Servicing
2. Change secondary fuel filter every 500 hours.
NOTE:
The fuel filter on the engine is considered the
“secondary fuel filter”. The engine will be fitted with a
quick change disposable secondary fuel filter.
SP7. CRANKSHAFT VIBRATION DAMPER
(6 Cylinder Engines Only)
1. Remove belts.
2. Try to turn the vibration damper in both directions
while grasping it with both hands. If rotation can be
felt, the damper is defective and should be replaced.
NOTE:
The vibration damper assembly should be
replaced every 4500 hours or 60 months, whichever
occurs first, as the vibration damper assembly is
not
repairable.
3. Place a dial indicator
(Figure 13)
so that the probe
contacts the damper’s outer diameter in order to
check the damper radial runout.
4. Make sure the engine is at operating temperature,
then rotate the crankshaft using the JD281A,
JDE81-4, or the JDE83 Flywheel Turning Tool.
5. If the runout reading exceeds the below
specification, replace the vibration damper.
Vibration Damper Maximum
Radial Runout ..........................1.50 mm (0.060 in.)
FUELS - GENERAL
1. Use only clean, high quality fuels of the following
specifications, as defined by ASTM designation D975 for
diesel fuels:
a. Use Grade No. 2 diesel at ambient temperatures
above freezing 30°F (0°C).
b. Use Grade No.1 at ambient temperatures below
freezing and for all temperatures at an altitude of
above 5,500 ft. (1500 meters).
2. Sulphur content should not exceed 0.5% (preferably less than 0.5%).
3. The cetane number should be a minimum of 45.
4. DO NOT use these unsuitable grades of fuel:
a. Domestic heating oils, all types, b. Class B engine,
c. Class D domestic fuels, d. Class E, F, G or H industrial
or marine fuels,
e. ASTM-D975-60T No. 4-D and higher
number fuels, f. JP4
5. Storing fuel:
a. Keep dirt, scale, water and other foreign matter
out of fuel.
b. Avoid storing fuel for long periods of time.
c. Fill the fuel tank at the end of each day's operation. This
will reduce condensation.
6. Biodiesel:
Biodiesel involves the transesterification of vegetable oils or animal fats.
Mainly in the U.S. soybean methyl ester is used (SME), but in Europe
mainly rapeseed (canola) methyl ester is made (RME), and in Asia palm
methyl ester is made (PME). 100% biodiesel (B100) is made in compliance
with ASTM D6751 or EN14214 (EU) specifications. Biodiesel may be used
in a 5% blend (5% biodiesel/ 95% diesel) from a BQ-9000 accredited pro-
ducer. 20% biodiesel blends can only be used if they meet ASTM D6751 or
EN14214 (EU) specifications. A 2% reduction in power and a 3% reduction
in fuel economy can be expected using a 20% blend, and a fuel conditioner
is recommended. Biodiesel blends must be used within 90 days of their
manufacture. Oil level, leaking, microbial growth, plugging, and component
degradation all must be checked more frequently using biodiesel blends.
Request a certificate of analysis from an approved biodiesel fuel distributor
to make sure the blend meets specifications.
NOTE: Using raw pressed or partially refined vegetable oils or recycled
greases as fuel (which have not been through transesterification) could
cause engine failure.
SP8-10. FUEL FILTERS
1. Your engine or generator set should have a primary
fuel filter installed. We recommend the Racor brand of fuel
filter - water separators.
a. Check the primary fuel filter daily as recommended by the
filter manufacturer. Empty the collection bowl as necessary.
b. Change the element every 250 hours (500 for electroni-
cally controlled fuel system units) or whenever necessary.
c. If the bowl fills with water, change the primary and
secondary elements immediately.
Reproduced by permission of Deere & Company, c2004. Deere & Company. All rights
reserved.
RG8018
Figure 12
Reproduced by permission of Deere & Company, c2004. Deere & Company. All rights
reserved. RG7508
Figure 13