Equipment replacement Page 27 of 34
QCA144 1.5 MB/S RPE Cabinet
Maintenance and equipment replacement
Procedure 13
QPC705 Converter replacement
1
Set the CAB INP breaker on the QUX19 power distribution unit to OFF.
2
Remove the screws securing the QPC705 converter to the cabinet.
3
Slide the QPC705 converter out of its position and disconnect the
QCAD278 power cable from the connector at the rear of the converter.
4
Perform this step only if the QCAD278 cable is being replaced.
—
Remove the screws securing the lower EMI shield (if equipped) at
the rear of the cabinet and remove shield.
—
Disconnect the QCAD278 cable from terminal 2 of TB2 on the
QUX19 unit, connector P2 at the rear of the QUAA3 unit and from
the lug on the ground bus.
—
Remove cable.
5
If QPC705 is being replaced, connect existing QCAD278 cable to
connector on rear of new QPC705 converter.
If the QCAD278 cable is being replaced, connect connector 705 of
new cable to connector at rear of existing QPC705 converter.
6
Install the QPC705 in its assigned position with the QCAD278 cable
towards the rear of the cabinet. Secure the QPC705 converter to the
cabinet with mounting screws.
7
Perform this step only if the QCAD278 power cable is being replaced.
—
Connect connector P2 of the QCAD278 cable to connector P2 at
the rear of the QUAA3 unit.
—
Connect the red wire equipped with a spade connector to terminal
2 of TB2 at the rear of the QUX19 unit.
—
Connect the black wire equipped with a ring connector to GRD2
terminal on the ground bus at the rear of the cabinet.
—
Reinstall the EMI shield at rear of cabinet and secure with
mounting screws.
CAUTION
Service in the cabinet is interrupted when performing step 1.