Notifier SFP-400B Manual Download Page 2

WARNING:

 This equipment generates, uses, and can radiate radio frequency

energy and if not installed and used in accordance with the instruction manual, may

cause interference to radio communications. It has been tested and found to comply

with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC

Rules, which is designed to provide reasonable protection against such interference

when operated in a commercial environment. Operation of this equipment in a

residential area is likely to cause interference, in which case the user will be required

to correct the interference at his own expense.

Installation Precautions 

 

-   Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING 

Several different sources of power can be connected to the fire alarm

control panel.

  Disconnect all sources of power before servicing.  Control unit and

associated equipment may be damaged by removing and/or inserting cards,

modules, or interconnecting cables while the unit is energized.  Do not attempt to

install, service, or operate this unit until this manual is read and understood.

CAUTION - 

System Reacceptance Test after Software Changes:

     To ensure

proper system operation, this product must be tested in accordance with NFPA 72-

1993 Chapter 7 after any programming operation or change in site-specific software.

Reacceptance testing is required after any change, addition or deletion of system

components, or after any modification, repair or adjustment to system hardware or

wiring.

All components, circuits, system operations, or software functions known to be

affected by a change must be 100% tested.  In addition, to ensure that other

operations are not inadvertently affected, at least 10% of initiating devices that are

not directly affected by the change, up to a maximum of 50 devices, must also be

tested and proper system operation verified.

This system  

meets NFPA requirements for operation at 0-49

O

 C/32-120

O

 F

and at a relative humidity of 85% RH (non-condensing) at 30

C/86

O

 F.

However, the useful life of the system's standby batteries and the electronic

components may be adversely affected by extreme temperature ranges and

humidity.  Therefore, it is recommended that this system and its peripherals be

installed in an environment with a nominal room temperature of 15-27

O

 C/60-80

O

F.

Verify that wire sizes are adequate

 for all initiating and indicating device loops.

Most devices cannot tolerate more than a 10% I.R. drop from the specified device

voltage.

Like all solid state electronic devices,

 this system may operate erratically or can

be damaged when subjected to lightning induced transients.  Although no system is

completely immune from lightning transients and interferences, proper grounding will

reduce susceptibility.

 Overhead or outside aerial wiring is not recommended, due to

an increased susceptibility to nearby lightning strikes.

  Consult with the Technical

Services Department if any problems are anticipated or encountered.

Disconnect AC power and batteries

 prior to removing or inserting circuit boards.

Failure to do so can damage circuits.

Remove all electronic assemblies

 prior to any drilling, filing, reaming, or punching

of the enclosure. When possible, make all cable entries from the sides or rear.

Before making modifications, verify that they will not interfere with battery,

transformer, and printed circuit board location.

Do not tighten screw terminals

 more than 9 in-lbs.  Over tightening may damage

threads, resulting in reduced terminal contact pressure and difficulty with screw

terminal removal.

This system 

contains static-sensitive components.  Always ground yourself with a

proper wrist strap before handling any circuits so that static charges are removed

from the body.  Use static suppressive packaging to protect electronic assemblies

removed from the unit.

Follow the instructions

 in the installation, operating, and programming manuals.

These instructions must be followed to avoid damage to the control panel and

associated equipment. FACP operation and reliability depend upon proper

installation.

Fire Alarm System Limitations

While installing a fire alarm system may make lower insurance

rates possible, it is not a substitute for fire insurance!

An automatic fire alarm system

 - typically made up of smoke detectors, heat

detectors, manual pull stations, audible warning devices, and a fire alarm control

with remote notification capability can provide early warning of a developing fire.

Such a system, however, does not assure protection against property damage or

loss of life resulting from a fire.

Any fire alarm system

 may fail for a variety of reasons:

Smoke detectors

 may not sense fire where smoke cannot reach the detectors such

as in chimneys, in walls, or roofs, or on the other side of closed doors.  Smoke

detectors also may not sense a fire on another level or floor of a building.  A second

floor detector, for example, may not sense a first floor or basement fire.  Further-

more, all types of smoke detectors - both ionization and photoelectric types, have

sensing limitations.  No type of smoke detector can sense every kind of fire caused

by carelessness and safety hazards like smoking in bed, violent explosions,

escaping gas, improper storage of flammable materials, overloaded electrical

circuits, children playing with matches, or arson.

IMPORTANT! 

 Smoke detectors  

must be installed in the same room as the

control panel and in rooms used by the system for the connection of alarm

transmission wiring, communications, signaling, and/or power.

  If detectors are

not so located, a developing fire may damage the alarm system, crippling its

ability to report a fire.

Audible warning devices

 such as bells  may not alert people if these devices are

located on the other side of closed or partly open doors or are located on another

floor of a building.

A fire alarm system

 will not operate without any electrical power.  If AC power fails,

the system will operate from standby batteries only for a specified time.

Rate-of-Rise heat detectors

 may be subject to reduced sensitivity over time.  For

this reason, the rate-of-rise feature of each detector should be tested at least once

per year by a qualified fire protection specialist.

Equipment used in the system

 may not be technically compatible with the control.

It is essential to use only equipment listed for service with your control panel.

Telephone lines

 needed to transmit alarm signals from a premise to a central

monitoring station may be out of service or temporarily disabled.

The most common cause

 of fire alarm malfunctions, however, is inadequate

maintenance.  All devices and system wiring should be tested and maintained by

professional fire alarm installers following written procedures supplied with each

device.  System inspection and testing should be scheduled monthly or as required

by National and/or local fire codes. Adequate written records of all inspections should

be kept.

FCC Warning

Canadian Requirements

This digital apparatus does not exceed the Class A limits for radiation noise

emissions from digital apparatus set out in the Radio Interference Regulations of the

Canadian Department of Communications.

Le present appareil numerique n'emet pas de bruits radioelectriques depassant les

limites applicables aux appareils numeriques de la classe A prescrites dans le

Reglement sur le brouillage radioelectrique edicte par le ministere des Communica-

tions du Canada.

Technical Publishing

        Document PRECAULG.P65  12/31/96

Summary of Contents for SFP-400B

Page 1: ...O N T R O L P A N E L Doc 15124 G1 ECN 97 192 ZONE 1 ZONE 2 ZONE 3 ZONE 4 AC POWER SYSTEM ALARM ALARM TEST SUPERVISORY SYSTEM TROUBLE TONE SILENCE ALARM SILENCE ALARM ACTIVATE RESET CIRCUIT TROUBLE P...

Page 2: ...yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the uni...

Page 3: ...LEDs 11 2 2 Control Switches 12 2 3 Zone Status LEDs 12 2 4 Supervisory 13 2 5 Zone Disable 13 2 6 Last Event Recall 13 3 0 Installation Procedure 14 3 1 General 14 3 2 Initiating Device Circuits 15 3...

Page 4: ...Code Underwriters Laboratories Documents UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors Single and Multiple Station UL 228 Door Closers Holders for Fire Protective Signaling Systems UL...

Page 5: ...o Optional supervised remote annunciator RZA 4X Requires LED Interface Module 4XLM o Optional digital communicator NOTI FIRE 911A 911AC Complies with NFPA 72 1993 Central Station and Remote Station P...

Page 6: ...SFP 400B 15124 G1 06 24 97 6 Figure 1 0 1 SFP 400B Installation Diagram...

Page 7: ...panel and trip coil 3 ohms Municipal Box wiring can leave the building For Remote Station service NFPA 72 1993 Remote Station Fire Alarm System Maximum load for each circuit 10 mA Reverse polarity out...

Page 8: ...provide for off premises monitoring of a fire alarm control panel The 911AC is triggered by the alarm trouble and orsupervisorycontactsreceived fromthecontrolpanelandconvertstheminto digitaltransmiss...

Page 9: ...stor Notification Appliance Circuits Power limited circuitry Maximum allowable voltage drop due to wiring 2 VDC Normal Operating Voltage 24 VDC Total current available to all external devices 2 25 amp...

Page 10: ...SFP 400B 15124 G1 06 24 97 10 Cabinet 3 047 Backbox 3 0 Door 14 218 Backbox 14 Door 14 718 Backbox 14 5 Trim Ring TR 2 R Figure 1 5 1 Cabinet Dimensions...

Page 11: ...LED that flashes for any trouble condi tion including those associated with option boards CIRCUIT TROUBLE Yellow LED that flashes for trouble conditions on output circuits notification ALARM SILENCED...

Page 12: ...until 60 seconds after the initiation of the alarm Alarm Activate The ALARM ACTIVATE switch may be used to activate Notification Appliance Circuits ALARM ACTIVATE also activates the System Alarm relay...

Page 13: ...status will be lost The Zone Disable routine makes use of the four panel switches as follows 1 Press and hold in the TONE SILENCE switch 2 With the TONE SILENCE switch held in press in sequence the A...

Page 14: ...be in accordance with the National and or Local codes for fire alarm systems UL Power Limited Wiring Requirements Power limited and non power limited circuit wiring must remain separated in the cabine...

Page 15: ...when connecting polarized devices 2 All circuits are supervised and power limited 3 Leave Dummy Load provided on all unused circuits TB4 4 7K 1 2 Watt part 71252 4 7K 1 2 Watt part 71252 4 7K 1 2 Wat...

Page 16: ...detector current in alarm IR is the end of line relay current 24 VDC Common IDC IDC Red Black 24 VDC Common IDC IDC UL listed 24 VDC Four Wire Smoke Detectors UL Listed 4 7K 1 2 Watt ELR TB2 3 4 TB4 7...

Page 17: ...ate only one Notification Appliance Circuit Circuit 2 cut jumper SUPV 1 To disable both NotificationApplianceCircuits cutjumper SUPV2forsupervisoryconditions Seefigurebelowforjumper location If a 4XZM...

Page 18: ...50 60 Hz 1 2 amps and primary power required for the SFP 400BE panel is 220 240 VAC 50 Hz 0 6 amps Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code...

Page 19: ...7 and J8 only 4XTM and 4XZM modules can be installed in either location Battery Power Observe polarity when connecting battery Connect battery cable to J9 on the main board using the plug in connector...

Page 20: ...main board Carefully align the pins on the main board with J1 and or J2 on the option board Press firmly on the option board until it locks in place on the standoffs Affix the terminal identification...

Page 21: ...h the disconnect switch down to prevent unwanted activation of the Municipal Box during testing of the control panel The Disconnect LED will remain illuminated while the Municipal Box is disconnected...

Page 22: ...ower limited and power limited wiring must have a minimum distance of 0 25 wire to wire If this module is used to drive non power limited and power limited circuits please follow the instructions belo...

Page 23: ...m Trouble Sound Resound 1 2 3 4 5 6 7 8 The wiring of this module must follow the requirements as specified in the General Section UL Power Limited Wiring Requirements LED Interface Module 4XLM Remote...

Page 24: ...ing Circuit under test will sound piezo and light Zone Trouble LED Switch 1 Alarm Verification If selected alarm signals that occur on any zone will be subjected to a two minute verification period t...

Page 25: ...ith AC power off System Trouble LED and audible trouble sounder on If using a 4XZM Zone Relay Module X 8 mA If using a 4XTM Transmitter Module add 11 mA If using the Reverse Polarity Alarm output add...

Page 26: ...s within 48 hours 7 amp hour minium Batteries larger than 12 amp hour will require a UL listed battery cabinet e g Notifier BB 17 Table A 2 Ampere Hour AH Calculations amps X hours Enter 0 20 for 5 mi...

Page 27: ...Transmitter Module for connection to a compatible listed Local Energy Municipal Box This unit must be installed as outlined in Figure B 1 NFPA 72 1993 Remote Station Protective Signaling System 4XTM T...

Page 28: ...snotsuitableforseparatetransmission of sprinkler supervisory or trouble conditions Note Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms 4XTM Transmitter Module...

Page 29: ...aving compatible ratings All connections are power limited and supervised with the exception of the reverse polarity loop Supervision of the loop is the responsibility of the receiver Fire Lite RS82 9...

Page 30: ...by load shall be 125 mA The Standby by Battery Requirement 24VDC 7AH Max To Central Station Common Trouble Supervisory Alarm Red Black STD DACT NOTE on STD DACT Place jumper over pins 2 3 marked DACT...

Page 31: ...and 911AC must be in conduit less than 20 in length in the same room NOTE on STD DACT Place jumper over pins 2 3 marked DACT when employ ing a DACT This directs the control panel to transmit all troub...

Page 32: ...12VDC Battery 2 7AH Red Black 120 VAC HOT Neutral Ground Black White Green yellow yellow 1 2 TB2 TB3 RESET SILENCE MODE ALARM AC POWER TROUBLE SUPERVISORY Primary Active Secondary Active Kissoff J2 J...

Page 33: ...ormer model ULT STK NO 1000391 listed Class 2 12 V 10 VA See Potter Electric Signal Company Bulletin 748 3 This control panel transmitter arrangement can be employed for NFPA 72 1993 Proprietary Prote...

Page 34: ...e v o m e R y m m u d l l a t s n I d e l l a t s n i f i s e l u d o m l a n o i t p o V 2 1 r o f K 2 2 V 4 2 r o f K 7 4 R L E 2 s d a e l y r e t t a b h t o b e v o m e R 3 e m i t e h t t a t i...

Page 35: ...SFP 400B 15124 G1 06 24 97 35 NOTES...

Page 36: ...ng constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all...

Reviews: