NOSHOK KING-GAGE ES2 5501 Installation And Operation Manual Download Page 8

Page 8

ES2 Electronic Liquid Level Transmitter 

 

 

 

 

 

EX-1845

Power Requirement (14–40 Vdc)

The ES2 transmitter requires a source of DC power for op-
eration. Minimum excitation voltage must be no less than 
14 Vdc. Any receiver installed on the signal loop (meters, 
data loggers, controllers, etc.) must be taken into account 
when determining the required power supply voltage to be 
used. The internal resistance of each device added together 
represents the total “load” residing on the signal loop circuit.

Load Capacity = (Supply Voltage - 14) 
 (OHMS) 

 

.02

Load Capacity at Supplied Voltage

KING-GAGE tank processors and LevelBAR provide 24 Vdc 
excitation to power the signal loop circuit. (If the application 
requirement exceeds 500-ohms, an external power supply 
of appropriate voltage will be required.)

ES2 Signal Connection

 20 Vdc 

24 Vdc 

28 Vdc 

32 Vdc

300 ohms 

500 ohms 

700 ohms 

900 ohms

The external connector of the ES2 transmitter affords an 
impermeable barrier against moisture infiltration of the 
transmitter housing. This connector receptacle has a metric 
M12 screw collar and is intended for plug type molded 
cable assemblies designed for 4-pole signal termination. 
Our ES2 transmitter package also includes a molded M12 
cable (32 ft / 10 m) to simplify installation and ensure a 
sealed connection at the unit—this molded cable meets 
IP68 standards for ingress protection.

NOTE: Avoid installing sensitive measuring equipment, or 
wire carrying low level signals, near sources of electrical and 
magnetic noise, such as breakers, transformers, motors, 
SCR drives, welders, fluorescent lamp controllers, or relays. 
Use twisted pair wiring to reduce magnetic noise pickup. 
Never run signal-carrying wires in the same conduit that 
carries power lines, relay contact leads, or other high-level 
voltages or currents.

The signal output is transmitted through 4-20 mA current 
loops that are low impedance electric circuits. Long cabling 
runs can increase the susceptibility for higher levels of noise 
to be transferred to the current loop circuit. Also, inter-
mittent EMI or RFI with a changing frequency or intensity 
may induce interference on the transmitted output signal.

Brown

: + SIGNAL (+ V power)

White

: - SIGNAL (- or common)

Blue

: SHIELD (ground)

Black (Not Used)

32 ft.

10 m 

4.5 in.

114 mm

Overall

1.96 in.

50 mm

Supplied Cable

M12 Connector

Summary of Contents for KING-GAGE ES2 5501

Page 1: ...sions KING GAGE A NOSHOK Company I 1010 West Bagley Road Berea Ohio 44017 I Ph 855 367 2494 I www king gage com ES2 Electronic Liquid Level Transmitter Effective October 2016 EX 1845 Installation and...

Page 2: ...rchantability are given by this agreement The exclusive remedy for nonconformity of these goods shall be repair and or replacement of the nonconforming goods or parts Seller will not be liable for con...

Page 3: ...ifications 4 Model No Designations 5 Mounting Dimensions 6 7 Typical Application 7 Power Requirement 8 Connectors and Signal Cable 9 10 Test Point Terminals 10 ES2 Calibration 12 13 Calibration Equipm...

Page 4: ...excitation 14 40 Vdc Output mAdc 4 20 milliamperes Span Adjustment Range Transmitter adjustment turndown is 3 1 for the 0 15 0 30 0 50 psig nominal ranges Nominal Minimum Range of Adjustment 0 5 psig...

Page 5: ...r 15 0 15 psig 0 1 03 bar 30 0 30 psig 0 2 06 bar 50 0 50 psig 0 3 44 bar Mounting Application 1 short mount single wall non insulated tank 2 standard mount insulated wall up to 4 5 in 114 mm or adapt...

Page 6: ...nce for installation and removal of the transmitter Clearance dimensions will vary depending upon type of cable or connector used Model 5502 ES2 Slimline Transmitter Standard Mount Model 5501 ES2 Slim...

Page 7: ...19 7 8 9 4 5 6 1 2 3 0 Men u Se lect Ed it En te r Re se t 6 in 152 mm 6 35 in 161 mm 2 Flange 150 lb ANSI Diameter Flange Size ANSI 4 25 108mm 1 pipe flange 150 lb 5 0 127mm 1 5 pipe flange 150 lb 6...

Page 8: ...r and is intended for plug type molded cable assemblies designed for 4 pole signal termination Our ES2 transmitter package also includes a molded M12 cable 32ft 10m to simplify installation and ensure...

Page 9: ...5 cm 25 in 0 5 cm Connector Body Compression Sleeve End Cap Seal Grommet L Transmitter Signal Cable Use twisted pair cable 20 22 AWG for the signal loop between transmitter and receiver 3 The connecto...

Page 10: ...ing the output signal without disturbing the signal loop Do not connect any device or meter whose internal resistance exceeds 20 ohms across these test points Also refer to In Process Zero Span Adjust...

Page 11: ...osts on the transmitter board 1 2 Adjust span potentiometer as necessary to increase output clockwise ordecreaseoutput counterclock wise until the signal displays as 20 00 or 20 01 mA on the test mete...

Page 12: ...m pressure to the sensing diaphragm of the ES2 transmitter requires a pres sure test shell available from King Engineering 2 2 Record the existing setting position of the rotary switch 2 3 Adjust the...

Page 13: ...ion CAUTION Some pressure regulators will allow a slight pressure output even when completely adjusted to the shut position It is preferable to vent the transmitter to atmospherebydisconnectingthepres...

Page 14: ...here A Reserve inches of depth from low point of tank to sensor B Full Tank inches of depth from low point of tank to full C Specific Gravity of Tank Contents MODEL RANGE 5701 1 15 PSIG Sensor Assembl...

Page 15: ...replaced if there are any signs of physical damage such as a cut to the O ring Signal wiring connectors The transmitter provides an M12 threaded outlet on the exterior of the housing that accepts an...

Page 16: ...Page 16 ES2 Electronic Liquid Level Transmitter EX 1845...

Reviews: