Page 26 of 34 Equipment replacement
553-2601-500A
Standard 2.0
December 1994
4
Perform this step only if the power distribution cable for the third tier is
being replaced.
—
Disconnect connector P4 and P7 from the rear of the QUAA3 unit.
—
Disconnect red and blue wires from terminals 4 and 5 of TB5 at
the rear of the QUX20 unit.
—
Disconnect the black and white wires from the distribution cable
to the GRD2 and GRD1 connections on the ground bus at the rear
of the cabinet.
—
Disconnect connectors PE4 and PE5 from the PE shelf
backplane.
—
Connect connectors PE4 and PE5 of the replacement distribution
cable to the PE shelf backplane J connector and connectors P4
and P7 to J4 and J7 at the rear of the QUAA3 unit.
—
Connect the white and black wires equipped with ring connectors
to GRD1 and GRD2 terminals on the ground bus.
—
Connect the red and blue wires to terminals 4 and 5 of TB5 at the
rear of the QUX20 unit.
5
Reinstall EMI shields and secure with mounting screws.
6
Reconnect all cables previously disconnected.
7
Set the CAB INP breaker on the QUX19 unit to ON.
Procedure 12
QUA6 Power Fail Transfer Unit (PFTU) replacement
1
Place temporary jumpers at cross-connect terminal to maintain service
on telephones involved with the QUA6 unit.
2
Remove and tag cable from connector J1 on the faceplate of the
QUA6 unit.
3
Remove screws securing QUA6 unit to wall (if mounted on wall) and
remove unit.
4
With mounting screws, mount replacement QUA6 unit.
5
Reconnect cable to connector J1 on the faceplate of the QUA6 unit.
6
Remove temporary jumpers at cross-connect terminal.