplied by 10, 

independently of 

dppo

 value. 

0002 

MV 

Read: Output Power in Automatic or 

Manual mode. 
Write: only allowed when in Manual mode. 
Range: 0 to 1000 (0.0 to 100.0 %). 

SPECIFICATIONS 

DIMENSIONS: ........................................ 48 x 48 x 110 mm (1/16 DIN) 

 ............................................................ Approximate Weight: 150 g 

CUTOUT IN THE PANEL: ................... 45.5 x 45.5 mm (+0.5 -0.0 mm) 
POWER SUPPLY: ..................... 100 to 240 Vac/dc (±10 %), 50/60 Hz 

Optional 24V: ..................... 12 to 24 Vdc / 24 Vac (-10 % / +20 %) 

 Maximum consumption: ........................................................  9 VA 

ENVIRONMENTAL CONDITIONS

Operation Temperature: ................................................ 5 to 50 

°

Relative Humidity: ...................................... 80 % max. up to 30 ºC 

For temperatures above 30 ºC, reduce 3 % for each ºC  
Internal Use; Category of installation II, Degree of pollution 2; 

altitude < 2000 m. 

INPUT ............. T/C, Pt100, voltage and current (according to Table 1) 

Internal Resolution: ................................... 32767 levels (15 bits) 

Resolution of Display: ...... 12000 levels (from -1999 up to 9999) 

Rate of input reading: .................................... up to 5 per second 

Precision: .. Thermocouples JKT, E: 0.25 % of the 

span 

±

1 ºC 

 ................... Thermocouples NRSB: 0.25 % of the 

span 

±

3 ºC 

 ................................................................ Pt100: 0.2 % of the 

span

 

 ............................. 4-20 mA, 0-50 mV, 0-5 Vdc: 0.2 % of the 

span

 

Input Impedance: . 0-50 mV, Pt100 and thermocouples: >10 M

 

 ................................................................................. 0-5 V: >1 M

 

 ................................................ 4-20 mA: 15 

 (+2 Vdc @ 20 mA) 

Measurement of Pt100: .............. Three wires type, (

α

=0.00385) 

with compensation for cable length, excitation current of 0.170 mA. 
All input and output types are factory-calibrated. Thermocouples 

according to standard NBR 12771 / 99, RTD’s NBR 13773 / 97; 

ANALOGICAL OUTPUT (I/O5):...... 0-20 mA or 4-20 mA, 550 

 max. 

 ..... 31000 levels, Isolated, for control or retransmission of PV and SP. 
CONTROL OUTPUT

 2 Relays SPST-NA (I/O1 and I/O2): 1.5 A / 240 Vac, general use 

 .......................... 1 Relay SPDT (I/O3): 3 A / 250 Vac, general use 

 .......................... Voltage pulse for SSR (I/O5): 10 V max. / 20 mA 

 ............. Voltage pulse for SSR (I/O3 and I/O4): 5 V max. / 20 mA 

INPUT OF REMOTE SP: ........................ 0-20 mA, 4-20 mA, 5 V, 10 V 

The Remote SP mA inputs require an external resistor of 100 R 

connected directly to the terminals 9 and 10 of the controller's back 

panel.  
ELECTROMAGNETIC COMPATIBILITY: ............... EN 61326-1:1997  

and EN 61326-1/A1:1998 
SAFETY: .......................... EN61010-1:1993 and EN61010-1/A2:1995 
USB INTERFACE:  2.0, CDC class  (virtual communications port), 

MODBUS RTU protocol. 
SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6.3 

mm; 
FRONT PANEL
: IP65, polycarbonate - UL94 V-2;  
CASE
: IP20, ABS+PC UL94 V-0; 

PROGRAMMABLE CYCLE OF PWM: 0.5, up to 100 seconds; 
STARTS UP OPERATION
: after 3 seconds connected to the power 

supply; 
CERTIFICATIONS
: .....................................  CE / UL (FILE: E300526) 

IDENTIFICATION 

N1100 - 

3R - 

485 - 

24V 

A:  Controller model:    

N1100

B:  Optional I/Os: 

Blank:    (basic version, without I/O3 nor I/O4); 

3R      (SPDT Relay in I/O3); 

DIO     (Digital I/Os in I/O3 and I/O4); 

C:  Digital Communication: 

Blank    (basic version, without serial communication); 

485     (RS485, Modbus protocol) 

D:  Power Supply: 

Blank    (basic version, 100 to 240 Vac/dc); 

24V     (12 to 24 Vdc / 24 Vac input voltage). 

SAFETY INFORMATION 

Any control system design should take into account that any part of 

the system has the potential to fail. This product is not a protection or 

safety device and its alarms are not intended to protect against 

product failures. Independent safety devices should be always 

provided if personnel or property are at risk. 
Product performance and specifications may be affected by its 

environment and installation. It’s user’s responsibility to assure 

proper grounding, shielding, cable routing and electrical noise 

filtering, in accordance with local regulations, EMC standards and 

good installation practices. 

SUPPORT AND MAINTENANCE 

This product contains no serviceable parts inside. Contact our local 

distributor in case you need authorized service. For troubleshooting, 

visit our FAQ at m 

www.novus.com.br

LIMITED WARRANTY AND LIMITATION OF LIABILITY 

NOVUS warrants to the original purchaser that this product is free 

from defects in material and workmanship under normal use and 

service within one (1) year from the date of shipment from factory or 

from its official sales channel to the original purchaser. 
NOVUS liability under this warranty shall not in any case exceed the 

cost of correcting defects in the product or of supplying replacement 

product as herein provided and upon the expiration of the warranty 

period all such liability shall terminate. 
For complete information on warranty and liability limitations, check 

appropriate section in our web site: 

www.novusautomation.com/warranty

 

Summary of Contents for N1100

Page 1: ...ts all available in the standard model Self tuning of PID parameters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmab...

Page 2: ...on of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starting from this same point when the digital input is closed Pr 1 Digital input with function to Execute Program 1 Defines the channel as Digital Input with the function of com...

Page 3: ...for retransmitting the PV and SP values in 0 20 or 4 20 mA This analog output is electrically isolated from other inputs and outputs The analog output signal is scalable with the output range defined by the values programmed in the parameters SPLL and SPkL It is possible to obtain a voltage output by installing a resistor shunt 550 Ω max to the current output terminals terminals 7 and 8 The actual...

Page 4: ...e USB in any other type of connection is possible but requires a careful analysis by the person responsible for installing it When MONITORING for long periods of time and with connected inputs and outputs we recommend using the RS485 interface which is available or optional in most of our products INSTALLATION CONNECTIONS The controller must be fastened on a panel following the sequence of steps d...

Page 5: ...hts continuously A1 A2 A3 and A4 indicators signalize the occurrence of alarm situation P P Key used to walk through the menu parameters Back Key used to retrocede parameters Increment key and Decrement key allow altering the values of the parameters When the controller is powered on its firmware version is presented for 3 seconds after which the controller starts normal operation The values of PV...

Page 6: ...as Bias function Allows adding a percentage value between 100 and 100 to the MV control output The value 0 zero disables the function ovll Output Low Limit Lower limit for the control output Minimum percentage value assumed by the control output when in automatic mode and in PID Typically configured with 0 0 ovkl Output High Limit Upper limit for the control output Maximum percentage for the contr...

Page 7: ...es the signal type for the remote SP 0 20 current of 0 20 mA 4 20 current of 4 20 mA 0 5 voltage of 0 5 V 0 10 voltage of 0 10 V Parameter displayed when remote SP is enabled rsll Remote SP Low Limit REMOTE SETPOINT LOW LIMIT used in conjunction with the rSxL scales the remote SP input defining the initial value in the remote SP indication range Parameter displayed when remote SP is enabled rskl R...

Page 8: ...FIGURATION The controller provides means for protecting the parameters configurations not allowing modifications to the parameters values avoiding tampering or improper manipulation The parameter Protection PROt in the Calibration level determines the protection strategy limiting the access to particular levels as shown by the table below Protection Level Protected Cycles 1 Only the Calibration le...

Page 9: ...t point SP0 in order to start the program execution Otherwise it will start promptly 2 Should any power failure occur the controller resumes the program execution at the beginning of the segment where it was interrupted DETERMINATION OF PID PARAMETERS During the automatic tuning the process is controlled in ON OFF mode in the programmed SP Depending on the process behavior oscillations may occur a...

Page 10: ...urrent output Read the current indicated on the current meter and adjust the parameter ovLC to indicate this current value use the and keys Select the screen ovxC Press the and keys for the controller to recognize the calibration process of the current output Read the current indicated on the current meter and adjust the parameter ovxC to indicate this current value Press the key in order to confi...

Page 11: ... s back panel ELECTROMAGNETIC COMPATIBILITY EN 61326 1 1997 and EN 61326 1 A1 1998 SAFETY EN61010 1 1993 and EN61010 1 A2 1995 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 mm FRONT PANEL IP65 polycarbonate UL94 V 2 CASE IP20 ABS PC UL94 V 0 PROGRAMMABLE CYCLE OF PWM 0 5 up to 100 seconds STARTS UP OPERATION after 3 ...

Reviews: