Novus N1100 Instruction Manual Download Page 3

N1100 Controller 

NOVUS AUTOMATION 

3/11 

PROMPT 

TYPE 

ACTION 

Off 

Disabled 

Output is not used as alarm. 

Ierr 

Sensor Break 

(input Error) 

Activated when the input signal of PV is 

interrupted, out of the range limits or Pt100 

in short-circuit.  

Rs 

Event 

(ramp and Soak)

 

Can be activated at a specific segment of 

program. 

Lo 

 Minimum value 

(Low) 

 

SPAn 

PV 

 

Ki 

Maximum value 

(High) 

 

SPAn 

PV 

 

Difl 

Minimum 

Differential  

(differential 

Low) 

Positive SPAn             Negative SPAn 

 

SV 

PV 

SV - SPAn 

 

SV 

PV 

SV - SPAn 

 

Difk 

Maximum 

Differential  

(differential 

High) 

 

SV 

PV 

SV + SPAn 

 

 

SV 

PV 

SV + SPAn 

 

Positive SPAn 

Ngative SPAn      

Dif 

Differential 

(differential) 

 

SV 

PV 

SV + SPAn 

 

SV - SPAn 

 

 

 

SV 

PV 

SV - SPAn 

 

SV + SPAn 

 

 

Positive SPAn 

Nagative SPAn      

Table 3 – Alarm functions 

Where SPAn refers to Setpoints of Alarm “

SPA1

”, “

SPA2

”, “

SPA3

” 

and “

SPA4

”. 

ALARM TIMER MODES 
The controller alarms can be configured to perform 4 timer modes: 

 

Continuous (normal mode).

 

 

One pulse with defined duration;

 

 

Delayed activation; 

 

Repetitive pulses; 

The illustrations in Table 4 show the behavior of the alarm output for 

various combinations of times T1 and T2. The timer functions can be 

configured in parameters 

A1t1

A1t2

A2t1

 and 

A2t2

OPERATION 

T 1 

T 2 

ACTION 

Normal 

operation 

Alarm Event

Alarm

Output

 

Activation for 

a defined time 

1 s to 

 6500 s 

Alarm Event

Alarm

Output

T1

 

Activation with 

delay 

1 s to 

6500 s 

Alarm Event

Alarm

Output

T2

 

Intermittent 

activation 

1 s to 

6500 s 

1 s to 

6500 s 

Alarm Event

Alarm

Output

T1

T2

T1

 

Table 4 - Temporization Functions for the Alarms 

The LEDs associated to the alarms will light when the alarm 

condition is recognized, not following the actual state of the output, 

which may be temporarily OFF because of the temporization. 

ALARM INITIAL BLOCKING 
The initial blocking option inhibits the alarm from being recognized 

if an alarm condition is present when the controller is first energized. 

The alarm will be enabled only after the occurrence of a non-alarm 

condition followed by a new occurrence for the alarm. 
The initial blocking is useful, for instance, when one of the alarms is 

configured as a minimum value alarm, causing the activation of the 

alarm soon upon the process start-up, an occurrence that may be 

undesirable.  
The initial blocking is disabled for the sensor break alarm function. 

SQUARE ROOT EXTRACTION 
When the input type is configured as 

SQRT

  the controller assumes 

the input as a 4-20 mA while extracting the square root of the applied 

input signal. 

ANALOG RETRANSMISSION OF PV AND SP  
The analog output, when not used for control purposes, is available 

for retransmitting the PV and SP values in 0-20 or 4-20 mA. This 

analog output is electrically isolated from other inputs and outputs.  
The analog output signal is scalable, with the output range defined by 

the values programmed in the parameters “

SPLL

” and “

SPkL

”. 

It is possible to obtain a voltage output by installing a resistor shunt 

(550 

Ω 

max.) to the current output terminals (terminals 7 and 8). The 

actual resistor value depends on the desired output voltage span. 
There is no electrical isolation  between serial communication 

(RS485) and channel I/O5. 

SOFT-START 
The soft-start feature avoids abrupt variations in the power delivered 

to the load regardless of the system power demand. 
This is accomplished by defining a limiting ramp for the control output. 

The output is allowed to reach maximum value (100 %) only after the 

time programmed in the soft-start parameter has elapsed.   
The Soft-start function is generally used in processes that require slow 

start-up, where the instantaneous application of 100 % of the available 

power to the load may cause damages to parts of the system.  
In order to disable this function, the soft-start parameter must be 

configured with 0 (zero). 

REMOTE SETPOINT 
The controller can have its Setpoint value defined by an analog, 

remotely generated signal. This feature is enabled through the 

channels I/O3, I/O4 or I/O5 when configured as digital inputs and 

configured with the function 

rsp

 (Remote SP selection) or through 

the parameter 

E.rsp

. The remote Setpoint input accepts the signals 

0-20 mA, 4-20 mA, 0-5 V and 0-10 V.  
For the signals of 0-20 and 4-20 mA, a shunt resistor of 100 

 is 

required between terminals, as shown in Figure 4c

CONTROL MODE 
The controller can operate in two different manners: Automatic mode 

or Manual mode. 
The parameter “

avto

” defines the control mode to be adopted. 

In Automatic mode the controller defines the amount of power to be 

applied on the process.  
In Manual mode the user himself defines this amount of power. The 

user can then adjust the MV percentage while displaying PV/MV

PID AUTOMATIC MODE 
For the Automatic mode, there are two different strategies of control: 

PID automatic control and ON/OFF automatic control. 
PID control has its action based on a control algorithm that takes into 

account the deviation of PV with respect to SP, the rate of change of 

PV and the steady state error. These parameters are particular to a 

system and can be obtained automatically by the controller’s Auto 

Tune feature (

Atvn

 parameter). 

On the other hand, the ON/OFF  control (obtained when 

Pb

=0) 

operates with 0 % or 100 % of power, when PV deviates from SP. 
The determination of parameters 

Pb

Ir

 and 

Dt

 is described in the 

item DETERMINATION OF PID PARAMETERS of this manual. 

Summary of Contents for N1100

Page 1: ...ts all available in the standard model Self tuning of PID parameters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmab...

Page 2: ...on of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starting from this same point when the digital input is closed Pr 1 Digital input with function to Execute Program 1 Defines the channel as Digital Input with the function of com...

Page 3: ...for retransmitting the PV and SP values in 0 20 or 4 20 mA This analog output is electrically isolated from other inputs and outputs The analog output signal is scalable with the output range defined by the values programmed in the parameters SPLL and SPkL It is possible to obtain a voltage output by installing a resistor shunt 550 Ω max to the current output terminals terminals 7 and 8 The actual...

Page 4: ...e USB in any other type of connection is possible but requires a careful analysis by the person responsible for installing it When MONITORING for long periods of time and with connected inputs and outputs we recommend using the RS485 interface which is available or optional in most of our products INSTALLATION CONNECTIONS The controller must be fastened on a panel following the sequence of steps d...

Page 5: ...hts continuously A1 A2 A3 and A4 indicators signalize the occurrence of alarm situation P P Key used to walk through the menu parameters Back Key used to retrocede parameters Increment key and Decrement key allow altering the values of the parameters When the controller is powered on its firmware version is presented for 3 seconds after which the controller starts normal operation The values of PV...

Page 6: ...as Bias function Allows adding a percentage value between 100 and 100 to the MV control output The value 0 zero disables the function ovll Output Low Limit Lower limit for the control output Minimum percentage value assumed by the control output when in automatic mode and in PID Typically configured with 0 0 ovkl Output High Limit Upper limit for the control output Maximum percentage for the contr...

Page 7: ...es the signal type for the remote SP 0 20 current of 0 20 mA 4 20 current of 4 20 mA 0 5 voltage of 0 5 V 0 10 voltage of 0 10 V Parameter displayed when remote SP is enabled rsll Remote SP Low Limit REMOTE SETPOINT LOW LIMIT used in conjunction with the rSxL scales the remote SP input defining the initial value in the remote SP indication range Parameter displayed when remote SP is enabled rskl R...

Page 8: ...FIGURATION The controller provides means for protecting the parameters configurations not allowing modifications to the parameters values avoiding tampering or improper manipulation The parameter Protection PROt in the Calibration level determines the protection strategy limiting the access to particular levels as shown by the table below Protection Level Protected Cycles 1 Only the Calibration le...

Page 9: ...t point SP0 in order to start the program execution Otherwise it will start promptly 2 Should any power failure occur the controller resumes the program execution at the beginning of the segment where it was interrupted DETERMINATION OF PID PARAMETERS During the automatic tuning the process is controlled in ON OFF mode in the programmed SP Depending on the process behavior oscillations may occur a...

Page 10: ...urrent output Read the current indicated on the current meter and adjust the parameter ovLC to indicate this current value use the and keys Select the screen ovxC Press the and keys for the controller to recognize the calibration process of the current output Read the current indicated on the current meter and adjust the parameter ovxC to indicate this current value Press the key in order to confi...

Page 11: ... s back panel ELECTROMAGNETIC COMPATIBILITY EN 61326 1 1997 and EN 61326 1 A1 1998 SAFETY EN61010 1 1993 and EN61010 1 A2 1995 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 mm FRONT PANEL IP65 polycarbonate UL94 V 2 CASE IP20 ABS PC UL94 V 0 PROGRAMMABLE CYCLE OF PWM 0 5 up to 100 seconds STARTS UP OPERATION after 3 ...

Reviews: