Reznor, PVE, Installation Manual EN 2019-11, D301113 iss D Page 11
Country code
Approved gas category
FR
I2Esi
BE
I2E(R)B
AT,CH,CZ,DK,EE,ES,FI,GB,GR,IE,IT,BGIS,LT,
LV,NO,PT,RO,SE,SI,SK,TR,CY,HR
I2H
PL,LU,DE,RO
I2E
DE
I2ELL
NL
I2Ek
BE,CZ,FR,IE,IT,ES,CH,GB,
SI,LU, SK,PT,PL,TR,GR,HR
I3P (37)
NL
I3P (30)
Table 6 : Approved gas categories
Model
30
50
72
95
120
145
Restriction
mm
70
80
67
78
130
130
Flue diameter
mm
100
100
130
130
130
130
Supply voltage
1*230V N
Power absorption
kW
1.25
1.90
1.85
2.90
3.10
3.40
Gross flue temperature
°C
100
120
140
145
140
140
Nett weight
kg
205
221
277
324
409
444
Electrical protection
IP
IP20
Appliance type
B22 C32 C12
Temperature rise
°C
36
38
40
34
34
30
Air flow
m³/s
0.8
1.05
1.5
2.3
3.05
3.66
Centrifugal static pressure
Pa
250
325
150
250
100
50
Sound level (3m)
dBA
63
67
64
74
74
76
NOx class
3
3
3
3
3
3
Minimum location/room temperature
°C
+5
Maximum location/room temperature
°C
+35
Table 7: Flue and electrical data
Electrical supply
Ensure the supply is in
accordance with the
manufacturer’s recommendations
and is as stated on the appliance data
plate.
The main electrical supply must not be
switched off or disconnected as a method
for stopping the heater, the exception
to this is in an emergency, or during
servicing, where the heat exchanger has
been given sufficient cooling time to
prevent damage from occurring.
Wiring external to the heater must be installed
in accordance with any local, national, and
European regulations.
The means of connection to the main electrical
supply must allow for complete electrical
isolation of the heater, furthermore, in the