5. MAINTENANCE AND INSPECTION
possibly be released to the surrounding space. Prior to work taking place, the area around the
equipment is to be surveyed to make sure that there are no flammable hazards or ignition
risks. “No Smoking” signs shall be displayed.
Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the
system or conducting any hot work. A degree of ventilation shall continue during the period
that the work is carried out. The ventilation should safely disperse any released refrigerant
and preferably expel it externally into the atmosphere.
Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the
correct specification. At all times the manufacturer's maintenance and service guidelines shall
be followed. If in doubt consult the manufacturer's technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
The charge size is in accordance with the room size within which the refrigerant containing
parts are installed;
The ventilation machinery and outlets are operating adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the
presence of refrigerant;
Marking to the equipment continues to be visible and legible. Markings and signs that are
illegible shall be corrected;
Refrigeration pipe or components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant containing components, unless the
components are constructed of materials which are inherently resistant to being corroded or
are suitably protected against being so corroded.
Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and
component inspection procedures. If a fault exists that could compromise safety, then no
electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the
fault cannot be corrected immediately but it is necessary to continue operation, an adequate
temporary solution shall be used. This shall be reported to the owner of the equipment so all
parties are advised.
Initial safety checks shall include:
-
That capacitors are discharged: this shall be done in a safe manner to avoid possibility of
sparking;
-
That there no live electrical components and wiring are exposed while charging,
recovering or purging the system;
-
That there is continuity of earth bonding.
Repairs to sealed components
1) During repairs to sealed components, all electrical supplies shall be disconnected from the
equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely
necessary to have an electrical supply to equipment during servicing, then a permanently
operating form of leak detection shall be located at the most critical point to warn of a
potentially hazardous situation.
2) Particular attention shall be paid to the following to ensure that by working on electrical
Summary of Contents for 7026965
Page 28: ...4 OPERATION AND USE Controller interface diagram and definition ...
Page 35: ...5 MAINTENANCE AND INSPECTION requirements ...
Page 45: ...Note Code 83900146 ...
Page 74: ...4 BETJENING OG BRUG Controllergrænsefladens diagram og definition ...
Page 91: ...6 SPECIFIKATION Bemærk Kode 83900146 ...
Page 120: ...4 BETRIEB UND VERWENDUNG Steuerungsschnittstellendiagramm und Definition ...
Page 137: ...Hinweis Code 83900146 ...
Page 166: ...4 FONCTIONNEMENT ET UTILISATION Schéma et définition de l interface du contrôleur ...
Page 183: ...Remarque Code 83900146 ...
Page 212: ...4 WERKING EN GEBRUIK Controller interface diagram en definitie ...
Page 229: ...Nota Code 83900146 ...
Page 257: ...4 DRIFT OCH ANVÄNDNING Controller gränssnittsschema och definition ...
Page 273: ...Notera Kod 83900146 ...