Nortek C6BA Series Installation Instructions Manual Download Page 4

4

 CAUTION:

The knockout must be removed and discarded 

to ensure proper condensate drainage. Failure to 

do so may result in structural damage, premature 

equipment failure, or possible personal injury.

4. Place the horizontal drain pan on the opposite side of the 

coil. 

NOTE:

 If unit has 2 sets of knockouts, remove the 

other set of knockouts in the coil spacing plates and insert 

support rod.

5. Install plug (from horizontal drain pan) in the open drain 

hole in the drain pan at the bottom of the unit. This will 

block bypass air from entering the system.

6. Slide the coil and the horizontal drain pan assembly back 

into the unit.

7. Remove the drain line knockout from the coil access door. 

This will allow access to the horizontal drain.

8. Install drain pan extension (if supplied with unit).
 

NOTE:

 The holes in the drain pan extension should be 

pressed over the nibs molded into the drain pan. Which 

pair of holes to use will depend on whether the unit is 

installed horizontal left or horizontal right. Verify proper 

positioning for clearance thru the top of the coil cabinet 

before affixing. The drain pan extension can be installed 

and removed after the ductwork has been attached to the 
cased coil.

9. Connect the refrigerant lines as outlined in the Refrigerant 

Lines Connection section.

10. Seal the enclosure as required to minimize air leakage.

11. Reinstall the coil access door.

12. Restore electrical power to the furnace.

Downflow Installations

C6 coils may be installed in downflow applications. It is 

required that the furnace and coil cabinets are securely 

mounted together before setting in place. Fossil fuel 

applications require the coil to be placed in the supply air 

stream only.

REFRIGERANT LINE CONNECTIONS

IMPORTANT NOTE TO INSTALLER

C6 Coils are not factory charged with refrigerant. It will 

be necessary to evacuate the indoor coil and lineset 

prior to charging. Refer to the outdoor unit installation 

manual for detailed charging instructions.

System Depressurization

1. Remove the cap from the end of the liquid line. See 

 

Figure 1

.

2. Verify pressurization by depressing the Schrader valve 

on the end of the liquid line. Listen for any escaping gas. 

If there is no pressure, test the coil for leakage.

•  If leakage is found, clearly mark the location of the leak 

and return the coil to the distributor for processing.

•  If no leaks are found, the coil may be installed.

3. Depress the valve to relieve all pressure from the coil.

4. Remove and discard the valve core and valve core holder 

on the liquid line.

5. Remove the rubber plug from the suction line.

Installing the TXV

(For Optional Bulkhead Mounted TXV’s)

1. Install the TXV retaining nut onto the inlet end of the TXV. 

See 

Figure 3 (page 6)

.

2. Add small amount of HVAC approved thread lock to the 

inlet end of the TXV.

3. Install the liquid line and accessory retaining nut onto the 

end of the TXV.

 CAUTION:

To prevent damage to the unit or internal 

components, it is recommended that two wrenches 

be used when loosening or tightening nuts. Do not 

over tighten!

4. Align the retaining nut on the TXV body and hand tighten 

both components. Mark a line on both bodies and then 

tighten an additional ¼ turn using two wrenches. See 

Figure 3

NOTE:

 The movement of the two lines will show 

how much the nut is tightened. If a torque wrench is used, 

tighten to 10-12 ft lbs or 14-16 Nm.

Connecting the Linesets

1. Remove the grommet from the suction line, making note 

of its orientation and fit.

2. Remove the coil access door.

3. Remove the rubber plug from the suction line.

4. Route and cut both lineset tubes to proper length in 

accordance with the outdoor unit specifications. Verify the 

ends are round, clean, and free of any burrs.

5. Place the grommet on the suction line of the lineset. 

NOTE:

 

DO NOT install grommet in the door cutout at this point. 

Allow sufficient distance to braze joint.

6. Connect the suction and liquid lineset tubes.

 CAUTION:

It is recommended that a wet rag be wrapped around 

the suction line in front of the close off plate before 

applying heat. Failure to keep components cool 

during brazing may result in structural damage, 

premature equipment failure, or possible personal 

injury.

7. Braze the individual connections with dry nitrogen flowing 

through the joints.

Suction 

Line

Liquid 

Line

Cap

Cap

Schrader 

Valve

Figure 1. 

Suction & Liquid Line Locations

Summary of Contents for C6BA Series

Page 1: ...ntion to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or pro...

Page 2: ...Unqualified individuals should not attempt to interpret these instructions or install this equipment If you do not posses mechanical skills ortools callyourlocaldealerforassistance Under no circumsta...

Page 3: ...ssaryclose offplatesaroundtherefrigerant lines and drain line where required Reinstall all inner and outerpanelsofthefurnace airhandlerthatwerepreviously removed when installing the indoor coil Upflow...

Page 4: ...2 Verify pressurization by depressing the Schrader valve on the end of the liquid line Listen for any escaping gas If there is no pressure test the coil for leakage If leakage is found clearly mark th...

Page 5: ...y the grommet is evenly aligned around the tube and securely positioned in the door cutout COMPLETING THE INSTALLATION 1 Position the drain pan so the connections are aligned with the corresponding kn...

Page 6: ...Coil Dimensions W HS HL H 5 8 4 17 3 4 20 3 4 FRONT VIEW TOP VIEW Distributor Thermal Expansion Valve TXV Door TXV Retaining Nut Liquid Line Stub w Screen Accessory Retaining Nut Grommet Figure 3 TXV...

Page 7: ...IONS MODEL C6BH 1 2 T24 A X24 A T30 A X30 A X35 A T24 B X24 B X26 B T30 B X30 B X35 B T36 B X36 B T42 B X42 B T36 C X36 C T42 C X42 C T48 C X48 C T60 C X60 C T42 D X42 D T48 D X48 D T60 D X60 D N omin...

Page 8: ...8...

Page 9: ...on tous les avertissements de s curit et toute autre remarque sp ciale donn e dans le manuel L installation inappropri e de la fournaise ou le non respect des avertissements de s curit risque d entra...

Page 10: ...endant son installation son entretien et son utilisation Les personnesnonqualifi esnedoiventpastenterd interpr ter ces instructions ou d installer cet quipement Si vous ne poss dez pas les comp tences...

Page 11: ...la Liste des pi ces de rechange pour les num ros de pi ces disponibles Installez les plaques de fermeture requises autour des conduites de frigorig ne et conduites d vacuation au besoin R installez to...

Page 12: ...bout de la conduite de liquide coutez pour d tecter toute fuite de gaz S il n y a pas de pression v rifiez s il y a une fuite dans le serpentin Si une fuite est d tect e marquez clairement l emplaceme...

Page 13: ...nt dans l entr e d fon able de la porte FINALISATION DE L INSTALLATION 1 Positionnez le plateau de d givrage de mani re ce que les raccords soient align s avec les d bouchures correspondants 2 V rifie...

Page 14: ...4 20 3 4 VUE AVANT VUE DE DESSUS Distributeur D tendeur thermostatique TXV Serrure crou de retenue du d tendeur thermostatique Embout de la conduite de liquide avec tamis crou de retenue d accessoire...

Page 15: ...X35 A T24 B X24 B X26 B T30 B X30 B X35 B T36 B X36 B T42 B X42 B T36 C X36 C T42 C X42 C T48 C X48 C T60 C X60 C T42 D X42 D T48 D X48 D T60 D X60 D Capacit nominale BTUH 3 24 000 30 000 36 000 24 0...

Page 16: ...ubjecttochangewithoutnoticeorincurringobligations 10 22 O Fallon MO Nortek Global HVAC LLC 2022 All Rights Reserved Sp cifications et illustrations sujettes changements sans pr avis ou sans aucune obl...

Reviews: