i
Appendix-A
Nortec GS
2583703_EN_1608
A
Appendix
A.1
Installation Checklist
The following is a consolidated installation checklist that can be used in the commissioning of the unit:
Mounting
Unit installed in the correct location (according to
"Clearances" on page 20
)?
Adequate clearance for servicing unit?
Mounting surface stable, and capable of supporting the full operating weight of the humidifier?
Unit level?
Unit secured properly?
Steam Line
Observed all best practices?
Steam pipe sized correctly?
The steam line does not exceed maximum equivalent length listed in
Table 12 on page 30
?
Long radius elbows (for rigid pipes) used?
Backpressure in the line combined with duct static pressure does not exceed 6 in H2O (1.49 kPa)
for compact units, or 10 in H2O (2.49 kPa) for full-size units?
Steam line runs straight up from the humidifier steam outlet for at least 12 in (300 mm) before bend?
Steam line has minimum upslope of 10°, or minimum downslope of 2°?
Steam line does not reduce in diameter except at the steam distributor; and condensate line installed
just before the restriction?
Steam lines do not merge except at the steam distributor through a Nortec adaptor?
Steam line does not sag?
Steam connections secured with clamps? Clamps torqued adequately?
Allowances made for thermal expansion of rigid pipes, and shrinkages of steam hose?
Steam line insulated over its entire length?
Condensate Line
Local regulations on drain water temperature requirements have been satisfied?
Condensate traps installed at all low points, and at horizontal-to-vertical transitions in the steam line?
Condensate lines in the steam line always connect to full-size "Tee" connectors?
Condensate traps have a minimum loop diameter of 12 in (300 mm) and installed at least 12 in
(300 mm) below the condensate "Tee" and the steam distributor?
All condensate lines have a minimum downslope of 1.2°?
Condensate traps primed with water?
Summary of Contents for GS
Page 3: ...INSTALLATION MANUAL Gas fired Steam Humidifier Nortec GS 2583703_EN_1608 ...
Page 12: ...6 For Your Safety 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Page 14: ...8 Receiving and Storage 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Page 20: ...14 Product Overview 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Page 72: ...66 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Page 78: ...72 Product Specifications 2583703_EN_1608 Nortec GS This page intentionally left blank ...
Page 82: ...iv Appendix A 2583703_EN_1608 Nortec GS This page intentionally left blank ...