Norton LEO 5710 Series Installation Instructions Manual Download Page 5

Low Voltage

Control

Wiring

Incoming

Power

Input Power Configurations

CONCEALED WIRING

Thread conduit fitting(s) into backplate as shown. A
second conduit fitting is required for low voltage
control wiring. CHECK LOCAL CODES. Pull conduit
out of header and attach to conduit fittings before
mounting Operator to door frame. Attach incoming
ground wire to backplate with ground screw as
illustrated below.

SURFACE WIRING

An optional bracket is provided for use with surface
wiring. Remove the two cable clamps screws and
slip the bracket under the cable clamps. Push the
cable clamp screw through the bracket holes and
tighten. ½” conduit fittings can now be installed on
the bracket.

Optional Bracket
(for surface wiring)

Ground
Lead

Power
Leads

Ground
Screw
(Green)

Cable
Clamps

Conduit
by Others
(from top)

“T1” Power
Input
Terminal

80-9357-0110-020 Rev. A

5

Ground Wire Connection – Ground wire must be secured to backplate under head of (green) ground screw nearest to “T1” Power Input
Terminal. Screw labeled “GND”.

General Electrical Data

Maximum current draw of unit is 0.6 amps.
Breaker Switch protects the motor assembly and inverter and
has a 5 amp rating.

Maximum wire size is:

12AWG at terminals HOT and COM on “T1” Power Input
Terminal.
14AWG at terminals 1 thru 4 on Accessory Terminal .
18AWG at terminals 22 thru 25 on “T1” Power Input
Terminal.

24

23

22

25

HOT

COM

Terminal

Description

HOT

25

23

24

22

COM

Common power lead

Hot power lead

Circuit Breaker

Switch

Circuit Breaker

Common connection to Circuit Breaker /
Inverter

Summary of Contents for LEO 5710 Series

Page 1: ...ctice in accordance with national and local wiring codes Note Unless otherwise noted all dimensions are given in inches millimeters Minimum suggested and required material thickness for hollow metal f...

Page 2: ...ches mm Thickness recommended for reinforcements in hollow metal doors and frames is charted at the left of this page Do not scale drawing Left hand door shown Maximum frame reveal is 6 7 8 175mm for...

Page 3: ...r unreinforced hollow metal frames or for aluminum frames six 6 Connect conduit to frame side of backplate Fasten unit to door frame seven screws Fasten unit to door frame seven screws Mount conduit b...

Page 4: ...door Allow door to close Loosen and readjust Open Position Ring as necessary to obtain desired door open position Tighten set screw Make all connections necessary for any accessories to the 4 positio...

Page 5: ...talled on the bracket Optional Bracket for surface wiring Ground Lead Power Leads Ground Screw Green Cable Clamps Conduit by Others from top T1 Power Input Terminal 80 9357 0110 020 Rev A 5 Ground Wir...

Page 6: ...lapsed 1 2 3 4 1 2 3 4 Door 1 Door 2 POT FUNCTION DESCRIPTION CL Obstruction Detection on Open CW Increase CCW Decrease MAX Door Open Speed CW Increase CCW Decrease MIN Motor Reversing Speed CW Increa...

Page 7: ...Supplied by Others 24VDC Out 24 VDC Electric Strike Wall Switch Card Reader Key Switch etc Normally Open Momentary dry contacts Notes 1 Power input to Door Operator Unit is at T1 Power Input Terminal...

Page 8: ...e requirements for the Power Assist Door POR Function is designed to meet or exceed all of the requirements for the Low Energy Power Operated Door C US UL An ASSAABLOY Group Co 1902 Airport Road Monro...

Page 9: ...hinges This template not for use with offset pivots Ceiling clearance of 6 152 mm from frame rabbet is required for this application Maximum frame reveal is 1 8 3 mm for this application Conduit hole...

Page 10: ...11 11 16 297 3 8 19 14 3 16 360 13 13 16 351 Door Opening Angle Dim A Dim B Up to 110 111 to 170 12 305 9 1 2 241 13 1 4 337 15 3 4 400 Frame Rabbet REVEAL Notes Do not scale drawing Left hand door sh...

Page 11: ...cordance with national and local wiring codes Note Unless otherwise noted all dimensions are given in inches millimeters Minimum suggested and required material thickness for hollow metal frames skin...

Page 12: ...mm Thickness recommended for reinforcements in hollow metal doors and frames is charted at the left of this page Do not scale drawing Left hand door shown Maximum frame reveal is 7 178mm for this app...

Page 13: ...ith the flat corner of the pinion shaft square See Fig 1 upper right Frame Door A Prepare holes for 1 4 20 machine screws or No 14 x 2 3 4 70mm wood screws Blind rivet nuts by others are suggested for...

Page 14: ...en door reaches 20 switch Breaker Switch to position cutting power to the unit Allow door to fully close door may be manually pulled closed Once door has fully closed manually open door slightly and i...

Page 15: ...talled on the bracket Optional Bracket for surface wiring Ground Lead Power Leads Ground Screw Green Cable Clamps Conduit by Others from top T1 Power Input Terminal 80 9357 0130 020 Rev A 5 Ground Wir...

Page 16: ...apsed 1 2 3 4 1 2 3 4 Door 1 Door 2 POT FUNCTION DESCRIPTION CL Obstruction Detection on Open CW Increase CCW Decrease MAX Door Open Speed CW Increase CCW Decrease MIN Motor Reversing Speed CW Increas...

Page 17: ...Supplied by Others 24VDC Out 24 VDC Electric Strike Wall Switch Card Reader Key Switch etc Normally Open Momentary dry contacts View of Jumper in Normally Open Position For Use With Fail Safe Strike...

Page 18: ...e requirements for the Power Assist Door POR Function is designed to meet or exceed all of the requirements for the Low Energy Power Operated Door C US UL An ASSAABLOY Group Co 1902 Airport Road Monro...