background image

14

WARNING

CARBON MONOXIDE POISONING
Failure to properly seal the vent system could 
cause flue products to enter the living space.

Item Material 

United 

States 

Canada 

Exhaust Vent/Air Intake

 

Schedule 40 PVC 

ANSI/ASTM D1785 

ULC S636 Certified 

Materials Only 

PVC-DWV ANSI/ASTM 

D2665 

Schedule 40 CPVC 

ANSI/ASTM F441 

Pipe Cement/Primer 

PVC ANSI/ASTM 

D2564 

CPVC ANSI/ASTM 

F493 

Note: Do Not Use Cellular Foam Core Pipe 

PVC/CPV

PVC/CPVC Installation Instruction

allation Instructions

•  

Use only solid PVC or CPVC schedule 40 pipe.  Cellular foam core piping is not allowed. 

 

In Canada, plastic vent systems must be certified to ULC S636.  The components of the certified 
vent system must not be interchanged with other vent systems or unlisted pipe/fittings.   

•  

In Canada, specified primers and glues of the ULC S636 certified vent system must be from a 
single system manufacturer and not intermixed with other system manufacturer’s vent system 
parts. 

•  

Follow all general venting guidelines as outlined on this page.

•  

The pipe shall be installed so that the first 3’ (0.9m) of pipe from the appliance flue outlet is readily 
accessible for visual inspection.   

•  

When preparing and assembling the pipe, follow instructions as provided by the pipe 
manufacturer.  In general, the following practices must be observed: 

Squarely cut all pieces of pipe. 

Remove all burs and debris from joints and fittings. 

All joints must be properly cleaned, primed, and cemented.  Use only cement and primer 
approved for use with the pipe material as outlined in the above table.  

•  

•  

PVC or CPVC pipe has been approved for use on this appliance with zero clearance to combustibles.

All piping must be fully supported. Use pipe hangers at a minimum of 3’ (0.9m) intervals. Do not use
the water heater to support the vent piping.

3" or 4" schedule 80 pipe may also be used on this appliance, however the BTUH input of the 
appliance will be reduced by up to 5%.

41'  (12.6m)

35'  (10.8m)

No. of Elbows

* Not including the termination

47'  (14.4m)

3

4

2
1

53'  (16.2m)

41'  (12.6m)

35'  (10.8m)

47'  (14.4m)
53'  (16.2m)

•  

Do not exceed the following maximum vent lengths:

Venting With PVC or CPVC

Venting With PVC or CPVC

 

 

This appliance can be vented with non cellular core plastic pipe materials as specified in the below table. 
Vent installations in Canada which utilize plastic vent systems must comply with ULC S636. 

•  

A bird screen must be installed on the vent terminations to prevent debris or animals from entering the 
piping.  These screens are not supplied with the water heater and must be purchased separately 
(part #VT4-PVCS, use part #VT3-PVCS when using 3" (75mm) PVC or CPVC). 

When attaching the piping to the water heater, use the appropriate primer and cement to ensure a 
proper seal.

4" (100mm) Pipe*

3" (75mm) Pipe*

Summary of Contents for NRC83-DV

Page 1: ...d by erroneous work or work not as instructed in this manual are not covered by the warranty Check that the installation was done properly in accordance with this Installation Manual upon completion A...

Page 2: ...lation Q ty Shape Part Part Shape Q ty Remote Controller Cord 26ft 8m Quick Connect Cord QC 2 1 1 1 each Isolation Valves includes pressure relief valve Owner s Guide Warranty Installation Manual this...

Page 3: ...e The hot water temperature will become unstable as the pipe length increases Distance at center 20 3 36 3 in 515 922mm Quick Connect Cord Union Gas Valve Union Shutoff Valve Shutoff Valve Hot Water S...

Page 4: ...Caution if Using With a Solar Pre Heater Using this unit with a solar pre heater can lead to unpredictable output temperatures and possibly scalding If absolutely necessary use mixing valves to ensure...

Page 5: ...result Avoid installation in places where special chemical agents e g hair spray or spray detergent are used Ignition failures and malfunction may occur as a result Carbon Monoxide Poisoning Hazard D...

Page 6: ...nal noises while it is running Before installing make sure that the exhaust ue termination will have the proper clearances according to the National Fuel Gas Code ANSI Z223 1 State of California The w...

Page 7: ...the unit to facilitate maintenance and service if necessary If possible leave 3 75mm or more above and below the vent pipe to facilitate inspection and repair if necessary Securing of space for repai...

Page 8: ...Illustration Outdoor Clearances to Opening into Any Building 12 300mm or more 12 300mm or more There must be no building opening within this area Flue terminal 12 300mm or more 12 300mm or more Vent C...

Page 9: ...aintain clearances in accordance with local installation codes and the requirements of the gas supplier A vent shall not terminate directly above a sidewalk or paved driveway that is located between t...

Page 10: ...installing Internal parts may be damaged and may become highly dangerous Install the unit on a vertical wall and ensure that it is level Locating Screw Holes Mounting Structure When installing with ba...

Page 11: ...t accessory on the top of the appliance as illustrated below Or if the vent pipe has already been installed 2 After installing the drain pipe make sure that the area around the appliance is well venti...

Page 12: ...temperature in excess of 149 F 65 C and schedule 40 PVC pipe may be used as the vent material If required by local code schedule 40 or 80 CPVC may also be used on this appliance Refer to page 13 for a...

Page 13: ...for the location of the dip switch bank 0 3 6 9 12 15 18 21 24 27 30 32 35 38 41 44 47 50 53 56 62 0 00 0 90 1 80 2 70 3 60 4 50 5 40 6 30 7 20 8 10 9 00 9 90 10 80 11 70 12 60 13 50 14 40 15 30 16 20...

Page 14: ...practices must be observed o Squarely cut all pieces of pipe o Remove all burs and debris from joints and fittings o All joints must be properly cleaned primed and cemented Use only cement and primer...

Page 15: ...National Fuel Gas Code ANSI Z223 1 NFPA 54 Slope the horizontal vent 1 4 upwards for every 12 300mm toward the termination Use a condensation drain if necessary In the Commonwealth of Massachusetts a...

Page 16: ...s fuel equipment Please refer to Technical Bulletin TB 010606 for full installation in structions Slope vent Upwards 4 100mm pipe requires the use of a reducing coupling just prior to the termination...

Page 17: ...must be supplied from the outdoors as shown on pages 15 16 Terminate at least 6 1 8m from the combustion air intake of any appliance and 3 0 9m from any other building opening gas utility meter servi...

Page 18: ...a mechanical closet provide a 600mm 24 clearance in front of the unit to the door If combustion air will be provided through a duct size the duct to provide 60 cubic feet of fresh air per minute Supp...

Page 19: ...ee next page for the pipe capacity charts Noritz Condensing Tankless Gas Water Heater NRC98 DV 180 000 Btuh NRC83 DV 157 000 Btuh Clothes Dryer 35 000 Btuh Barbecue 50 000 Btuh Gas Range Stove 65 000...

Page 20: ...32 252 511 787 1496 55 112 213 440 675 1260 Maximum Capacity of Flex TracPipe in Cubic Feet per Hour of Natural Gas 0 60 Specific Gravity 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1...

Page 21: ...to supply potable water may not be connected to any heating system or components previ ously used with a nonpotable water heating appliance When water is required in one part of the system at a higher...

Page 22: ...eans to en sure that the supply water pressure to the inlet of the heater does not fall below 29 PSI when the maximum amount of water is being demand ed Also install a pressure meter on the inlet If t...

Page 23: ...een ON and OFF oF PRIORITY LED goes out on PRIORITY LED blinks 6 If 2D also needs to be changed repeat steps 4 and 5 7 To con rm the settings press the Setting Buttons and simultaneously for more than...

Page 24: ...Treatment Required Install Noritz Isolation Valves to allow for flushing Flushing is required if a water treatment device is not installed Suggested Suggested Install Noritz Isolation Valves to allow...

Page 25: ...Long runs or applications where the nearest drain is above the water heater will require the use of a condensate pump Size the pump to allow for a maximum condensate discharge of 2 GPH from the water...

Page 26: ...CLEARANCE DO NOT ADD ANY VALVES DO NOT ADD ANY VALVES NORITZ Condensing Tankless Gas Water Heater NORITZ Condensing Tankless Gas Water Heater Note If the drain line becomes clogged or frozen condensa...

Page 27: ...the pump Set the Aquastat to 10 F 5 C below the set output temperature 4 Noritz recommends the use of an Isolation Kit with the installation These kits include an integrated shut off and serv ice valv...

Page 28: ...the water heater will not activate resulting in possible freezing damage Do not let the power cord contact the gas piping Tie the redundant power cord out side the water heater Putting the redundant...

Page 29: ...FF button on the remote controller To keep the water heater off let the unit sit for 30 sec to return to the original display The NRC98 DV NRC83 DV can be programmed so that it will default to one of...

Page 30: ...t the end of the remote controller cord to the terminal block 5 Replace the terminal block cover and install the screw previously removed in step 3 6 Reconnect electrical power to the water heater Ext...

Page 31: ...om a wall circuit to the pump 5 Replace the front cover Pump Wiring This feature is not available when using the Quick Connect Multi System feature Relay connection with larger pumps 85 W 1 Locate and...

Page 32: ...ling Cord Clamp Ground wire Connector Connector Connecting Quick Connect Cord 2 Caution For Quick Connect Multi System Installation use part QC 2 only sold separately Quick Connect Cord 2 Quick Connec...

Page 33: ...proper blue color and consistency If the ame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a quali ed service technician Do not ob...

Page 34: ...ower to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop a...

Page 35: ...00mm 2 8 70mm 1 4 36mm 6 7 170mm 5 5 140mm 3 9 100mm 2 8 70mm 1 4 36mm 1 6 40mm 2 4 61mm 5 5 140mm 9 4 240mm 1 1 28mm 26 2 665mm 23 1 586mm 0 4 10mm 4 0 5 13mm 6 0 24 x 0 4 6mm x 10mm OBLONG HOLE 0 4...

Page 36: ...on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the con troller Avoid location...

Page 37: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Reviews: