background image

~ 8 ~ 

ОМ-163

                                                                                                                               

NOVATEK-ELECTRO

 



Maximum voltage 
threshold 

Values from 230 to 280 V. 





AR voltage delay time  Values from 1 to 900 s. 





Default displayed 
parameter 

 

«



» – Total power; 

 

«



» – Active power; 

 

«



» – Reactive power; 

 

«



» – Consumption current; 

 

«



» – Mains voltage. 





Parameter display 
mode 

 

«



» – the parameter value is displayed 

continuously; 

 

«



»  –  the  parameter  value  is  displayed  for  15 s 

(then the default setting is displayed); 

 

«



»  –  continuous  cyclic  displaying  of  parameter 

values. 





Password setting 

Permitted values from 000 to 999 



 

3.2. The device use 
3.2.1. 

Operating condition

 

The device can be in one of the following conditions: 

  "

Normal o

peration

"; 

  "

P

arameter

 s

etting

"; 

 

Fault

”. 

The device is in the "

Normal operation

" condition if: 

  the controlled parameter does not exceed the value set by the user; 

  AR time countdown has been completed. 

The parameter values are changed (Table 4) in the "

Parameter settings

" condition. 

In the "

Fault

" condition: at the time of the fault, the device opens contacts 1 to 3 (the 

On

 LED is off, the 

Off 

LED lights up continuously). 

 

3.2.2. The device operation

 

3.2.2.1. Power and current control

 

If  the  value  of  the  controlled  parameter  is  exceeded  (menu  item

 



”,  Table 4),  the  off-delay  time 

countdown begins (parameter “



”, Table 4). At the same time, the LED 

Off

 (it. 7, Fig. 1) and LED 

On

 (it. 6, 

Fig. 1) are flashing alternately. 

After completion of the off-delay time countdown (if the controlled parameter has not accepted value up to 

this moment): 

  Contacts 1 

– 3 are opened; 

  LED 

On 

goes out; 

  LED 

Off 

goes out; 

  The display shows the AR time in minutes and one of the LEDs blinks (it. 9-13, Fig. 1), corresponding 

to the parameter, over which the protection has tripped. 

If the AR countdown relative to power or current is inhibited (parameter “



”, value “



”, Table 4), the 

device does not turn on the load, the display will show “



”.To turn on the load, you should turn off the OM-

163 power and turn it on again, or set the AR time (parameter 



”, Table  4) as 580 min or less. 

Note:

 when sel

ecting the controlled parameter (menu item “



”, Table 4) the other parameters of this item are not 

controlled.

 

 

3.2.2.2. Voltage control 

If the mains voltage exceeds the thresholds set by the user (parameter 



” or “



”, Table 4), the load 

off-delay  time  countdown  begins  (fixed  off-delay,  Table 2).  At  the  same  time,  the  LED 

Off

  (it. 7,  Fig. 1)  and 

LED 

On

 (it. 6, Fig. 1) are flashing alternately. After completion of the off-delay time countdown (if the voltage 

has not accepted value up to this moment): 

  Contacts 1 

– 3 are opened; 

  LED 

On 

goes out; 

 

the display alternately shows the voltage AR time in seconds and the actual value of the mains voltage, 

the  LED 

Off 

lights  up  continuously  (it. 7,  Fig. 1).  At  the  same  time,  when  the  AR  time  relative  to  voltage  is 

displayed, the dot in the low-order display is on and the indicator (it. 13, Fig. 1) does not light, and when the 
voltage value is displayed, the indicator (it. 13, Fig. 1) lights up.

 

After  the  AR  time  countdown  relative  to  voltage  is  over,  the  contacts  1  -  3  are  closed,  if  the  mains  voltage 
value is acceptable (the LED 

On 

lights up, the LED 

Off 

goes off). 

Summary of Contents for OM-163

Page 1: ...t and production complies with requirements ISO 9001 2015 Dear Customer NOVATEK ELECTRO Ltd Company thanks you for purchasing our products You will be able to use properly the device after carefully s...

Page 2: ...AL ELEMENTS OF THE DEVICE ATTENTION THE DEVICE IS NOT INTENDED FOR THE LOAD COMMUTATION IN CASE OF SHORT CIRCUIT THEREFORE THE DEVICE SHOULD BE OPERATED IN THE ELECTRICAL MAINS PROTECTED BY THE CIRCUI...

Page 3: ...rameter deviation of the mains voltage from the set values excess of the temperature of the contact group 85 The ranges of measured and controlled parameters are given in Table 1 Table 1 The ranges of...

Page 4: ...reen LED Q kVAr is on when the display shows the reactive power value 12 green LED I A is on when the display shows the actual value of load current 13 green LED U V is on when the display shows the v...

Page 5: ...able 3 Relay Output Contacts Specifications Description Value Max current at voltage of 220 V os 1 63 Max power when contacts are closed kVA 14 Max switching power os 0 4 kVA 1 4 Max permissible AC vo...

Page 6: ...lue of the mains voltage is within the limits set by the user the device closes the contacts 1 3 Fig 1 the LED On will light up the LED Off will off The display shows the measured parameter that was s...

Page 7: ...press the button OK Similarly set the middle and lower order digits of the password After entering the value in the low order digit of the password the device will store the password and exit to the...

Page 8: ...s moment Contacts 1 3 are opened LED On goes out LED Off goes out The display shows the AR time in minutes and one of the LEDs blinks it 9 13 Fig 1 corresponding to the parameter over which the protec...

Page 9: ...AINS 4 2 Recommended frequency of maintenance is every six months 4 3 Maintenance Procedure 1 Check the connection reliability of the wires if necessary clamp with the force specified in Table 2 2 Vis...

Reviews: