Nortek R6GF Series Installation Instructions Manual Download Page 12

12

Table 3. Copper Wire Size

COPPER WIRE SIZE — AWG

(1% VOLTAGE DROP)

SUPPLY WIRE LENGTH-FEET

SUPPLY CIRCUIT

AMPACITY

200

150

100

50

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

2

3

4

6

55

1

2

3

4

60

NOTE:

 Wire Size based on N.E.C. for 60° type copper conductors.

Table 4. Thermostat Wire Gauge

WIRE GAUGE

RECOMMENDED MAXIMUM

WIRE LENGTH (FT) FROM UNIT

TO THERMOSTAT

22

45

20

70

18

115

16

180

Checking Heat Anticipator Settings

•  Add the current draw of the system components.

OR

•  Measure the current flow on the thermostat 

R

-

W

 circuit 

after the circulating blower motor has started. Set the heat 

anticipator according to the thermostat manufacturer’s 

instructions for heat anticipator settings.

Heating Configurations

This furnace is factory configured for two stage gas heating 

operation with a two stage heating thermostat. Connect the low 

voltage thermostat 

White

 & 

Brown

 wires to 

W1

 & 

W2

, between 

the unit low voltage terminal board and thermostat sub-base.
To operate with a single stage heat thermostat, only connect 

the low voltage thermostat 

White

 wire between 

W1

 on the unit 

low voltage terminal board and thermostat sub-base. Reposition 

the automatic heat staging jumper located on the ignition control 

module from NONE to 5 or 10 for the desired delay in minutes 

before the gas furnace will automatically move to high heat 
operation. See 

Figure 12 (page 27)

.

NOTE: 

When low fire on the gas valve is energized, the furnace 

operates in low fire mode at a lower blower speed and the timer 

begins its delay function. If the room thermostat is not satisfied 

before the timer activates, the furnace will stage to high fire. 

The inducer motor and blower will ramp to a higher speed until 

the thermostat is satisfied.

Configuring the Variable Speed Blower

The variable speed blower has been designed to give the 

installer maximum flexibility for optimizing system performance, 

efficiency, and comfort. It is equipped with a microprocessor-

controlled variable speed motor that is pre-programmed to 

deliver optimum airflow in a variety of conditions and system 

configurations. Because the blower can be configured in many 

ways, it is important to read and follow all instructions carefully.

 CAUTION:

To avoid personal injury or property damage, make 

certain that the motor leads cannot come into contact 

with any uninsulated metal components of the unit.

Before operation, the variable speed blower must be configured 

to match the unit with the system, climatic conditions, and 

other system options. With the blower installed and configured 

properly, the furnace will gradually change speed in response 

to changes in system variables such as thermostat settings, 

duct static, filters, etc. The variable speed blower is configured 

by setting the heat, cool, and adjust jumpers located on the 
ignition control board as described below. See 

Figure 12

.

Selecting Cooling Airflow

The cooling airflow is selected by setting the Cool and Adjust 
jumpers on the ignition control board. 

Table 10 (page 24)

 

lists the recommended airflow values (CFM) and selector 

tap settings for each nominal system capacity. All airflows 

for other modes of operation (except secondary gas heat) 

are determined by this basic setting. For maximum capacity, 

generally, a selection at or near the top of the CFM range for 

that nominal capacity is best.

NOTES:

•  The CFM values listed in 

Table 10

 are not dependent on 

duct static pressure. The motor automatically compensates 

(within the limits of the motor) for changes in duct static 

pressure.

•  If coil icing occurs, the basic cooling airflow selected may 

be too low. Verify the selected setting is within the range 
shown in 

Table 10

 and the system is properly charged. If 

icing continues, raise the selected airflow to the next higher 

tap.

•  For maximum dehumidification and energy efficiency, select 

an airflow near the middle or bottom of the CFM range for 

that nominal capacity.

•  The 2-stage cooling feature of the unit requires modulating 

the airflow. The unit will automatically adjust the airflow to 

the appropriate rate when the unit capacity changes.

Selecting Gas Heating Airflow

The heating airflow is selected by setting the heat jumper to 

the desired tap (A,B,C, or D) located on the ignition control 
board. Refer to 

Table 11 (page 24)

 and select a nominal 

rise based on the furnace’s nominal efficiency and firing input. 

Follow across the table row to find the tap setting and nominal 

air-flow. Verify the selected rise is within the specification shown 

on the furnace rating label.

Optional Humidistat

An optional humidistat may be installed in the return air duct 

for humidity control (when needed), maximum system capacity 

and energy efficiency. The humidistat senses when humidity in 

the return air stream is above a preset level and sends a signal 

to the motor to reduce airflow. This allows more moisture to be 

removed until the humidity level drops. 

NOTE:

 The indoor blower 

motor of this packaged unit is pre-programmed for humidistat 

operation. Remove the 

Red

 jumper wire between the 

R

 and 

DEHUM

 terminals on the ignition control board.

If installing a humidistat, install it in the return air duct as 

directed in the installation instructions included with the kit. 

Summary of Contents for R6GF Series

Page 1: ...plier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Ne pas entreposer ni utiliser de l essence ni d autres vapeurs ou...

Page 2: ...ion 17 System Cooling 17 System Heating 17 Verifying Adjusting Temperature Rise 17 Verifying Adjusting Firing Rate 18 Verifying Over Temperature Limit Control Operation 18 Verifying Burner Operation 1...

Page 3: ...g is required If repairs make it necessary for evacuationandcharging itshouldonlybeattempted by qualified trained personnel thoroughly familiar with this equipment Some local codes require licensed in...

Page 4: ...ctions and all applicable local codes Install this unit only in a location and position as specified on page 7 This unit is designed only for outdoor installations and should be located with considera...

Page 5: ...D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d installation du fabricant Aclearanceofatleast36inchesfromthebloweraccesspanel andfromthe...

Page 6: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilationaumomentdesamiseenmarche celapeut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes doivent t...

Page 7: ...fault condition If this control must be replaced use only factory authorized replacement parts See the list of Replacement Parts on page 21 Vent Termination This unit has been equipped with an integr...

Page 8: ...gned so that the return air to the unit is not less than 50 F 10 C during heating operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the...

Page 9: ...g enough to support the unit s weight The slab height must be a minimum of 2 5cm above grade and with adequate drainage See Figure 3 Remove and discard the horizontal supply and return duct covers loc...

Page 10: ...lectrique au g n rateur d air chaud avant de prod der aux travaux d entretein Au moment de l entretien des commandes tiquetez tous les fils avant de les d brancher S assurer de les raccorder correctem...

Page 11: ...rdancewith the instructions supplied with the thermostat and the indoor equipment These units use a special 2 speed compressor to achieve a high level of efficiency in a compact frame A 2 stage coolin...

Page 12: ...r system options With the blower installed and configured properly the furnace will gradually change speed in response to changes in system variables such as thermostat settings duct static filters et...

Page 13: ...noid damage from overheating conditions L Terminal Wiring White RodgersCompatibleThermostats TheLconnection is used to communicate Comfort Alert codes to compatible White Rodgersthermostats TheLtermin...

Page 14: ...al Electrical Code ANSI NFPA 70 or the CSA C22 1 Electrical Code Use the grounding lug provided in the control box for grounding the unit GAS SUPPLY PIPING WARNING FIRE OR EXPLOSION HAZARD Failure to...

Page 15: ...ectors A soap and water solution can be applied on each joint or union using a small paintbrush If any bubbling is observed the connection is not sealed adequately and must be retightened Repeat the t...

Page 16: ...al Gas R6GF X24K080XB R6GF X36K100XB MANIFOLD PRESSURE FOR NATURAL GAS INSTALLATIONS IN W C ALTITUDE ABOVE SEA LEVEL HEATING VALUE BTU CU FT ORIFICE SIZE 800 TO 899 FT 900 TO 999 FT 1 000 TO 1 100 FT...

Page 17: ...perly after 1 2 minutes lower the thermostat temperature set point an additional 3 4 degrees until the cooling system moves into 2nd stage or high cool operating mode The compressor and indoor blower...

Page 18: ...operating sequence page 19 NOTE The over temperature limit control should turn off the gas valve within approximately four minutes exact time depends on the efficiency of the close off when blocking t...

Page 19: ...on step 6 begins If no flame is sensed on the fifth try for ignition the furnace control is locked and the red LED will flash 4 times repetitively The thermostat must be opened for at least ten second...

Page 20: ...eginning of each heating and cooling season or more frequently if required Inspectthecondensatedrainandoutdoorcoilatthebeginning of each cooling season Remove any debris Clean the outdoorcoilandlouver...

Page 21: ...ches separate the ground joint union in the gas supply piping at the unit 7 Remove the piping between the gas valve and the ground joint union if applicable 8 Remove all screws securing the burner ass...

Page 22: ...Speed Blower call OFF SYSTEM STATUS CFM LED STATUS YELLOW NOT USED OFF automatically opens and regulates the gas pressure in the manifold See Figure 8 page 18 Over Temperature Limit Control The over t...

Page 23: ...rizontal Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 Unit Dimensions Table 8 Center of Gravity Unit Shipping Weights MODE...

Page 24: ...ormal 1170 Normal 1700 10 990 10 1290 10 1870 TAP C 10 900 TAP C 10 1140 TAP C 10 1620 Normal 1000 Normal 1270 Normal 1800 10 1100 10 1400 10 1980 TAP D 10 1080 TAP D 10 1260 TAP D 10 Normal 1200 Norm...

Page 25: ...9 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 164 327 112 32 161...

Page 26: ...compagnie du gaz en utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Ne jamais utiliser...

Page 27: ...UNIT CONTROL BOARD W1 W2 C R G Y Y2 0 DEHUM P2 1 5 HUM LINE XMFR CONT EAC COOL PARK1 PARK2 HI HEAT LO HEAT NEUTRALS AUTO HEAT STAGE 10 5 NONE HOT SURFACE IGNITION VARIABLE SPEED BLOWER CONTROL BOARD C...

Page 28: ...208 230 Volt Single Phase Packaged Two Stage Heat Two Stage Electric Air Conditioner 60Hz WIRING DIAGRAM NOTES 1 Disconnect power before servicing 2 For supply connections use copper conductors only...

Page 29: ...Single Phase Packaged Two Stage Heat Two Stage Electric Air Conditioner 60Hz WIRING DIAGRAM NOTES 1 Disconnect power before servicing 2 For supply connections use copper conductors only 3 Not suitabl...

Page 30: ...fective Condenser coil is dirty Liquid line restriction filter drier blocked if present in system Thermostat is malfunctioning Solenoid plug not connected Y2 not wired at Comfort Alert Check thermosta...

Page 31: ...s flashing at same time means control circuit voltage is too low for operation Table 14 LED Diagnostics Continued Table 15 Module Wiring Troubleshooting MISWIRED MODULE INDICATION RECOMMENDED TROUBLES...

Page 32: ...repeat steps 1 through 3 until the system is correctly charged Charging Charts Application Notes This equipments cooling system contains refrigerant under high pressure always use safe practices when...

Page 33: ...igerant when below curve Remove refrigerant when above curve Figure 15 Charging Chart for 2 Ton Units Figure 16 Charging Chart for 3 Ton Units Liquid Pressure psig Liquid Temperature F R6GF X36 Chargi...

Page 34: ...igerant when below curve Remove refrigerant when above curve Figure 18 Charging Chart for 5 Ton Units Figure 17 Charging Chart for 4 Ton Units Liquid Pressure psig Liquid Temperature F R6GF X48 Chargi...

Page 35: ...35...

Page 36: ...nit YES NO ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity correct YES NO Rated Voltage VOLTS L1 L2 Volts __________________________________________________________________...

Reviews: