This  Operation  Manual  is  intended  to  familiarize  you  with  the  design,  the  requirements  for  safety, 

operation  and  maintenance  procedures  of  the  power  limiting  relay 

ОМ-163  (hereinafter  referred  to  as  the 

"device", 

ОМ-163).

 

The device meets the requirements of the following: 

  IEC 60947-1, Low-voltage switchgear and controlgear; Part 1; General rules; 

  IEC  60947-6-2,  Low-voltage  switchgear  and  controlgear;  Part  6-2;  Multiple  function  equipment;  Control  and 

protective switching devices; 

  CISPR  11,  Electromagnetic  compatibility;  Industrial,  scientific  and  medical  RF  equipment;  Electromagnetic 

interference characteristics; Limits and methods of measurements; 

  IEC  61000-4-2,  Electromagnetic  compatibility;  Part  4-2; 

Testing  and  measurement  techniques

Electrostatic 

discharge immunity test

 

Harmful substances in amounts exceeding maximum permissible concentrations are not available

 

 

Terms and abbreviations: 

 

controlled  parameter

  is  the  parameter  selected  by  the  user  (total  power,  active  power,  reactive 

power, load current, mains voltage), in case of exceeding of which the device open contacts 1 - 3 (Fig. 1);

 

 

AR

 is automatic reclosing delay time which is counted after opening contacts 1 - 3 (Fig. 1); 

 

display

 - three-digit seven-segment indicator; 

 

ACB

 is automatic circuit breaker. 

 

1. SERVICE 

 

1.1. Device service 

ОМ-163 is designed to protect (disconnect) the equipment connected to it in the following cases: 

  exceeding the threshold value of the controlled parameter; 

  deviation of the mains voltage from the set values; 

  excess of the temperature of the contact group

 

(85 

°С). 

 

The ranges of measured and controlled parameters are given in Table 1. 

 

Table 1

 

– The ranges of measured and controlled parameters 

 

Description 

Controlled range 

Measured range 

Total power, kVA 

– 14 

– 14 

Active power, kW 

– 14 

– 14 

Reactive power, kVAr 

– 14 

– 14 

Load current, A

 

– 63 

0.5 

– 63 

Input voltage, V 

160 

– 280 

120 

– 350 

 

ОМ-163 opens contacts 1 - 3, if the controlled parameter exceeds the limits set by the user. 
The user sets the maximum power, off-delay time and AR time using the buttons (it. 2, 3, 4, Fig. 1).  
 
ОМ-163

 

can be used as: 

  power consumption limiting relay; 

  voltage relay; 

  digital multi-meter (indication of total, active, reactive power, current consumption and mains voltage). 

ОМ-163 is powered by the circuit that feeds the load. 
ОМ-163 displays the value of the parameters and the status of the relay using indicators. 

 

1.2.

 

Controls and overall dimensions of 

ОМ-163 

Controls and overall dimensions are shown in Fig. 1. 

 

1.3. Operation conditions

 

The device is intended for operation in the following conditions: 

  Ambient temperature: from minus 35 to +55 

°С; 

  Atmospheric pressure: from 84 to 106.7 kPa; 

  Relative humidity (at temperature of +25 

°С): 30 … 80 %. 

 

If  the  temperature  of  the  device  after  transportation  or  storage  differs  from  the  ambient  temperature  at 

which it is supposed to be operated, then before connecting to the mains keep the device under the operating 
conditions within two hours (because of condensation may be on the device elements). 

 

ATTENTION! The device is not intended for operation in the following conditions: 

  Significant vibration and shocks; 

Summary of Contents for OM-163

Page 1: ...t and production complies with requirements ISO 9001 2015 Dear Customer NOVATEK ELECTRO Ltd Company thanks you for purchasing our products You will be able to use properly the device after carefully s...

Page 2: ...AL ELEMENTS OF THE DEVICE ATTENTION THE DEVICE IS NOT INTENDED FOR THE LOAD COMMUTATION IN CASE OF SHORT CIRCUIT THEREFORE THE DEVICE SHOULD BE OPERATED IN THE ELECTRICAL MAINS PROTECTED BY THE CIRCUI...

Page 3: ...rameter deviation of the mains voltage from the set values excess of the temperature of the contact group 85 The ranges of measured and controlled parameters are given in Table 1 Table 1 The ranges of...

Page 4: ...reen LED Q kVAr is on when the display shows the reactive power value 12 green LED I A is on when the display shows the actual value of load current 13 green LED U V is on when the display shows the v...

Page 5: ...able 3 Relay Output Contacts Specifications Description Value Max current at voltage of 220 V os 1 63 Max power when contacts are closed kVA 14 Max switching power os 0 4 kVA 1 4 Max permissible AC vo...

Page 6: ...lue of the mains voltage is within the limits set by the user the device closes the contacts 1 3 Fig 1 the LED On will light up the LED Off will off The display shows the measured parameter that was s...

Page 7: ...press the button OK Similarly set the middle and lower order digits of the password After entering the value in the low order digit of the password the device will store the password and exit to the...

Page 8: ...s moment Contacts 1 3 are opened LED On goes out LED Off goes out The display shows the AR time in minutes and one of the LEDs blinks it 9 13 Fig 1 corresponding to the parameter over which the protec...

Page 9: ...AINS 4 2 Recommended frequency of maintenance is every six months 4 3 Maintenance Procedure 1 Check the connection reliability of the wires if necessary clamp with the force specified in Table 2 2 Vis...

Reviews: