Nortek PVE 120 Installation, Commissioning, Servicing Download Page 16

Page 14   Reznor, PVE, Installation Manual EN 2019-11, D301113 iss D

Natural ventilation openings to the 
heated space

When the heater(s) are to be installed in a 
heated space with an air change of less than 
0.5 / hour and without the connection of 
combustion ductwork. Then provision for low 
level natural ventila tion will be necessary.

The minimum free area of the low level natural 
ventilation opening shall be

2 cm

2

 for each kW of rated heat input

The low level natural ventilation opening 
should be situated on an external wall and 
be within 1000 mm of floor level for natural 
gas and ideally at floor level for L.P.G gas 
installations but in any event no higher than 
250 mm.

Model

High cm

2

Low cm

2

30

None

64

50

None

107

72

None

158

95

None

211

120

None

263

145

None

315

Table 8 : Minimum Free Area Of Natural 
Ventilation Opening (heated space)

When the heater(s) are to be installed in a 
heated space with an air change of less than 
0.5 / hour and without the connection of 
combustion ductwork. 

Using a mechanical ventilation system, rather 
than ventilation openings then 
 
•  The heated space needs to be mechanically 

ventilated so that the air change is equal or 
greater than 0.5/hour.

•  ONLY USE input type mechanical 

ventilation with a natural or mechanical 
extraction system

•  DO NOT use mechanical extraction with a 

natural inlet

•  It is necessary to provide an automatic 

means to safely inhibit heater(s) operation 
should mechanical air supply fail for any 
reason

Heaters installed within a plant 
room or enclosure.

For plant room applications the minimum 
free area of ventilation opening will depend 
upon whether the heater(s) is installed in room 
sealed mode (ie with a positive connection to 
atmosphere of both flue and combustion air).

Or with flue only (e.g. without the positive 
connection to atmosphere of a combustion air 
duct)

Where the heater(s) is installed in a plant room 
and in room sealed mode (e.g. with a positive 
connection to atmosphere of both flue and 
combustion air) the minimum free area of 
ventilation opening needs to be
•  At high level 5 cm

2

 for each kW of rated 

heat input.

•  At low level 5 cm

2

 for each kW of rated 

heat input

The high level ventilation opening should be 
sited on an external wall and positioned as 
high as is practical and always within the top 
15% of the wall height.

The low level natural ventilation opening 
should be situated on an external wall and 
be within 1000 mm of floor level for natural 
gas and ideally at floor level for L.P.G gas 
installations but in any event no higher than 
250 mm.

Model

High cm

2

Low cm

2

30

160

160

50

267

267

72

394

394

95

527

527

120

656

656

145

787

787

Table 9 : Minimum Free Area Of Natural 
Ventilation Opening (room sealed heaters)

Summary of Contents for PVE 120

Page 1: ...property damage injury or death All work must be carried out by appropriately qualified persons The manufacturer does not take any responsibility in the event of non observance of the regulations con...

Page 2: ......

Page 3: ...11 Pre installation 12 Warm air circulation 13 Air supply for combustion and ventilation 13 Flue requirements 16 Flue outlet 17 Air supply 18 Location of the heater 19 Gas piping and pressures 20 Elec...

Page 4: ...or maintenance can cause property damage injury or death Read the installation operation and maintenance instructions thoroughly before installing or servicing this equipment Do not use this appliance...

Page 5: ...must be positioned and installed to comply with all relevant standards and guidelines And should also meet the local and national fire regulations and insurance criteria carefull consideration should...

Page 6: ...ot be held responsible for any third party modifications to the heater The services that are to be connected fuel pipes power supply etc must be suitably secured and must not be dangerous with the ris...

Page 7: ...f the heater to ensure that they are familiar with the appropriate information manuals supplied by the manufacturer and the safety instructions In addition operators must be suitably trained in the us...

Page 8: ...re available for floor mounting only PVE heaters have been approved for alternative flue discharge arrangements but each heater must be connected to its own individual open flue these are detailed in...

Page 9: ...1232 1232 1242 1242 Flue diameter E 100 100 130 130 130 130 Flue connection F 240 240 283 272 260 261 G 100 100 111 100 101 102 H 95 95 115 155 101 221 I n a n a 259 300 381 380 Duct outlet PVED J 57...

Page 10: ...0 280 314 314 355 355 R n a n a 677 677 815 815 Nozzle plate centre line of the nozzle mounting hole S 492 492 659 659 1075 1110 T 208 208 209 209 281 242 U 197 197 235 235 222 236 V 481 481 645 645 5...

Page 11: ...e burner will not be adversely affected by high winds or draughts The height if applicable at which the heater is to be mounted and potential stratification circulation problems The position of the he...

Page 12: ...1 4 7 2 6 4 2 5 5 Main injector G25 natural gas mm 5 75 6 8 7 4 10 0 8 0 7 4 Natural gas G25 consumption m h 4 64 6 50 9 76 12 86 17 23 18 46 Nominal inlet pressure G25 3 natural gas mbar 25 Burner pr...

Page 13: ...0 8 1 05 1 5 2 3 3 05 3 66 Centrifugal static pressure Pa 250 325 150 250 100 50 Sound level 3m dBA 63 67 64 74 74 76 NOx class 3 3 3 3 3 3 Minimum location room temperature C 5 Maximum location room...

Page 14: ...tely Prior to installation the assembly of the heater should be completed it is advisable that this is undertaken in the area where the heater is to be sited obey the clearances in table 3 It is stron...

Page 15: ...ulations and rules in force In areas where it is proposed that more than one heater is to be installed a general scheme of circulation should be drawn up and maintained thereby offering the best heat...

Page 16: ...ical extraction system DO NOT use mechanical extraction with a natural inlet It is necessary to provide an automatic means to safely inhibit heater s operation should mechanical air supply fail for an...

Page 17: ...osphere of both flue and combustion air Or with flue only ie without the connection to atmosphere of a combustion air duct Where the heater s is installed in a plant room The maximum temperature withi...

Page 18: ...ments These unit heaters are designed to operate safely and efficiently with either a horizontal or vertical flue system when installed with the specific requirements and instructions If this heater i...

Page 19: ...a sealable test port Ideally the test port should be at least 450 mm away from the air heater flue connection socket However if a concentric flue fitting is attached directly to the connection socket...

Page 20: ...quires ventilation of the heated space Natural infiltration of air may not be adequate Use of exhaust fans aggravates this situation It is important to ensure that there is adequate combustion air sup...

Page 21: ...toward the exposed walls In large areas units should be located to discharge air along exposed walls with extra units provided to discharge air in toward the centre of the area For optimum results hea...

Page 22: ...ushing on a leak detecting solution Do not over tighten and do not rotate the gas valve inside the heater control compartment PVE Model Natural gas propane connection Inches 30 95 3 4 120 145 1 Table...

Page 23: ...Terminals shown may not be in numerical order Unused terminals may not be shown at all 900689 PVE Control Interconnections NEUTRAL LIVE 1 Phase 230v 50Hz L N 1 Phase Permanent Mains Supply Mains Fused...

Page 24: ...ot try to light the burner by hand Ensure that all pressure test points on the gas valve and manifold along with the pilot outlet plug see Figures 9 and 10 item 6 are fully closed and gas tight Before...

Page 25: ...f the gas tap when the fan has stopped 3 Switch off electric power to the appliance Check gas pressure as described in detail below Turn the unit off and on pausing 2 minutes between each cycle Observ...

Page 26: ...nd perform the following steps Using hex wrench adjust burner jet to corresponding burner diameter listed in Table 14 Adjust burner pressure to corresponding burner pressure listed in Table 15 Check i...

Page 27: ...et button visibly mounted on the heater will glow If no flame the starting procedure will be repeated five times after the 5th attempt unit goes into lockout mode After 120 seconds main fan will be sw...

Page 28: ...tenance at least once a year If the heater is operating in an area where an unusual amount of dust or other impurities are present in the air more frequent maintenance is recommended When any service...

Page 29: ...ight hand side of the heater Check that the manifold is straight the injectors are correctly aligned and that they are clean and that there are no contaminates restricting the orifices if necessary cl...

Page 30: ...ion With the light shining into the heat exchanger observe the outside surface of the tube where discolouration is evident Be sure to repeat this procedure with each heat exchanger tube If any light i...

Page 31: ...care when cleaning the fan blades to prevent causing misalignment or imbalance Check that the hub of the fan blades is secure to the shaft Follow these instructions for replacement of the fan guard f...

Page 32: ...the instructions on the lighting plate Check for proper operation Replace the access door Figure 19 PVE model 30 50 venter Figure 20 PVE model 72 90 venter Figure 21 PVE model 120 145 venter Combustio...

Page 33: ...he set point is reached the limit control will interrupt the electric power to the gas valve These safety devices provide protection in the case of motor failure or lack of airflow due to restrictions...

Page 34: ...ections Check fan runs correctly Automatic Controls Spark Ignition is via an ignition electrode Ensure that the ceramic insulation material is not damaged or cracked Flame supervision is via a flame s...

Page 35: ...Yes No Yes Yes Yes No Wait 20 seconds and press the lockout button on SmartCom3 Wait 25 seconds and check is the flame is visible in the view point Check the flame signal using the micro amp meter Is...

Page 36: ...essure Check if the fan operates ca 10 seconds after starting up the burner Line voltage disconnected Check if the switch point LC3 110 is OK Check if the fan continues to run for 3 minutes after the...

Page 37: ...le Cause Remedy Venter motor will not start 1 No power to unit Turn on power check supply fuses or circuit breaker 2 No power to venter motor Check connections at burner relay and or venter motor term...

Page 38: ...ng If voltage is available to burner relay and all other causes have been eliminated replace burner relay Check following in order Ensure that unit is properly vented Remove obstructions from vent Rep...

Page 39: ...35136 M337 Gas injector natural gas G20 G25 G25 3 07 25813 575 07 25813 680 07 25806 740 07 25806 1000 07 25813 800 07 25806 740 Gas injector LPG G31 07 25813 310 07 25813 370 07 25806 450 07 25806 52...

Page 40: ...At minimal capacity elmin kW 0 08 0 08 0 08 0 08 0 32 0 35 In standby mode elsb kW 0 02 0 02 0 02 0 02 0 03 0 03 Useful efficiency Useful efficiency at rated heating capacity nth nom 84 1 84 1 83 4 8...

Page 41: ......

Page 42: ......

Page 43: ......

Page 44: ...nor eu Nortek Global HVAC is a registered trademark of the Nortek Global HVAC limited Because of the continuous product innovation Nortek Global HVAC reserves the right to change product specification...

Reviews: