background image

7

6.  Insert the new orifice in the distributor body 

rounded end down

 as shown in Figure 5.

7.  After installing the orifice in the distributor 

body, realign the assembly nut to the 
distributor body. Mark a line along both 
bodies after hand tightening and then tighten 
an additional 1/4 turn. 

Caution: Do not 

overtighten!

 The misalignment of the two 

lines will show how much the nut is tightened. 
If a torque wrench is used, tighten to 10-12 

ft. lbs. or 14-16 Nm.

Line Connections:

8.   Making note of orientation, remove the hole 

grommets and tube close-off insulation from 
around the coil and refrigerant line set.

9.  Remove the valve cap from the end of the 

liquid line. Relieve all pressure from the coil 
by depressing the valve.  Remove the valve 
core.

Note: 

On  models  which  use  a  TXV,  it  is 

recommended  to  wrap  a  wet  rag  around  the 
suction line between the sensing bulb and the 
line set braze joint before applying any heat. 

 

10.  Unbraze and remove the cap on the suction 

line.  Unbraze and remove the valve core 

holder on the liquid line.

11.   Cut  the  line  set  tubing  to  the  proper 

length.  Be  sure  that  the  tubing  has  been 
sized in accordance with the outdoor unit 

specifications.

12.  Inspect both refrigerant lines. The ends of 

the lines must be round, clean, and free of 
any burrs.

13.  Place grommets in proper orientation onto 

line  set  with  sufficient  distance  to  braze 
joint.

14.  Insert the line set tubes into the coil tube 

stubs until they bottom out.

15.  Braze  the  individual  connections  with 

dry  nitrogen  flowing  through  the  joints  to 

eliminate internal oxidation and scaling.

 

NOTE:

 On models which use a TXV, it is 

recommended  to  wrap  a  wet  rag  around 
the suction line between the sensing bulb 
and the line set braze joint before applying 

any heat.

16.  Check the assembly for leaks.
17.  On horizontal applications of models with 

TXV valve, re-position the sensing bulb on 
the suction line so it is in the 4 o'clock or 8 
o'clock position on the suction tube.

18.   Properly dispose of all removed parts.

6. COMPLETING THE INSTALLATION

Condensate Drain:

 CAUTION:

The indoor coil must be checked to 
ensure a level installation. Failure to do 
so may result in improper condensate 
disposal, causing structural damage, 
premature equipment failure, or 
possible personal injury.

1.  The coil condensate pan is furnished with 

3/4" NPSC drain connections. Use a PVC 

or similar material fitting to attach the drain 
line to the pan. The fitting should be hand 
tightened only. 

Overtightening may crack 

Figure 3. Wrenches on Distributor Body

and Assembly Nut

Figure 4. Removal of Orifice

Figure 5. Restrictor Insertion in 

Distributor Body

Summary of Contents for C5B

Page 1: ...tionsand orfurnace air handler markings before proceeding with installation of the coil These instructions are primarily intended to assist qualified individuals experienced in the proper installation...

Page 2: ...izontal Furnace Horizontal Ready Coils for Horizontal Left Installation Horizontal Ready Coils for Horizontal Right Installation 4 Verify Pressurization 6 5 Refrigerant Line Connections 6 6 Completing...

Page 3: ...tdoor unit NOTE Some coils employ a thermostatic expansion valve TXV as the metering device See page 4 H 20 3 4 B 16 5 8 W A 3 4 133 8 155 8 19 3 4 Figure 1 3 Wherepreciseformingoftherefrigerantlines...

Page 4: ...63 913963 913963 913964 913964 913964 Extra Orifice in N A 0 053 for 1 5 ton condenser N A N A 0 053 for 1 5 ton condenser N A N A N A N A N A N A N A N A Coil Model 1 C5BA H T X24C A C5BA H T25C A C5...

Page 5: ...the threaded holes of the horizontal drain pan If webbing is not removed the drain will not function properly and ceiling damage may occur 3 Insert a plug from the horizontal drain pan into the open a...

Page 6: ...id direct face exposure or contact with valve when gas is escaping Always ensure adequate ventilation ispresentduringthedepressurization process Any uncertainties should be addressed before proceeding...

Page 7: ...ends of the lines must be round clean and free of any burrs 13 Place grommets in proper orientation onto line set with sufficient distance to braze joint 14 Insert the line set tubes into the coil tub...

Page 8: ...coil case and furnace that were previously removed to install the indoor coil Refrigerant Charging These cased indoor coils are not factory charged with refrigerant It will be necessary to evacuate th...

Reviews: