- 3 -
Snap on Installation
Steamline
Steam Outlet
B or BH Venting Type
Control Wiring
Main Power Disconnect
Shut Off
To Drain
Auxiliary Drain
Air Gap with Funnel
Service Access Door
(Mechanical)
Service Access
Door (Electrical)
Clean Out
Access Door
Optional Stand
Drain
Gas Line
Connection
Fresh Water
Fill Line
3/4"min 30-80 psi
Exhaust Outlet
Optional
Direct Vent
Figure #1
Typical Installation (Indoor)
HIGH ALTITUDE
- A derate in input exists for installations at higher altitudes. For Canadian models, an automatic
10% derate applies to installations from 2000-4500 feet. For U.S. Models, refer to the chart below for high altitude
derate information.
FOR U.S. MODELS ONLY
Altitude
Derate %
Feet
Meters
0-2000
0-610
0
2001-3000
610-915
8
3001-4000
915-1220
12
4001-4500
1220-1370
16
4501-higher
1370-higher
Contact Factory