16
10.
Relief Valve Mounting
1. Remove the front cover of the unit.
2. Remove the single screw holding the cap to the
housing.
• Do not lose this screw, it will be used in a
later step.
Fitting
Paper Backing
Gasket
Fitting
Safety Relief Valve
O-ring
Relief Valve Assembly
Boiler Case
Housing
3. Remove the cap.
4. Locate the gasket supplied with the boiler, remove
the paper backing, and attach it to the supplied fitting
around the flange.
5. Install the relief valve (supplied separately) in the fitting
before attaching it to the boiler.
7. Secure the relief valve assembly to the boiler case
with the 2 supplied screws.
6. Insert the relief valve assembly into the housing being
careful not to damage the o-ring. Insert and tighten
the screw that was previously removed in step 2.
8. Replace the front cover of the unit.
NOTE
When attaching the drain line to the end of the relief
valve, do not apply excess force to the end of the relief
valve assembly. Excessive force can damage both the
casing and the internal piping.
Screw
Boiler Case
Housing
Cap
Boiler Case
Housing
Screw
Relief Valve Assembly
Boiler Case
Screw
Screw
Press the fitting firmly into the housing while tightening
the screw. Failure to do so could cause a leak.
Before installing the relief valve, test the piping at 45 psi with the cap on.