Section 1 Overview
PN 50702:B2 4/14/03
9
Specifications
The APS-6R is compatible with the NFS-3030, NFS-640, AM2020,
AFP-1010, AFC-600, AFP-400, AFP-300, AFP-200, System 5000,
and System 500 control panels. Specifications for the APS-6R are:
Table 2 APS-6R Specifications
Electrical Specifications
AC Primary Input Power
Wire Size: #14 AWG with
600 VAC insulation
120 VAC, 60 Hz, 2.5 A
240 VAC, 50 Hz, 1.2 A
24 VDC Secondary Input Power
(lead-acid batteries only)
25 mA DC standby current
16 mA DC standby current (with AC fail delay
operating)
Note:
The APS-6R is not equipped with a battery charger. Batteries are charged
by the system power supply.
24 VDC output power
Circuit 1
Circuit 2
Circuit 3
Total 6 A (4 A continuous)
3 A @24 VDC power-limited (+10, –15%)
3 A @24 VDC power-limited (+10, –15%)
6 A @24 VDC non power-limited (+10, –15%)
Fuses
F1 (AC supervision)
F2 (battery supervision)
250 VAC, 4A, 3 AG, slow blow
32 VAC, 10 A, 3 AG, slow blow
Trouble supervision bus
J3 output
J4 input
Note:
J3 and J4 can be
interchanged.
Form A contact (open collector)
Form A contact (open collector)
Loss of AC Indication
Immediate indication (default)
8 or 16 hour delay
Mechanical Specifications
Size of APS-6R
Inches:6.09 x 4.23. x 2.92 (mm:154.7 x 107.4 x 74.2)
Cabinets for mounting
CAB-3/CAB-4
Series for NFS-3030, NFS-640,
AM2020, AFP-1010, AFC-600, AFP-300,
AFP-400, and System 5000 control panels.
CAB-400AA
for AFP-300 and AFP-400 control
panels; accepts one APS-6R.
CAB-600AA
for AFC-600 control panels;
accepts one APS-6R.
AFP-200
backbox; accepts one APS-6R.
CAB-500
Can mount one APS-6R.
Note:
An optional module (such as an ICM) without an expansion card can mount above
an APS-6R in a CHS-4 Series chassis, a CAB-500, CAB-600AA and a CAB-400AA.
www.PDF-Zoo.com
firealarmresources.com