Nortek R6GF Series Installation Instructions Manual Download Page 32

32

REFRIGERANT CHARGING

 WARNING:

These units are shipped fully charged with R-410A 

refrigerant and ready for installation. When a system 

is installed according to these instructions, no 

refrigerant charging is required. If repairs make it 

necessary for evacuation and charging, it should 

only be done by qualified, trained personnel 

thoroughly familiar with this equipment. Some 

local codes require licensed installation/service 

personnel to service this type of equipment. Under 

no circumstances should the owner attempt to install 

and/or service this equipment. Failure to comply 

with this warning could result in property damage, 

personal injury, or death.

 CAUTION:

This unit uses R-410A refrigerant. DO NOT use 

any other refrigerant in this unit. Use of another 

refrigerant will damage the unit.

The system refrigerant charge can be checked and adjusted 

through the service ports provided at the front panel. Use only 

gauge lines which have a 

Schrader

 depression device present to 

actuate the valve. Refrigerant charging must be done by qualified 

personnel familiar with safe and environmentally responsible 

refrigerant handling procedures. Refer to the application notes 

and charging charts on pages 33-35

Charging an R-410A unit in AC mode at outdoor 
temperatures above 65F.

1. With the system operating at steady-state, measure the liquid 

refrigerant pressure in psig at the service valve.

2. Measure the liquid refrigerant temperature in Fahrenheit at 

the outlet of the condensor coil.

3. For the temperature measured, determine the required liquid 

refrigerant pressure from the appropriate charging charts in 

Figure 15

Figure 16 (page 33)

Figure 17

, & 

Figure 18 

(page 34)

.

4. If the pressure measured in step 1 is greater than the required 

liquid refrigerant pressure determined in step 3, then there 

is too much charge in the system. Remove refrigerant and 

repeat steps 1 through 3 until the system is correctly charged.

5. If the pressure measured in step 1 is less than the required 

liquid refrigerant pressure determined in step 3, then there 

is too little charge in the system. Add refrigerant and repeat 

steps 1 through 3 until the system is correctly charged. 

Charging Charts & Application Notes

This equipments cooling system contains refrigerant under 

high pressure, always use safe practices when servicing the 

unit. Always review the factory literature and safety warnings 

prior to servicing.
These units are shipped from the factory with the proper 

amount and type of refrigerant. Always inspect the unit rating 

label to determine the units information prior to working on the 

system. Do not mix different refrigerants or charge the unit with 

a refrigerant not listed on the unit rating label.
The charging charts Figures 13 - 16 pages 34 - 35 are valid 

for a variety of indoor, return air conditions and are most highly 

influenced by the outdoor ambient temperature, outdoor fan 

operation and the unit operating voltage. Before referencing the 

charts below, always make sure that the compressor circuit is 
energized on high speed and has stable operation.  See 

Figure 

15

Figure 16 (page 33)

Figure 17

, & 

Figure 18 (page 34)

.

As can be seen in the charging charts, the ideal system sub-

cooling can vary over the range of operation. Always reference 

the charts to determine the ideal amount of sub-cooling for a 

given liquid pressure. Units charged to other values will not 

perform at the rated unit efficiency (EER).
To inspect a systems operation, using quality instruments, 

match the measured liquid temperature to the units chart. The 

measured liquid pressure reading should be within 3% of the 

value shown for most installations. For two stage systems, 

the charts are valid for compressor operating on high speed.
DO NOT use the charts for a two stage system operating under 

a single stage call for cooling.
For systems that are operating with more then a 5% deviation, 

inspect the unit for leaks. Always use safe and environmentally 

sound methods for refrigerant handling.  When repairing system 

leakages, always utilize a nitrogen (inert) gas to protect the 

refrigerant system and pressure check the repair before re-

charging. Always replace the filter-dryers when performing 

any repair to the refrigeration system. After completing the 

repairs, evacuate the system to 350-500 microns and weigh in 

the refrigerant to the amount specified on the unit rating label.

Summary of Contents for R6GF Series

Page 1: ...plier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Ne pas entreposer ni utiliser de l essence ni d autres vapeurs ou...

Page 2: ...ion 17 System Cooling 17 System Heating 17 Verifying Adjusting Temperature Rise 17 Verifying Adjusting Firing Rate 18 Verifying Over Temperature Limit Control Operation 18 Verifying Burner Operation 1...

Page 3: ...g is required If repairs make it necessary for evacuationandcharging itshouldonlybeattempted by qualified trained personnel thoroughly familiar with this equipment Some local codes require licensed in...

Page 4: ...ctions and all applicable local codes Install this unit only in a location and position as specified on page 7 This unit is designed only for outdoor installations and should be located with considera...

Page 5: ...D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d installation du fabricant Aclearanceofatleast36inchesfromthebloweraccesspanel andfromthe...

Page 6: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilationaumomentdesamiseenmarche celapeut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes doivent t...

Page 7: ...fault condition If this control must be replaced use only factory authorized replacement parts See the list of Replacement Parts on page 21 Vent Termination This unit has been equipped with an integr...

Page 8: ...gned so that the return air to the unit is not less than 50 F 10 C during heating operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the...

Page 9: ...g enough to support the unit s weight The slab height must be a minimum of 2 5cm above grade and with adequate drainage See Figure 3 Remove and discard the horizontal supply and return duct covers loc...

Page 10: ...lectrique au g n rateur d air chaud avant de prod der aux travaux d entretein Au moment de l entretien des commandes tiquetez tous les fils avant de les d brancher S assurer de les raccorder correctem...

Page 11: ...rdancewith the instructions supplied with the thermostat and the indoor equipment These units use a special 2 speed compressor to achieve a high level of efficiency in a compact frame A 2 stage coolin...

Page 12: ...r system options With the blower installed and configured properly the furnace will gradually change speed in response to changes in system variables such as thermostat settings duct static filters et...

Page 13: ...noid damage from overheating conditions L Terminal Wiring White RodgersCompatibleThermostats TheLconnection is used to communicate Comfort Alert codes to compatible White Rodgersthermostats TheLtermin...

Page 14: ...al Electrical Code ANSI NFPA 70 or the CSA C22 1 Electrical Code Use the grounding lug provided in the control box for grounding the unit GAS SUPPLY PIPING WARNING FIRE OR EXPLOSION HAZARD Failure to...

Page 15: ...ectors A soap and water solution can be applied on each joint or union using a small paintbrush If any bubbling is observed the connection is not sealed adequately and must be retightened Repeat the t...

Page 16: ...al Gas R6GF X24K080XB R6GF X36K100XB MANIFOLD PRESSURE FOR NATURAL GAS INSTALLATIONS IN W C ALTITUDE ABOVE SEA LEVEL HEATING VALUE BTU CU FT ORIFICE SIZE 800 TO 899 FT 900 TO 999 FT 1 000 TO 1 100 FT...

Page 17: ...perly after 1 2 minutes lower the thermostat temperature set point an additional 3 4 degrees until the cooling system moves into 2nd stage or high cool operating mode The compressor and indoor blower...

Page 18: ...operating sequence page 19 NOTE The over temperature limit control should turn off the gas valve within approximately four minutes exact time depends on the efficiency of the close off when blocking t...

Page 19: ...on step 6 begins If no flame is sensed on the fifth try for ignition the furnace control is locked and the red LED will flash 4 times repetitively The thermostat must be opened for at least ten second...

Page 20: ...eginning of each heating and cooling season or more frequently if required Inspectthecondensatedrainandoutdoorcoilatthebeginning of each cooling season Remove any debris Clean the outdoorcoilandlouver...

Page 21: ...ches separate the ground joint union in the gas supply piping at the unit 7 Remove the piping between the gas valve and the ground joint union if applicable 8 Remove all screws securing the burner ass...

Page 22: ...Speed Blower call OFF SYSTEM STATUS CFM LED STATUS YELLOW NOT USED OFF automatically opens and regulates the gas pressure in the manifold See Figure 8 page 18 Over Temperature Limit Control The over t...

Page 23: ...rizontal Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 Unit Dimensions Table 8 Center of Gravity Unit Shipping Weights MODE...

Page 24: ...ormal 1170 Normal 1700 10 990 10 1290 10 1870 TAP C 10 900 TAP C 10 1140 TAP C 10 1620 Normal 1000 Normal 1270 Normal 1800 10 1100 10 1400 10 1980 TAP D 10 1080 TAP D 10 1260 TAP D 10 Normal 1200 Norm...

Page 25: ...9 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 164 327 112 32 161...

Page 26: ...compagnie du gaz en utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Ne jamais utiliser...

Page 27: ...UNIT CONTROL BOARD W1 W2 C R G Y Y2 0 DEHUM P2 1 5 HUM LINE XMFR CONT EAC COOL PARK1 PARK2 HI HEAT LO HEAT NEUTRALS AUTO HEAT STAGE 10 5 NONE HOT SURFACE IGNITION VARIABLE SPEED BLOWER CONTROL BOARD C...

Page 28: ...208 230 Volt Single Phase Packaged Two Stage Heat Two Stage Electric Air Conditioner 60Hz WIRING DIAGRAM NOTES 1 Disconnect power before servicing 2 For supply connections use copper conductors only...

Page 29: ...Single Phase Packaged Two Stage Heat Two Stage Electric Air Conditioner 60Hz WIRING DIAGRAM NOTES 1 Disconnect power before servicing 2 For supply connections use copper conductors only 3 Not suitabl...

Page 30: ...fective Condenser coil is dirty Liquid line restriction filter drier blocked if present in system Thermostat is malfunctioning Solenoid plug not connected Y2 not wired at Comfort Alert Check thermosta...

Page 31: ...s flashing at same time means control circuit voltage is too low for operation Table 14 LED Diagnostics Continued Table 15 Module Wiring Troubleshooting MISWIRED MODULE INDICATION RECOMMENDED TROUBLES...

Page 32: ...repeat steps 1 through 3 until the system is correctly charged Charging Charts Application Notes This equipments cooling system contains refrigerant under high pressure always use safe practices when...

Page 33: ...igerant when below curve Remove refrigerant when above curve Figure 15 Charging Chart for 2 Ton Units Figure 16 Charging Chart for 3 Ton Units Liquid Pressure psig Liquid Temperature F R6GF X36 Chargi...

Page 34: ...igerant when below curve Remove refrigerant when above curve Figure 18 Charging Chart for 5 Ton Units Figure 17 Charging Chart for 4 Ton Units Liquid Pressure psig Liquid Temperature F R6GF X48 Chargi...

Page 35: ...35...

Page 36: ...nit YES NO ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity correct YES NO Rated Voltage VOLTS L1 L2 Volts __________________________________________________________________...

Reviews: