background image

21

10.

 Water Piping

This appliance is suitable for combination potable water and space heating applications. It cannot be used for space 
heating applications only. Do not use this appliance if any part has been underwater.  Immediately call a quali ed 
service technician to inspect the appliance and replace any part of the control system and gas control which has 
been under water.

If the water heater is installed in a closed water supply system, such as one having a back ow preventer in the 
cold water supply line, means shall be provided to control thermal expansion. Contact the water supplier or a local 
plumbing inspector on how to control this situation.

A pressure relief valve must be installed near the hot water outlet that is rated in accordance with and complying 
with either The Standard for Relief Valves and Automatic Shutoff Devices for Hot Water Supply Systems, ANSI 
Z21.22, or The ANSI/ASME Boiler and Pressure Vessel Code, Section IV (Heating Boilers). This pressure relief 
valve must be capable of an hourly Btu rated temperature steam discharge of 180,000 Btuh(NRC98-DV), 157,000 
Btuh(NRC83-DV). Multiple valves may be used. The pressure relief capacity must not exceed 150 psig. No valve 
shall be placed between the relief valve and the water heater. The relief valve must be installed such that the dis-
charge will be conducted to a suitable place for disposal when relief occurs. No reducing coupling or other restric-
tion may be installed in the discharge line. The discharge line must be installed to allow complete drainage of both 
the valve and the line. If this unit is installed with a separate storage vessel, the separate vessel must have its own 
temperature and pressure relief valve. This valve must also comply with The Standard for Relief Valves and Au-
tomatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22. (in the U.S. only). A temperature relief 
valve is not required, but if one is used, do not install the valve with the probe directly in the  ow of water. This may 
cause unwarranted discharge of the valve.

Piping and components connected to the water heater shall be suitable for use with potable water.
Toxic chemicals, such as those used for boiler treatment, shall not be introduced into the potable water.
A water heater used to supply potable water may not be connected to any heating system or components previ-
ously used with a nonpotable water heating appliance.
When water is required in one part of the system at a higher temperature than in the rest of the system, means 
such as a mixing valve shall be installed to temper the water to reduce the scald hazard.

Installation and service must be performed by a quali ed plumber.  In the 
Commonwealth of Massachusetts, this product must be installed by a licensed 
plumber or gas  tter in accordance with the Massachusetts Plumbing and Fuel 
Gas Code 248 CMR Sections 2.00 and 5.00. Observe all applicable codes.

•  Flush water through the pipe to clean out metal powder, sand and dirt before connecting it.
•  Perform the following insulation measures for prevention of freezing. 
•  Take appropriate heat insulation measures (e.g., wrapping with heat 

insulation materials, using electric heaters) according to the climate of 
the region to prevent the pipe from freezing.

•  Make sure that there are no water leaks from the cold and hot water 

supply pipes, then insulate the pipes completely. 

•  Be sure to also completely insulate the water supply valve and the 

cold and hot water connections on the water heater (refer to the  gure 
on the right).  

•  Do not cover the water drain plug with insulation so that water in the 

pipe can be drained. (Refer to the  gure in the right.)  

•  Use a union coupling or  exible pipe for connecting the pipes to reduce the force applied to the piping.
•  Do not use piping with a diameter smaller than the coupling.
•  When feed water pressure is too high, insert a depressurizing valve, or take water hammer prevention measure.
•  Avoid using joints as much as possible to keep the piping simple.
•  Avoid piping in which an air holdup can occur.
•  If installing the unit on a roof:
•  About lower-level hot water supply
  If the unit is installed on a roof to supply water to the levels below, make sure that the water pressure supplied 

to the unit does not drop below 29 psi. It may be necessary to install a pump system to ensure that the water 
pressure is maintained at this level.

  Check the pressure before putting the unit into operation.
  Failure to supply the proper pressure to the unit may result in noisy operation, shorter lifetime of the unit, and 

may cause the unit to shut down frequently.

Completely insulate 
the water inlet and 
outlet fittings.

Insulate the water 
supply valve completely.

Do not cover the water 
drain plug with insulationso t
can be drained.

Summary of Contents for NRC83-DV

Page 1: ...d by erroneous work or work not as instructed in this manual are not covered by the warranty Check that the installation was done properly in accordance with this Installation Manual upon completion A...

Page 2: ...lation Q ty Shape Part Part Shape Q ty Remote Controller Cord 26ft 8m Quick Connect Cord QC 2 1 1 1 each Isolation Valves includes pressure relief valve Owner s Guide Warranty Installation Manual this...

Page 3: ...e The hot water temperature will become unstable as the pipe length increases Distance at center 20 3 36 3 in 515 922mm Quick Connect Cord Union Gas Valve Union Shutoff Valve Shutoff Valve Hot Water S...

Page 4: ...Caution if Using With a Solar Pre Heater Using this unit with a solar pre heater can lead to unpredictable output temperatures and possibly scalding If absolutely necessary use mixing valves to ensure...

Page 5: ...result Avoid installation in places where special chemical agents e g hair spray or spray detergent are used Ignition failures and malfunction may occur as a result Carbon Monoxide Poisoning Hazard D...

Page 6: ...nal noises while it is running Before installing make sure that the exhaust ue termination will have the proper clearances according to the National Fuel Gas Code ANSI Z223 1 State of California The w...

Page 7: ...the unit to facilitate maintenance and service if necessary If possible leave 3 75mm or more above and below the vent pipe to facilitate inspection and repair if necessary Securing of space for repai...

Page 8: ...Illustration Outdoor Clearances to Opening into Any Building 12 300mm or more 12 300mm or more There must be no building opening within this area Flue terminal 12 300mm or more 12 300mm or more Vent C...

Page 9: ...aintain clearances in accordance with local installation codes and the requirements of the gas supplier A vent shall not terminate directly above a sidewalk or paved driveway that is located between t...

Page 10: ...installing Internal parts may be damaged and may become highly dangerous Install the unit on a vertical wall and ensure that it is level Locating Screw Holes Mounting Structure When installing with ba...

Page 11: ...t accessory on the top of the appliance as illustrated below Or if the vent pipe has already been installed 2 After installing the drain pipe make sure that the area around the appliance is well venti...

Page 12: ...temperature in excess of 149 F 65 C and schedule 40 PVC pipe may be used as the vent material If required by local code schedule 40 or 80 CPVC may also be used on this appliance Refer to page 13 for a...

Page 13: ...for the location of the dip switch bank 0 3 6 9 12 15 18 21 24 27 30 32 35 38 41 44 47 50 53 56 62 0 00 0 90 1 80 2 70 3 60 4 50 5 40 6 30 7 20 8 10 9 00 9 90 10 80 11 70 12 60 13 50 14 40 15 30 16 20...

Page 14: ...practices must be observed o Squarely cut all pieces of pipe o Remove all burs and debris from joints and fittings o All joints must be properly cleaned primed and cemented Use only cement and primer...

Page 15: ...National Fuel Gas Code ANSI Z223 1 NFPA 54 Slope the horizontal vent 1 4 upwards for every 12 300mm toward the termination Use a condensation drain if necessary In the Commonwealth of Massachusetts a...

Page 16: ...s fuel equipment Please refer to Technical Bulletin TB 010606 for full installation in structions Slope vent Upwards 4 100mm pipe requires the use of a reducing coupling just prior to the termination...

Page 17: ...must be supplied from the outdoors as shown on pages 15 16 Terminate at least 6 1 8m from the combustion air intake of any appliance and 3 0 9m from any other building opening gas utility meter servi...

Page 18: ...a mechanical closet provide a 600mm 24 clearance in front of the unit to the door If combustion air will be provided through a duct size the duct to provide 60 cubic feet of fresh air per minute Supp...

Page 19: ...ee next page for the pipe capacity charts Noritz Condensing Tankless Gas Water Heater NRC98 DV 180 000 Btuh NRC83 DV 157 000 Btuh Clothes Dryer 35 000 Btuh Barbecue 50 000 Btuh Gas Range Stove 65 000...

Page 20: ...32 252 511 787 1496 55 112 213 440 675 1260 Maximum Capacity of Flex TracPipe in Cubic Feet per Hour of Natural Gas 0 60 Specific Gravity 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1...

Page 21: ...to supply potable water may not be connected to any heating system or components previ ously used with a nonpotable water heating appliance When water is required in one part of the system at a higher...

Page 22: ...eans to en sure that the supply water pressure to the inlet of the heater does not fall below 29 PSI when the maximum amount of water is being demand ed Also install a pressure meter on the inlet If t...

Page 23: ...een ON and OFF oF PRIORITY LED goes out on PRIORITY LED blinks 6 If 2D also needs to be changed repeat steps 4 and 5 7 To con rm the settings press the Setting Buttons and simultaneously for more than...

Page 24: ...Treatment Required Install Noritz Isolation Valves to allow for flushing Flushing is required if a water treatment device is not installed Suggested Suggested Install Noritz Isolation Valves to allow...

Page 25: ...Long runs or applications where the nearest drain is above the water heater will require the use of a condensate pump Size the pump to allow for a maximum condensate discharge of 2 GPH from the water...

Page 26: ...CLEARANCE DO NOT ADD ANY VALVES DO NOT ADD ANY VALVES NORITZ Condensing Tankless Gas Water Heater NORITZ Condensing Tankless Gas Water Heater Note If the drain line becomes clogged or frozen condensa...

Page 27: ...the pump Set the Aquastat to 10 F 5 C below the set output temperature 4 Noritz recommends the use of an Isolation Kit with the installation These kits include an integrated shut off and serv ice valv...

Page 28: ...the water heater will not activate resulting in possible freezing damage Do not let the power cord contact the gas piping Tie the redundant power cord out side the water heater Putting the redundant...

Page 29: ...FF button on the remote controller To keep the water heater off let the unit sit for 30 sec to return to the original display The NRC98 DV NRC83 DV can be programmed so that it will default to one of...

Page 30: ...t the end of the remote controller cord to the terminal block 5 Replace the terminal block cover and install the screw previously removed in step 3 6 Reconnect electrical power to the water heater Ext...

Page 31: ...om a wall circuit to the pump 5 Replace the front cover Pump Wiring This feature is not available when using the Quick Connect Multi System feature Relay connection with larger pumps 85 W 1 Locate and...

Page 32: ...ling Cord Clamp Ground wire Connector Connector Connecting Quick Connect Cord 2 Caution For Quick Connect Multi System Installation use part QC 2 only sold separately Quick Connect Cord 2 Quick Connec...

Page 33: ...proper blue color and consistency If the ame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a quali ed service technician Do not ob...

Page 34: ...ower to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop a...

Page 35: ...00mm 2 8 70mm 1 4 36mm 6 7 170mm 5 5 140mm 3 9 100mm 2 8 70mm 1 4 36mm 1 6 40mm 2 4 61mm 5 5 140mm 9 4 240mm 1 1 28mm 26 2 665mm 23 1 586mm 0 4 10mm 4 0 5 13mm 6 0 24 x 0 4 6mm x 10mm OBLONG HOLE 0 4...

Page 36: ...on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the con troller Avoid location...

Page 37: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Reviews: