background image

page 10

Model 

5900 

D/P 

Module 

     

EX-1710-1

Pressure Range Calculation

There are two simple equations that can be used to 
determine the actual range (span) required for the 
transmitter. One of these gives the range in psid and the 
other in INCHES OF WATER.

 

(B  

  A)  

×

  C

 

  27.6807       

=  Range (psid)

Where . . .

A = Reserve (inches of depth from low point of tank to
       sensor)
B  =  Full Tank (inches of depth from low point of tank to full)
C = Specific Gravity of Tank Contents

Converting LBS/GAL to Specific Gravity

If the density of the liquid is expressed as pounds per gallon 
(e.g., 8.6 lbs/gal), the specific gravity can be determined 
by dividing the value by 8.33 (weight of water per gallon).

Examples—Pressure Range Calculations

A typical tank gauging application is illustrated in Figure 
1. The “reserve” represents the distance from the lowest 
point on the bottom of the tank to the installed sensor. 
“Full” is the level of contents at which the tank is filled 
to capacity (or may be some point below the tank top, as 
desired). The liquid contents in the tank is water @ 1.00 
specific gravity.

C = 1.00 (Specific Gravity)
B = 382" (Full Tank)
A = 30"  (Reserve)

(382 

 30)  

× 

 1.00

       27.6807            

=  12.72 psid

(382 

 30)  

×

 1.00   = 352" water

A second tank gauging application is illustrated in Figure 2. 
The “reserve” represents the distance from the lowest 
point on the bottom of the tank to the installed sensor. 
“Full” is the level of contents at which the tank is filled 
to desired level (which is less than the actual full capacity 
of the tank). The liquid contents in the tank has a specific 
gravity of 1.032. 

C = 1.032 (Specific Gravity)
B = 300"  (Upper Level)
A = 28"   (Reserve)

  (300  

− 

 28)  

× 

 1.032 

          27.6807               

=  10.14 psid

(300 

 28)  

× 

 1.032   =   281" water

NOTE

—Should the calculated range exceed the upper span 

limits of the transmitter, the next higher range is required. 
If the calculated range falls below the lower span limits, a 
lower range transmitter is required (to obtain 20 mAdc).

Figure 1

Figure 2

When Output will be Less Than 20 mA . . .

Maximum Pressure Below 3.00 PSID

When the nominal 5 psid transmitter is used on an 
application whose maximum pressure is less than 3.00 psid, 
the full calculated range output will be less than 20 mA. 
To determine the actual milliamp output of the transmitter 
when the maximum applied pressure is below the lower 
span limit, use the following formula:

(16 

×

 Calculated PSID)    +   4   =   mA Output

 3.0 

Other Ranges

The above formula may also be used for other nominal 
range transmitters if maximum applied pressure will be 
less than the adjustment range allows. Merely divide by 
the lower span limit PSID value (see page 4) in place of the 
“3.0” shown in the formula.

A

B

Water

1.00 SP. GR.

Sensor

A

B

Milk

1.032 SP. GR.

Sensor

A

B

Water

1.00 SP. GR.

Sensor

A

B

Milk

1.032 SP. GR.

Sensor

Summary of Contents for KING-GAGE 5900

Page 1: ...e to Range Calculation Calibration Procedures Zero Span Adjustments for Differential Pressure Transmitters Model 5900 D P Module 4 mA to 20 mA Pressure Transmitter Multiple Tank Level Display KING GAGE A NOSHOK Company I 1010 West Bagley Road Berea Ohio 44017 I Ph 855 367 2494 I www king gage com ...

Page 2: ...ties of fitnessforaparticularpurposeormerchantability aregiven bythisagreement Theexclusiveremedyfornonconformity of these goods shall be repair and or replacement of the nonconforming goods or parts Sellerwillnotbeliableforconsequentialdamagesresulting from breach of this agreement The term consequential damages shall include but shall not be limited to damage toallmachines equipmentandgoodsother...

Page 3: ...pan Adjustment 6 Low Pressure Input for differential pressure 8 Calibration Test Setup Typical 9 Pressure Range Calculation 10 Troubleshooting 11 5900 1 2 Fittings 1 none 1 8 NPT connection 4 Swagelok 1 4 tube 1 8 NPT compatible with copper or poly tubing Range 0 0 5 psid 0 0 3 bar 1 0 10 psid 0 0 69 bar 2 0 15 psid 0 1 03 bar 3 0 30 psid 0 2 06 bar 4 0 50 psid 0 3 44 bar Model No Designations ...

Page 4: ...r Supply Voltage 14 40 Vdc unregulated Power Supply Stability Effect on FSO less than 0 005 of span change in output per volt change at input terminals Burst Pressure 200 psi Span Adjustment Range Transmitter adjustment turndown is 3 1 for the 0 15 0 30 0 50 psid nominal ranges Nominal Minimum Range of Adjustment 0 5 psid 0 3 psid 0 83 in thru 0 138 in water 0 2 1 m thru 0 3 5 m water 0 10 psid 0 ...

Page 5: ...Pressure Transm itter T E S T Plug in Power Signal Connector Ð 2 1 RL K IN G G A G E ZERO SPAN D P M O DULE 4 2 0 m A Pressure Transm itter T E S T Plug in Power Signal Connector Ð 2 1 Power Requirement The D P transmitter requires a source of DC power 14 40 Vdc for operation Minimum excitation voltage must be no less than 14 Vdc Any receiver installed on the signal loop meters data loggers contro...

Page 6: ...t to the maximum depth hydrostatic pressure Measure the output using the meter terminal posts on the transmitter board 2 Adjust span potentiometer as necessary to increase output clockwise ordecreaseoutput counterclock wise until the signal displays as 20 00 or 20 01 mA on the test meter 3 Next step is to re check the zero output and slightly adjust if necessary In Process Zero Span Adjustment It ...

Page 7: ...lease refer to the individual DIP switch positions listed for adjusting the existing setting of the transmitter The four 4 switches provide 16 increments of coarse adjustment Prior to changing any switch setting check the current output of the transmitter at the desired upper pressure value Also note the existing switch setting 1 Apply the desired maximum pressure to the sensing diaphragmoftheD Pt...

Page 8: ...tter sensing element and the high pressure to the other side the internal tank pressure above the liquid low pressure is balanced across the sensing element This is also referred to as being equalized which is why we designate the low pressure connection as E CAUTION While the internal pressure above the liquid is not a factor in determining range span there may be instances where the sum of the l...

Page 9: ...ipment MILLIAMMETER 3 1 2 digit minimum 0 05 accuracy 20 ohms max internal resistance DC POWER SUPPLY PRESSURE INDICATOR PSI or IN OF WATER 0 05 accuracy corresponding to transmitter range 5 psid nominal 0025 psi or 0693 of water 10 psid nominal 005 psi or 1385 of water 15 psid nominal 0075 psi or 2078 of water 30 psid nominal 015 psi or 4156 of water 50 psid nominal 025 psi or 6927 of water NOTE ...

Page 10: ...rve represents the distance from the lowest point on the bottom of the tank to the installed sensor Full is the level of contents at which the tank is filled to desired level which is less than the actual full capacity of the tank The liquid contents in the tank has a specific gravity of 1 032 C 1 032 Specific Gravity B 300 Upper Level A 28 Reserve 300 28 1 032 27 6807 10 14 psid 300 28 1 032 281 ...

Page 11: ...20 0 mA Check zero output of transmitter adjust zero to 4 00 mA if necessary Check span setting adjust to 20 00 mA at nominal range or calculated full pressure Maximum output less than 20 00 mA Check that applied pressure is within span limits for transmitter range Transmitter has 40 span adjustment Check span setting adjust to 20 00 mA at nominal range or calculated full pressure Higherresistivel...

Page 12: ......

Reviews: