background image

8

Orifice Removal & Installation

 CAUTION:

Before brazing the air handler, remove the core 
from the service port. Failure to comply may 
result in leakage at the service valve. Replace 
the core and cap once brazing is complete.

 WARNING:

This coil is pressurized with Nitrogen. Pressure 
must be relieved in order to prevent the potential 
of an injury or fatality from the cap during the 
removal process. Avoid direct face exposure or 
contact with valve when gas is escaping. Always 
ensure adequate ventilation is present during 
the depressurization process. Any uncertainties 
should be addressed before proceeding.

NITROGEN

HEALTH

FLAMMABILITY

REACTIVITY

0 Minimal Hazard

1 Slight Hazard

1

0

0

Refrigerant Line Connections

 WARNING:

The coil in the air handler is factory shipped with 
a nitrogen charge. Avoid direct face exposure 
or contact with valve when gas is escaping. 
Always ensure adequate ventilation is present 
during the depressurization process. Address 
any uncertainties before proceeding. Failure 
to comply with this warning could result in 
equipment damage, personal injury, or death.

NITROGEN

HEALTH

FLAMMABILITY

REACTIVITY

0 Minimal Hazard

1 Slight Hazard

1

0

0

 CAUTION:

Before charging, refer to the units rating label 
for proper refrigerant information. Only use 
refrigerant specified on the rating label. Use of 
another refrigerant will damage the unit.

•  The  installer  should  make  every  effort  to  ensure  the 

field installed refrigerant containing components of the 
system have been installed in accordance with these 
instructions and sound installation practices for reliable 
system operation and longevity.

•  The air handler coil does not contain a refrigerant charge. 

Refer to the installation instructions supplied with the 
outdoor unit for refrigerant charge information.

•  Always refer to the installation instructions supplied with 

the outdoor unit for piping requirements. The suction 
and liquid lines must be sized in accordance with the 
condensing unit specifications. See Figure 11 (page 
16) for liquid and suction line locations.

•  When  connecting  refrigerant  linesets  together,  it  is 

recommended that dry nitrogen be flowing through the 
joints during brazing. This will prevent internal oxidation 
and scaling from occurring.

•  Refrigerant tubing should be routed in a manner that 

minimizes the length of tubing and the number of bends 
in the tubing. It should be supported in a manner that 
prevents it from vibrating or abrading during system 
operation. Tubing should be kept clean of foreign debris 
during installation.

•  If precise forming of refrigerant lines is required, a copper 

tubing bender is recommended. Avoid sharp bends and 
contact of the refrigerant lines with metal surfaces.

•  Refrigerant  lines  should  be  wrapped  with  pressure 

sensitive neoprene or other suitable material where 
they pass against sharp sheet metal edges.

The orifice installed in the air handler has been sized for 
use with the most popularly matched outdoor units. The 
orifice size as shipped from the factory is listed on the air 
handler rating plate. Perform steps 1 - 9 to confirm that 
the orifice size meets the requirements outlined in the 
outdoor unit installation manual.

1. Remove the cap from the end of the liquid line.
2. Verify pressurization by depressing the Schrader valve 

on the end of the liquid line. Listen for any escaping gas. 
If there is no pressure, test the coil for leakage.

•  If leakage is found, clearly mark the location of the leak 

and return the coil to the distributor for processing.

•  If no leaks are found, the coil may be installed.

3. Depress the valve to relieve all pressure from the coil.
4. Remove and discard the valve core.

 CAUTION:

To prevent damage to the unit or internal 
components, it is recommended that two 
wrenches be used when loosening or tightening 
nuts. Do not over tighten!

5. Using two wrenches, loosen the nut and distributor 

body as shown in Figure 6 (page 9). Turn the assembly 
nut counter-clock-wise until the orifice body halves are 
seperated.

Summary of Contents for B5BM

Page 1: ...ion service adjustment or maintenance may cause explosion fire electrical shock or other hazardous conditions which may result in personal injury or property damage Unless otherwise noted in these ins...

Page 2: ...ns 11 Control Board 12 Twinning 12 Heater Kits 12 Startup Adjustments 12 Before You Start the Unit 12 Refrigerant Charging 13 Air Circulation 13 Running the Blower Continuously 13 Continuous Low Speed...

Page 3: ...his unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in possible damage to the equipment...

Page 4: ...ervice access and noise The dimensions of the room or alcove must be able to accommodate the overall size of the unit and the installation clearances listed in Figure 1 Physical dimensions for this ai...

Page 5: ...duct opening or filter rack located in the bottom of the unit Accessing the filter does not require tools and can be removed from the front of the unit by removing the filter door See Unit Maintenanc...

Page 6: ...hen installing the unit in an upflow configuration All return air must enter from the bottom of the unit A typical upflow unit is shown in Figure 2 Downflow Installations Thedownflowaccessorykit SeeTe...

Page 7: ...orizontal drain pan into the open and unused drain hole in the drain pan at the bottom of the unit to block bypass air 4 Remove the corresponding drain line knockout from the coil access door to allow...

Page 8: ...quid lines must be sized in accordance with the condensing unit specifications See Figure 11 page 16 for liquid and suction line locations When connecting refrigerant linesets together it is recommend...

Page 9: ...h lineset tubes to proper length in accordance with the outdoor unit specifications Verify the ends are round clean and free of any burrs 4 Positiongrommetonlinesetwithsufficientdistanceaway from braz...

Page 10: ...ccurring 7 Wrap the refrigerant lines with pressure sensitive neoprene or other suitable material especially where the lines enter the opening in the sheet metal 8 Evacuatethesystemofmoistureandnon co...

Page 11: ...the unit Use only copper wire for the line voltage power supply to this unit Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit Aluminum supply...

Page 12: ...vided 3 Connect the heater kit plug with the mating receptacle on the air handler control board If a heater kit is not installed 1 Remove the 2 wire plug of the air handler by cutting the wires and di...

Page 13: ...un for several minutes and then set the thermostat s temperature below room temperature Verify the blower cycles off with the thermostat Minimum Electric Heat Airflow The minimum electric heat airflow...

Page 14: ...he factory It is recommended that the filter be cleaned or replaced monthly Newly built or recently renovated homes may requiremorefrequentchanginguntiltheconstructiondust has minimized Filter sizes s...

Page 15: ...11 4 15 8 17 8 11 4 3 1 4 2 5 8 11 8 K O typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A Cabinet Size H W A Detail D A 43 5 16 14 3 16 12...

Page 16: ...Motor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Control Board Filter Door Upper Door Assem...

Page 17: ...1270 1196 1113 1018 913 Corrected ESP1 0 00 0 00 0 00 0 09 0 23 0 36 0 50 0 64 42 48K B Cabinet Low 1324 1302 1271 1233 1187 1134 1072 1003 Corrected ESP1 0 00 0 06 0 17 0 27 0 38 0 49 0 61 0 72 Medi...

Page 18: ...Conditioner with Variable Speed Air Handler Typical 2 Stage Cooling Heat Pump with Optional Outdoor Thermostat Variable Speed Air Handler W2 W1 O Y Y2 G R C W2 W1 O Y Y2 G R C Y2 Y2 Y2 Y2 W1 W3 R Y1...

Page 19: ...19 C R G Y Y2 O W1 W2 Y1 24VAC COM FUSE P2 P3 X13 COM X13 HEAT X13 COOL XFMR L1 VSPOWER L1 L2COM L2 L2 Figure 13 Motor Control Board...

Page 20: ...8 9 10 11 12 13 14 15 16 G C O HUM Y1 W R HUM Y Y2 L2 COM 2 L2 L2COM L1 VS POWER XFMR COOL HEAT Y1 HEATER PLUG P3 1 2 3 4 5 6 7 8 YELLOW BLUE RED JUMPER SELECTOR SWITCHES NOTE 1 ON 0 OFF 710544D Repl...

Page 21: ...IELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE The blower motor speed tap connection may not be as shown See the Installation Instructions Disconnect all power before servicing Transformer may have a dua...

Page 22: ...ct all power before servicing 3 Transformer may have a dual voltage primary tap Match the tap position with the supply voltage used 4 If the Internal wiring is replaced use only 105 C copper wire of t...

Page 23: ...K GREY BLACK GREY BLUE ORANGE POWER PLUG LIMIT RED RED RED RED BLACK BLACK RED BLACK RELAY RELAY TERMINAL BLOCK for select models only CIRCUIT BREAKER Circuit breaker models only BLUE W2 W1 O Y Y2 G R...

Page 24: ...pply voltage used 4 If the Internal wiring is replaced use only 105 C copper wire of the same gauge W2 W1 O Y Y2 G R C 4 SPD MOTOR 1 2 3 5 6 4 TRANSFORMER 24V BLACK RED WHITE BLACK WHITE FUSE L2 COM 2...

Page 25: ...1 2 3 5 4 TRANSFORMER 24V BLACK RED WHITE BLACK WHITE FUSE BLOWER MOTOR PLUG C L G N N NEUTRAL G GROUND L LINE C COMMON L2 L2 L2 COM L1 L1 XFMR X13 COOL X13 HEAT 24 VAC RED COM GREY Y1 C L G N WHITE X...

Page 26: ...1 only On Stage 1 Heat on instantly Heat blower on after 3 second delay Stage 3 5 Heat on after 1 minute delay Stage 2 Heat on after 2 minute delay Stage 4 6 Heat on after 3 minute delay Off Heat stag...

Page 27: ...27...

Page 28: ...sareprimarilyintendedtoassistqualifiedindividuals experienced in the proper installation of this appliance Some local codes require licensed installation service personnel for this type of equipment P...

Reviews: