Novus N1100 Instruction Manual Download Page 10

N1100 Controller 

NOVUS AUTOMATION 

10/11 

CALIBRATION OF THE INPUT 
All inputs are factory calibrated and recalibration should only be done 

by qualified personnel. If you are not familiar with these procedures 

do not attempt to calibrate this instrument. 
The calibration steps are: 
a)  Configure the type of input to be calibrated. 
b)  Configure the lower and upper limits of indication for the 

maximum span of the selected input type. 

c)  At the input terminals inject a signal corresponding to a known 

indication value a little above the lower display limit. 

d)  Access the parameter “

inLC

”. With the keys 

 

 and 

 

, adjust 

the display reading such as to match the applied signal. Then 

press the

 

 key. 

e)  Inject a signal that corresponds to a value a little lower than the 

upper limit of indication. 

f)  Access the parameter “

inkC

”. With the keys 

 

 and 

 

, adjust 

the display reading such as to match the applied signal. Then 

press the

 

 key. 

Note:  When checking the controller calibration with a Pt100 

simulator, pay attention to the simulator minimum excitation current 

requirement, which may not be compatible with the 0.170 mA 

excitation current provided by the controller. 

REMOTE SETPOINT CALIBRATION 
All inputs are factory calibrated and recalibration should only be done 

by qualified personnel. If you are unfamiliar with these procedures do 

not attempt to calibrate this instrument. 
If the recalibration or the remote Setpoint is required, proceed as 

follows.  
a)  Configure the remote Setpoint type to be calibrated. 
b)  Program  the low and high limits of the remote Setpoint to the 

minimum and maximum values respectively. 

c)  Apply to the remote Setpoint input a known signal that is slightly 

above the low limit of that input.  

d)  At the parameter “

rsL(

” use the  

 

 and 

 

  keys to show in 

the display the corresponding value of the applied signal. Then 

press the 

 

 key. 

e)  Apply to the remote Setpoint input a known signal that is slightly 

below the high limit of that input. 

f)  At the parameter “

rsk(

” use the  

 

 and 

 

 keys to show in the 

display the corresponding value of the applied signal. Then press 

the 

 

 key

ANALOG OUTPUT CALIBRATION 

 

Configure I/O 5 for the current output to be calibrated, be it control 

or retransmission. 

 

In the screen “

Ctrl

”, program manual mode (

man

). 

 

Connect a current meter at the analog output. 

 

Enter the calibration cycle with the correct password. 

 

Select the screen “

ovLC

”. Press the 

 

  and  

 

  keys  for the 

controller to recognize the calibration process of the current 

output.  

 

Read the current indicated on the current meter  and adjust the 

parameter “

ovLC

” to indicate this current value (use the 

 

  and  

 

  keys) 

 

Select the screen “

ovxC

”. Press the 

 

  and 

 

  keys  for the 

controller to recognize the calibration process of the current 

output.  

 

Read the current indicated on the current meter and adjust the 

parameter “

ovxC

” to indicate this current value  

 

Press the   key in order to confirm the calibration procedure and 

return to the operating level. 

SERIAL COMMUNICATION 

The controller can be supplied with an asynchronous RS-485 digital 

communication interface for master-slave connection to a host 

computer (master).  
The controller works as a slave only and all commands are started by 

the computer which sends a request to the slave address. The 

addressed unit sends back the requested reply. 
Broadcast commands (addressed to all indicator units in a multi drop 

network) are accepted but no reply is sent back in this case. 

CHARACTERISTICS 

 

Signals compatible with RS-485 standard. MODBUS (RTU) 

Protocol. Two wire connection between 1 master and up to 31 

(addressing up to 247 possible) instruments in bus topology. The 

communication signals are electrically insulated from the rest of 

the device; 

 

Maximum connection distance: 1000 meters. 

 

Time of disconnection for the controller: Maximum 2 ms after last 

byte. 

 

Selectable speed; 8 data bits; 1 stop bit; selectable parity (no 

parity, pair or odd); 

 

Time at the beginning of response transmission: maximum 100 

ms after receiving the command. 

 

There is no electrical isolation  between serial communication 

(RS485) and channel I/O5 

The RS-485 signals are: 

D1  D  D +  B  Bi-directional data line. 

Terminal 16 

D0 

 D -  A  Bi-directional inverted data line. 

Terminal 17 

Optional connection that improves the 

performance of the communication. 

Terminal 18 

GND 

CONFIGURATION OF PARAMETERS FOR SERIAL 

COMMUNICATION 

Three parameters must be configured for using the serial type: 

bavd

:  Communication speed. 

prty

:  Parity of the communication. 

addr

:  Communication address for the controller. 

REDUCED REGISTERS TABLE FOR SERIAL 

COMMUNICATION 

COMMUNICATION PROTOCOL 
The MOSBUS RTU slave is implemented. All configurable parameters 

can be accessed for reading or writing through the communication port. 

Broadcast commands are supported as well (address 0). 
The available Modbus commands are: 

03 - 

Read Holding Register

 

06 - 

Preset Single Register

 

05 - 

Force Single Coil

 

16 - 

Preset Multiple Register

 

HOLDING REGISTERS TABLE 
Follows a description of the usual communication registers. For full 

documentation download the Registers Table for Serial 

Communication  in the N1100 section of our web site – 

www.novusautomation.com

 

D:

Summary of Contents for N1100

Page 1: ...ts all available in the standard model Self tuning of PID parameters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmab...

Page 2: ...on of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starting from this same point when the digital input is closed Pr 1 Digital input with function to Execute Program 1 Defines the channel as Digital Input with the function of com...

Page 3: ...for retransmitting the PV and SP values in 0 20 or 4 20 mA This analog output is electrically isolated from other inputs and outputs The analog output signal is scalable with the output range defined by the values programmed in the parameters SPLL and SPkL It is possible to obtain a voltage output by installing a resistor shunt 550 Ω max to the current output terminals terminals 7 and 8 The actual...

Page 4: ...e USB in any other type of connection is possible but requires a careful analysis by the person responsible for installing it When MONITORING for long periods of time and with connected inputs and outputs we recommend using the RS485 interface which is available or optional in most of our products INSTALLATION CONNECTIONS The controller must be fastened on a panel following the sequence of steps d...

Page 5: ...hts continuously A1 A2 A3 and A4 indicators signalize the occurrence of alarm situation P P Key used to walk through the menu parameters Back Key used to retrocede parameters Increment key and Decrement key allow altering the values of the parameters When the controller is powered on its firmware version is presented for 3 seconds after which the controller starts normal operation The values of PV...

Page 6: ...as Bias function Allows adding a percentage value between 100 and 100 to the MV control output The value 0 zero disables the function ovll Output Low Limit Lower limit for the control output Minimum percentage value assumed by the control output when in automatic mode and in PID Typically configured with 0 0 ovkl Output High Limit Upper limit for the control output Maximum percentage for the contr...

Page 7: ...es the signal type for the remote SP 0 20 current of 0 20 mA 4 20 current of 4 20 mA 0 5 voltage of 0 5 V 0 10 voltage of 0 10 V Parameter displayed when remote SP is enabled rsll Remote SP Low Limit REMOTE SETPOINT LOW LIMIT used in conjunction with the rSxL scales the remote SP input defining the initial value in the remote SP indication range Parameter displayed when remote SP is enabled rskl R...

Page 8: ...FIGURATION The controller provides means for protecting the parameters configurations not allowing modifications to the parameters values avoiding tampering or improper manipulation The parameter Protection PROt in the Calibration level determines the protection strategy limiting the access to particular levels as shown by the table below Protection Level Protected Cycles 1 Only the Calibration le...

Page 9: ...t point SP0 in order to start the program execution Otherwise it will start promptly 2 Should any power failure occur the controller resumes the program execution at the beginning of the segment where it was interrupted DETERMINATION OF PID PARAMETERS During the automatic tuning the process is controlled in ON OFF mode in the programmed SP Depending on the process behavior oscillations may occur a...

Page 10: ...urrent output Read the current indicated on the current meter and adjust the parameter ovLC to indicate this current value use the and keys Select the screen ovxC Press the and keys for the controller to recognize the calibration process of the current output Read the current indicated on the current meter and adjust the parameter ovxC to indicate this current value Press the key in order to confi...

Page 11: ... s back panel ELECTROMAGNETIC COMPATIBILITY EN 61326 1 1997 and EN 61326 1 A1 1998 SAFETY EN61010 1 1993 and EN61010 1 A2 1995 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 mm FRONT PANEL IP65 polycarbonate UL94 V 2 CASE IP20 ABS PC UL94 V 0 PROGRAMMABLE CYCLE OF PWM 0 5 up to 100 seconds STARTS UP OPERATION after 3 ...

Reviews: