6.7.2 Load Cabinet Configuration Files
Before you begin: Save the cabinet configuration file (*.rcfgx or *.rcfg) to the local PC.
Step 1 Run NovaLCT and choose
Tools
>
Controller Cabinet Configuration File Import
.
Step 2 On the displayed page, select the currently used Ethernet port, click
Add Configuration File
to select and
add a cabinet configuration file.
Step 3 Click
Save the Change to HW
to save the change to the controller.
Figure 6-21 Importing configuration file of controller cabinet
Note
Configuration files of irregular cabinets are not supported.
6.7.3 Set Alarm Thresholds
Set the alarm thresholds for device temperature and voltage. When a threshold is exceeded, its corresponding
icon on the home screen will be flashing, instead of displaying the value.
: Voltage alarm, icon flashing. Voltage threshold range: 3.5 V to 7.5 V
: Temperature alarm, icon flashing. Temperature threshold range:
–20°C to +85°C
: Voltage and temperature alarms at the same time, icon flashing
Note
When there are no temperature or voltage alarms, the home screen will display the backup status.
6.7.4 Image Settings
Adjust the color of the output image. You can see the adjustment result on the LED screen in real time.
Table 6-2 Image parameters
Parameter
Description
Color temperature
Range: 4000 K to 9500 K; step: 100
Red/Green/Blue
Range: 0 to 255; step: 1