RNPP-301

CONTROLS DESCRIPTION AND DIMENSIONS DIAGRAM

control for minimum voltage threshold, Umin (%); 

1. 

control for maximum voltage threshold, Umax (%); 

2. 

control for peak phase imbalance threshold, PI (%); 

3. 

control of trip delay setting for Umin, Tmin (sec); 

4. 

control of trip delay setting for the mains voltage faults, Toff (sec); 

5. 

control for automatic reset delay setting, Ton (sec); 

6. 

green LED signal that the mains voltage is present, ON; 

7. 

green LED signal that load is energized, Load; 

8. 

red  LEDs  signal  for  the  mains  voltage  fault/  magnetic  starter  (MS)  power  contacts 

9. 

monitoring, Fault; 

MS power contacts monitoring terminals; 

10. 

input contacts; 

11. 

output contacts; 

12. 

      13  terminals for the mode selection: line/phase voltage monitoring.

A RNPP-301 VOLTAGE CONTROL RELAY IS DESIGNED FOR:

monitoring of the tolerable RMS phase/line voltage level (at the option of user) with independent setting 

1. 

adjustments for the minimum/maximum voltage thresholds; 

monitoring of the correct phase sequence and phase “non-coincidence” (the phases are supposed to be 

2. 

coinciding when a load is energized not from two different phases but instead from one and the same 

phase); 

monitoring of three phase lines for voltage presence and the mains voltage symmetry with adjustable 

3. 

phase imbalance setting; 

monitoring of the magnetic starter power contacts status at no-load and under load; 

4. 

the load (

415

V/50Hz) de-energization with user-set trip delay (Toff) through the opening the magnetic 

5. 

starter coil power circuit (A.C and D.C. electric circuit switching) when fault conditions occur; 

the mains voltage quality monitoring after the relay had tripped and did reset automatically with the user-

6. 

set reset delay (Ton) upon the voltage parameters regeneration; 

all fault conditions (not switching of the magnetic starter power contacts is included) are displayed by 

7. 

special LEDs indicating the specific cause of the occurring voltage fault in the mains.

1. APPLICATION

1

2

THE 10-11, 12-13 OUTPUT CONTACTS SPECIFICATION

Summary of Contents for RNPP-301

Page 1: ...RNPP 301 Three phase voltage and phase monitoring relay NOVATEK ELECTRO LTD Research and Manufacturing Company www novatek electro in TECHNICAL DESCRIPTION AND USERS MANUAL...

Page 2: ...setting 1 adjustments for the minimum maximum voltage thresholds monitoring of the correct phase sequence and phase non coincidence the phases are supposed to be 2 coinciding when a load is energized...

Page 3: ...0 11 12 13 In the dead status of the relay a voltage is not applied to the relay the relay is not connected the 12 13 are the N O contacts and the 10 11 are N C contacts After the relay has been conne...

Page 4: ...m switched current of output contacts A 5 Output contacts life under load 5A operations under load 1A operations 100 000 1 mln Protection degree of apparatus terminal block IP40 IP20 Operating tempera...

Page 5: ...to the relay front panel Umin trip threshold for the minimum allowable voltage of rated voltage Umax trip threshold for the maximum allowable voltage of rated voltage PI phase line voltage imbalance...

Page 6: ...relay should be connected in parallel to load according to the diagrams shown below The RNPP 301 wiring diagram with selectable mode of operation For line voltage monitoring mode that is not necessari...

Page 7: ...nnect the relay output contacts the 10 11 12 13 terminals to the MS coil power circuit the control circuit 4 To connect the 1 2 3 terminals to the MS output contacts If there is no need in the MS powe...

Page 8: ...RNPP 301 NOVovatek LTD C 30 Patparganj Industrial Area 1st floor Delhi 110092 INDIA Email info novatek electro in Tel 91 11 42143253 Fax 91 11 43010600 www novatek electro in...

Reviews: