background image

3

Operating Options

The furnace is shipped from the factory in a “Standard Heating Mode” (all switches are in the Down position). When the thermostat
calls for heat, the automatic controls will be activated and the furnace turned “ON”.

The blower will run at low speed or higher speed (as selected by

SPEED SELECTOR

switch).

As the furnace heats up, it automatically switches to the pre-programmed heating speed when additional elements are activated by
the electronic control, if it was initially set to run at low speed. The timing of this blower speed change will depend on whether C

OLD

or M

ILD

is selected on the

SEASON SELECT

switch.

You may, however, change from the Standard Heating Mode by using the controls built into your furnace.

The

SPEED SELECTOR

switch is used to control the fan speed

(ventilation). Even if there is no call for heat, the ventilation can
be controlled by the thermostat; the fan speed is determined by
this switch.

H

IGH

– The blower motor will operate at low speed.

L

OW

– The blower motor will operate at a higher speed.

During spring and fall, you may not require full heating capacity
to maintain a comfortable temperature.

M

ILD

– Approximately half of the elements are “off-line” and will

not be energized when the thermostat calls for heat.

C

OLD

– All elements are “on-line” and controlled by the

thermostat.

NOTE: If outdoor or two-stage thermostat is used, switch MUST
be in MILD position at all times. This switch has no effect on the
10 kW model.

4

Breakers

ECM Series furnaces are equipped with breakers, located on
the front panel of the unit. These devices protect the heating
elements from overcurrent. If this situation occurs, the breakers
will open to cut the power from the heating elements only.

NOTE: The number of breakers varies according to the
furnace model; 21ECM10 model has no breakers, 21ECM15,
21ECM18 and 21ECM20 models have 2 breakers, and
21ECM23 and 21ECM25 models have 3 breakers. Refer to
Section 8 Wiring Diagrams.

WARNING

Breakers do not cut power to entire furnace, only to the heating elements. Do not use the breakers to turn off the furnace. The
power to the whole unit can only be cut from the main electrical panel.

5

Summary of Contents for 21ECM10

Page 1: ...AND USER MANUAL ECM SERIES ELECTRIC FURNACE MODELS 21ECM10 21ECM15 21ECM18 21ECM20 AND 21ECM23 IMPORTANT READ AND SAVE THESE INSTRUCTIONS NORTRON Sherbrooke Quebec www dettson ca 1 800 567 2733 2019 1...

Page 2: ...not block the combustion air openings in the furnace Any blockage will result in improper overheat situation and may result in a fire hazard and or cause bodily harm The unit must have an uninterrupte...

Page 3: ...Supply 6 5 3 Connecting and Adjusting the Low Voltage Thermostat 6 6 Use in Mobile Homes 7 7 Using Optional Equipment 7 7 1 Two Stage or Outdoor Thermostat 7 7 2 Air Conditioning 7 7 3 Electronic Air...

Page 4: ...indicated on the data label attached to the furnace 4 TEMPERATURE RISE Furnaces are shipped to operate at 0 20 W C 50 Pa external static pressure They are certified for operation up to 0 50 W C 125 Pa...

Page 5: ...speed LOW The blower motor will operate at a higher speed During spring and fall you may not require full heating capacity to maintain a comfortable temperature MILD Approximately half of the element...

Page 6: ...the electrician s responsibility to ensure that the wiring and connections are compliant to the latest editions of the Canadian Electrical Code and local codes 5 3 Connecting and Adjusting the Low Vo...

Page 7: ...e will supply heat as follows in the opposite chart Model First Stage Second Stage 10 kW 10 kW 15 kW 10 kW 5 kW 18 kW 9 kW 9 kW 20 kW 10 kW 10 kW 25 kW 15 kW 10 kW 7 2 Air Conditioning Your furnace is...

Page 8: ...on When the electric furnace is used in combination with another device as for example a wood burning furnace it is recommended to perform the connection by referring to the wiring diagram at right Th...

Page 9: ...RNING Risk of electric shock Disconnect power before installation servicing maintenance or field wiring Replace all panels before operating Failure to do so can result in electric shock causing severe...

Page 10: ...ot for all replacement parts and repairs No Part No Description 1 L01H030 24VDC Relay DPST 2 30274131 24VDC Relay SPDT 3 30300022 Transformer 4 Z01I035 Blower 5 B40805 04 Motor 10 KW 6 B40805 05 Motor...

Page 11: ...rmostat or its connecting wiring After the fault area is isolated by use of the thermostat a check of the following components can be made more efficiently Problem Possible defective parts or componen...

Page 12: ...tation of repaired part or replaced product mentioned above and for reinstallation costs The duration of any implied warranty is limited to the sixty month period as specified for the express warranty...

Reviews: