background image

page 8

Model 

5900 

D/P 

Module 

     

EX-1710-1

P

1

P

2

Sensor

Surface of Liquid

E

S

High

Pressure

P

1

 + P

2

Low

Pressure

P

2

P

1

 + P

2

(P

1

 + P

2

) - P

2

 = P

1

Gauge

 Air Signal

S E

P

1

P

2

Sensor

Surface of Liquid

E

S

High

Pressure

P

1

 + P

2

Low

Pressure

P

2

P

1

 + P

2

(P

1

 + P

2

) - P

2

 = P

1

Gauge

 Air Signal

S E

Range Less Than 3.00 PSID

When the nominal 5 psid transmitter is used on an 
application whose maximum pressure is less than 3.00 psid, 
the full calculated range output will be less than 20 mA. 
To determine the actual milliamp output of the transmitter 
when the maximum applied pressure is below the lower 
span limit, use the following formula:

 

(16  ×  Calculated PSID)

 

3.0 

        

 +   4  =  mA Output

Note

The above formula may also be used for other nominal 
range transmitters if maximum applied pressure will be 
less than the adjustment range allows. Merely divide by 
the lower span limit psid value (listed above) in place of 
the “3.0” shown in the formula.

Low Pressure Input

Internal Tank Pressure or Vacuum

In a closed, pressurized or evacuated tank, it is necessary to 
measure differential pressure. This is achieved by subtracting 
the internal pressure condition of the tank above the surface 
of the liquid from the total pressure sensed at the bottom 
of the tank. When the low pressure is applied to one side 
of the transmitter sensing element and the high pressure to 
the other side, the internal tank pressure above the liquid 
(low pressure) is balanced across the sensing element. This 
is also referred to as being “equalized” (which is why we 
designate the low pressure connection as “E”).

CAUTION: While the internal pressure above the liquid is 
not a factor in determining range (span), there may be 
instances where the sum of the liquid and internal pressure 
exceeds the 150 psi burst pressure rating of the transmitter. 
Also, do not subtract pressure when a vacuum condition 
is present within the tank (since loss of vacuum would be 
seen as an increase at the high pressure connection of the 
transmitter).

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

Decrease

mA

Increase

mA

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

Coarse Setting Procedure

: The number of switches in 

the ON position will increase the milliamp value as each 
switch controls an identical fixed resistor. To increase 
milliamp output, place additional switches into the ON 
position. To decrease milliamp output, move switches 
to the off position.

1  2

  3  4

ON

17.002

Meter

DIP Switch

1  2

  3  4

ON

19.970

Meter

DIP Switch

DIP Switch—Coarse Adjustment

Coarse Range Setting—Alternate Version

Previous versions of the D/P transmitter employ similar DIP 
switches, but only offer 5 increments of coarse adjustment. 
With these versions, the span potentiometer offers greater 
range of adjustment.

Summary of Contents for KING-GAGE 5900

Page 1: ...e to Range Calculation Calibration Procedures Zero Span Adjustments for Differential Pressure Transmitters Model 5900 D P Module 4 mA to 20 mA Pressure Transmitter Multiple Tank Level Display KING GAGE A NOSHOK Company I 1010 West Bagley Road Berea Ohio 44017 I Ph 855 367 2494 I www king gage com ...

Page 2: ...ties of fitnessforaparticularpurposeormerchantability aregiven bythisagreement Theexclusiveremedyfornonconformity of these goods shall be repair and or replacement of the nonconforming goods or parts Sellerwillnotbeliableforconsequentialdamagesresulting from breach of this agreement The term consequential damages shall include but shall not be limited to damage toallmachines equipmentandgoodsother...

Page 3: ...pan Adjustment 6 Low Pressure Input for differential pressure 8 Calibration Test Setup Typical 9 Pressure Range Calculation 10 Troubleshooting 11 5900 1 2 Fittings 1 none 1 8 NPT connection 4 Swagelok 1 4 tube 1 8 NPT compatible with copper or poly tubing Range 0 0 5 psid 0 0 3 bar 1 0 10 psid 0 0 69 bar 2 0 15 psid 0 1 03 bar 3 0 30 psid 0 2 06 bar 4 0 50 psid 0 3 44 bar Model No Designations ...

Page 4: ...r Supply Voltage 14 40 Vdc unregulated Power Supply Stability Effect on FSO less than 0 005 of span change in output per volt change at input terminals Burst Pressure 200 psi Span Adjustment Range Transmitter adjustment turndown is 3 1 for the 0 15 0 30 0 50 psid nominal ranges Nominal Minimum Range of Adjustment 0 5 psid 0 3 psid 0 83 in thru 0 138 in water 0 2 1 m thru 0 3 5 m water 0 10 psid 0 ...

Page 5: ...Pressure Transm itter T E S T Plug in Power Signal Connector Ð 2 1 RL K IN G G A G E ZERO SPAN D P M O DULE 4 2 0 m A Pressure Transm itter T E S T Plug in Power Signal Connector Ð 2 1 Power Requirement The D P transmitter requires a source of DC power 14 40 Vdc for operation Minimum excitation voltage must be no less than 14 Vdc Any receiver installed on the signal loop meters data loggers contro...

Page 6: ...t to the maximum depth hydrostatic pressure Measure the output using the meter terminal posts on the transmitter board 2 Adjust span potentiometer as necessary to increase output clockwise ordecreaseoutput counterclock wise until the signal displays as 20 00 or 20 01 mA on the test meter 3 Next step is to re check the zero output and slightly adjust if necessary In Process Zero Span Adjustment It ...

Page 7: ...lease refer to the individual DIP switch positions listed for adjusting the existing setting of the transmitter The four 4 switches provide 16 increments of coarse adjustment Prior to changing any switch setting check the current output of the transmitter at the desired upper pressure value Also note the existing switch setting 1 Apply the desired maximum pressure to the sensing diaphragmoftheD Pt...

Page 8: ...tter sensing element and the high pressure to the other side the internal tank pressure above the liquid low pressure is balanced across the sensing element This is also referred to as being equalized which is why we designate the low pressure connection as E CAUTION While the internal pressure above the liquid is not a factor in determining range span there may be instances where the sum of the l...

Page 9: ...ipment MILLIAMMETER 3 1 2 digit minimum 0 05 accuracy 20 ohms max internal resistance DC POWER SUPPLY PRESSURE INDICATOR PSI or IN OF WATER 0 05 accuracy corresponding to transmitter range 5 psid nominal 0025 psi or 0693 of water 10 psid nominal 005 psi or 1385 of water 15 psid nominal 0075 psi or 2078 of water 30 psid nominal 015 psi or 4156 of water 50 psid nominal 025 psi or 6927 of water NOTE ...

Page 10: ...rve represents the distance from the lowest point on the bottom of the tank to the installed sensor Full is the level of contents at which the tank is filled to desired level which is less than the actual full capacity of the tank The liquid contents in the tank has a specific gravity of 1 032 C 1 032 Specific Gravity B 300 Upper Level A 28 Reserve 300 28 1 032 27 6807 10 14 psid 300 28 1 032 281 ...

Page 11: ...20 0 mA Check zero output of transmitter adjust zero to 4 00 mA if necessary Check span setting adjust to 20 00 mA at nominal range or calculated full pressure Maximum output less than 20 00 mA Check that applied pressure is within span limits for transmitter range Transmitter has 40 span adjustment Check span setting adjust to 20 00 mA at nominal range or calculated full pressure Higherresistivel...

Page 12: ......

Reviews: