Page 8 of 34
Fault detection and locating
553-2601-500A
Standard 2.0
December 1994
Procedure 1
CE/PE1 breaker on QUX19 unit trips
Step
Action
Verification
1
Reset breaker.
If breaker does not trip, fault has cleared.
If breaker trips, proceed with next step.
2
Unseat the QPC659 buffer pack in the PE
shelf in the first tier (base) of the cabinet.
Reset breaker.
If breaker trips, replace power distribution
cable at rear of cabinet. If breaker does
not trip, proceed with next step.
3
Set breakers to OFF. Unseat all
remaining circuit packs from PE shelf. Set
breaker to ON.
If breaker trips, replace the shelf
backplane.
4
Set breaker to OFF. Inset QPC659 pack.
Reset breaker ON.
If breaker trips. replace defective
QPC659 pack.
5
Reinsert circuit packs one at a time until
circuit breaker trips.
If breaker trips when a pack is inserted,
it is defective. Replace pack.