Reznor, PVE, Installation Manual EN 2019-11, D301113 iss D Page 33
Is polarity of
mains
corr
ect?
Check the bur
ner r
elay (E)
Replace the bur
ner r
elay (E)
Reposition the flame sensor
Can you
see a spark?
Check spark igniter -
check spark
gap, spark
wir
e and connector
The spark is visible,
but ther
e is no flame
Is ther
e 230V on the bur
ner
relay at terminals J 7 (3 and 4)
Check the multi
functional gas valve and
wiring
Corr
ect
polarity
No
No
No
No
No
Ye
s
Ye
s
No
Ye
s
Ye
s
Ye
s
No
Ye
s
No
Ye
s
Ye
s
Ye
s
No
W
ait 20 seconds and pr
ess the
lockout button on SmartCom3
W
ait 25 seconds and
check is the flame is
visible in the view point?
Check the flame signal using
the micr
o amp meter
. Is the
signal gr
eater than 0.2 micr
oA?
Is the signal gr
eater
than 0.2 micr
oA?
Is the sensor
located in the flame
Replace the
flame sensor
Is the heater
gr
ounded
Corr
ect i
f necessary
No
Do the inlet gas pr
essur
es
and the data badge have
the same data
Check the electr
onic
ignition contr
ol, i
f
necessary clean the contr
ol
Check the
bur
ner r
elay
During the 5 second trial
for ignition is a spark
visible?
Check the
bur
ner r
elay
Flame Failur
e 2a
Corr
ect gas
supply pr
essur
e