Norton LEO 5710 Series Installation Instructions Manual Download Page 6

CL

MAX

MIN

DEC/B

ACC

COMP

Component Layout

Inverter Details

80-9357-0110-020 Rev. A

6

Standard Function with Switches

1

2

3

4

1

2

3

4

Notes:
1. Power input to Door Operator Unit is at

“T1” Power Input Terminal (not shown)
120VAC 60Hz.

Wall Switch, Card
Reader, Key Switch,
etc.
Normally Open Momentary
dry contacts

Wall Switch, Card
Reader, Key Switch,
etc.
Normally Open Momentary
dry contacts

Operation:

Doors are normally closed.

Activating either switch will open both doors. Door will

close after hold open time delay has elapsed.

1

2

3

4

1

2

3

4

Door 1

Door 2

POT

FUNCTION

DESCRIPTION

CL

Obstruction Detection on Open

CW - Increase
CCW - Decrease

MAX

Door Open Speed

CW - Increase
CCW - Decrease

MIN

Motor Reversing Speed

CW - Increase
CCW - Decrease

DEC/B

Hold Open Time (5 - 30 Seconds)

CW - Increase
CCW - Decrease

ACC

Door Mounting (Factory Set)

Full CW - Push
Full CCW - Pull

COMP

Motor Torque at Hold Open
Position

CW - Increase
CCW - Decrease

Trimpot Adjuster

Inverter Adjustments:


Based on function adjustment desired, use table above to determine
which POT is to be adjusted.
Using Trimpot Adjuster, shown below and supplied with screw pack,
adjust the appropriate POT using illustration on the left.

Note: Trimpot may be

adjusted through slot
in finger guard.

Summary of Contents for LEO 5710 Series

Page 1: ...ctice in accordance with national and local wiring codes Note Unless otherwise noted all dimensions are given in inches millimeters Minimum suggested and required material thickness for hollow metal f...

Page 2: ...ches mm Thickness recommended for reinforcements in hollow metal doors and frames is charted at the left of this page Do not scale drawing Left hand door shown Maximum frame reveal is 6 7 8 175mm for...

Page 3: ...r unreinforced hollow metal frames or for aluminum frames six 6 Connect conduit to frame side of backplate Fasten unit to door frame seven screws Fasten unit to door frame seven screws Mount conduit b...

Page 4: ...door Allow door to close Loosen and readjust Open Position Ring as necessary to obtain desired door open position Tighten set screw Make all connections necessary for any accessories to the 4 positio...

Page 5: ...talled on the bracket Optional Bracket for surface wiring Ground Lead Power Leads Ground Screw Green Cable Clamps Conduit by Others from top T1 Power Input Terminal 80 9357 0110 020 Rev A 5 Ground Wir...

Page 6: ...lapsed 1 2 3 4 1 2 3 4 Door 1 Door 2 POT FUNCTION DESCRIPTION CL Obstruction Detection on Open CW Increase CCW Decrease MAX Door Open Speed CW Increase CCW Decrease MIN Motor Reversing Speed CW Increa...

Page 7: ...Supplied by Others 24VDC Out 24 VDC Electric Strike Wall Switch Card Reader Key Switch etc Normally Open Momentary dry contacts Notes 1 Power input to Door Operator Unit is at T1 Power Input Terminal...

Page 8: ...e requirements for the Power Assist Door POR Function is designed to meet or exceed all of the requirements for the Low Energy Power Operated Door C US UL An ASSAABLOY Group Co 1902 Airport Road Monro...

Page 9: ...hinges This template not for use with offset pivots Ceiling clearance of 6 152 mm from frame rabbet is required for this application Maximum frame reveal is 1 8 3 mm for this application Conduit hole...

Page 10: ...11 11 16 297 3 8 19 14 3 16 360 13 13 16 351 Door Opening Angle Dim A Dim B Up to 110 111 to 170 12 305 9 1 2 241 13 1 4 337 15 3 4 400 Frame Rabbet REVEAL Notes Do not scale drawing Left hand door sh...

Page 11: ...cordance with national and local wiring codes Note Unless otherwise noted all dimensions are given in inches millimeters Minimum suggested and required material thickness for hollow metal frames skin...

Page 12: ...mm Thickness recommended for reinforcements in hollow metal doors and frames is charted at the left of this page Do not scale drawing Left hand door shown Maximum frame reveal is 7 178mm for this app...

Page 13: ...ith the flat corner of the pinion shaft square See Fig 1 upper right Frame Door A Prepare holes for 1 4 20 machine screws or No 14 x 2 3 4 70mm wood screws Blind rivet nuts by others are suggested for...

Page 14: ...en door reaches 20 switch Breaker Switch to position cutting power to the unit Allow door to fully close door may be manually pulled closed Once door has fully closed manually open door slightly and i...

Page 15: ...talled on the bracket Optional Bracket for surface wiring Ground Lead Power Leads Ground Screw Green Cable Clamps Conduit by Others from top T1 Power Input Terminal 80 9357 0130 020 Rev A 5 Ground Wir...

Page 16: ...apsed 1 2 3 4 1 2 3 4 Door 1 Door 2 POT FUNCTION DESCRIPTION CL Obstruction Detection on Open CW Increase CCW Decrease MAX Door Open Speed CW Increase CCW Decrease MIN Motor Reversing Speed CW Increas...

Page 17: ...Supplied by Others 24VDC Out 24 VDC Electric Strike Wall Switch Card Reader Key Switch etc Normally Open Momentary dry contacts View of Jumper in Normally Open Position For Use With Fail Safe Strike...

Page 18: ...e requirements for the Power Assist Door POR Function is designed to meet or exceed all of the requirements for the Low Energy Power Operated Door C US UL An ASSAABLOY Group Co 1902 Airport Road Monro...

Reviews: