background image

10

Illustration

7.

 Installation

Check

4. Drill holes for the remaining four screws.

5. Hang the unit again by the first screw, and then

insert and tighten the remaining four screws.

6. Take waterproofing measures so that water does

not enter the building from screws mounting the
device.

• Make sure the unit is installed securely so that it will

not fall or move due to vibrations or earthquakes.

Securing to the wall

Mounting Bracket
(upper)

Tapping Screw

Location of Screw Hole

1. Drill a single screw hole, making sure to hit a stud.

2. Insert and tighten the screw and hang the  unit by

the upper wall mounting bracket.

3. Determine the positions for the remaining four screws

(two for the top bracket and two for the bottom), and
remove the unit.

• The weight of the device will be applied to the wall. If the strength of the wall is not suffi-

cient, reinforcement must be done to prevent the transfer of vibration.

• Do not drop or apply unnecessary force to the device when installing. Internal parts may

be damaged and may become highly dangerous.

• Install the unit on a vertical wall and ensure that it is level.

Locating Screw Holes

Locating Screw Holes

Mounting

Structure

• When installing with bare hands, take caution to

not inflict injury.

• Be careful not to hit electrical wiring, gas, or water

piping while drilling holes.

Item

CAUTION

Be sure to do

• If this water heater is being installed at an elevation of

610m (2,000') or higher, disconnect the connector la-
beled "High Elevation Disconnect" as illustrated on the
right. This connector is located inside the unit.

Installations at Elevations

Above 610m (2,000').

HIGH ELEV

ATION

DISCONNECT 

• Disconnect power to the water heater before discon-

necting this connector. Failure to perform this step will
result in a "73" code displayed on the remote controller
and a cease in operation. If this occurs, disconnect,
then reconnect power to the water heater to reset the
system.

Summary of Contents for N-0842MC

Page 1: ... the warranty and to hand the warranty to the customer along with the Owner s Guide WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or death NORITZ AMERICA CORPORATION Installation Manual DANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING indi...

Page 2: ...s The accessories listed below are not included with the units but may be necessary for installation Owner s Guide Warranty Installation Manual this document Outdoor Vent Cap VC4C 1 Quick Connect Cord Q ty Shape Part Part Shape Q ty 1 1 Remote Controller Cord 8m 26 1 Isolation Valves includes pressure relief valve 1 Remote Controller Outdoor Junction Box System Controller 1 Bird Screen for 100mm 4...

Page 3: ...ength between the two units When connecting two units use only a single remote controller Note Connect the remote controller to only one of the units System Diagram Insulate the hot water piping to prevent heat loss Insulate and apply heating materials to the cold water supply piping to prevent heat loss and freezing of pipes when exposed to excessively cold temperatures Union Make this distance a...

Page 4: ...ING CAUTION Check the Gas Check that the rating plate indicates the correct type of gas Check that the gas supply line is sized for 199 900 Btuh for this unit Check the Power The power supply required is 120VAC at 60Hz May result in fire or electric shock Use Extreme Caution if Using With a Solar Pre Heater Using this unit with a solar pre heater can lead to unpredictable output temperatures and p...

Page 5: ...er materials Avoid places where fires are common such as those where gasoline benzene and adhesives are handled or places in which corrosive gases ammonia chlorine sulfur ethylene compounds acids are present Using the incorrect voltage may result in fire or cracking Avoid installation in places where dust or debris will accumulate Dust may block the air supply opening causing the performance of th...

Page 6: ...termination directed towards a window or any other structure which has glass or wired glass facing the termination Avoid installation where the unit will be exposed to excessive winds For outdoor installation only For indoor installation only Avoid installation above gas ranges or stoves Avoid installation between the kitchen fan and stove If oily fumes or a large amount of steam are present in th...

Page 7: ...stove that has the possibility of generating steam that contains fats or oils use a dividing plate or other measure to ensure that the unit is not exposed to air containing such impurities The dividing plate should be of noncombust ible material of a width greater than the water heater Exhaust hood Range Dividing plate Water heater Cooking Equipment WARNING 200mm 8 or more 300mm 12 or more Indoor ...

Page 8: ... if within 3m 10 1 8m 6 0 9m 3 above if within 3m 10 1 8m 6 L Above paved sidewalk or paved driveway located on public property Under veranda porch deck or balcony 2 1m 7 M indicates clearances required in Canada Maintain clearances in accordance with local installation codes and the requirements of the gas supplier A vent shall not terminate directly above a sidewalk or paved driveway that is loc...

Page 9: ...ny building 0 9m 3 above any forced air inlet within 3m 10 Vent Clearances When Heater is Installed Outdoors With a Vent Cap All clearance requirements are in accordance with ANSI Z21 10 3 and the National Fuel Gas Code ANSI Z223 1 and in Canada in accordance with NSCNGPIC For Installations in Canada clearances are as follows To windows doors gravity air inlets 900mm 36 To forced air inlets 1 8m 6...

Page 10: ... be done to prevent the transfer of vibration Do not drop or apply unnecessary force to the device when installing Internal parts may be damaged and may become highly dangerous Install the unit on a vertical wall and ensure that it is level Locating Screw Holes Locating Screw Holes Mounting Structure When installing with bare hands take caution to not inflict injury Be careful not to hit electrica...

Page 11: ...ure that the neutralizer unit is filled with water 1 Fill the neutralizer unit by pouring approx 17 oz 500ml of water into the exhaust accessory on the top of the appliance as illustrated below Or if the vent pipe has already been installed 2 After installing the drain pipe make sure that the area around the appliance is well ventilated open a window or a door if necessary Then operate the unit an...

Page 12: ...al vertical vent runs should be no less than 0 9m 3 Do not store hazardous or flammable sub stances near the vent termination and check that the termination is not blocked in any way Steam or condensed water may come out from the vent termination Select the location for the termination so as to prevent injury or property damage If snow is expected to accumulate take care the end of the pipe is not...

Page 13: ...e from the appliance flue outlet is readily accessible for visual inspection When preparing and assembling the pipe follow instructions as provided by the pipe manufacturer In general the following practices must be observed o Squarely cut all pieces of pipe o Remove all burs and debris from joints and fittings o All joints must be properly cleaned primed and cemented Use only cement and primer ap...

Page 14: ...n Each End of Tee Support Insert Bird Screen in End of 45 Elbow PVC CPVC Coupling PVC CPVC Coupling Slope vent Upwards Pipe Material PVC or CPVC Not supplied with water heater order separately Max Straight Vent Length 3 4 6m 15 0 9m 3 No of Elbows 100mm 4 Pipe 75mm 3 Pipe 2 8 2m 27 3m 10 1 12 0m 39 5 1m 17 Terminate at least from the combustion air intake of any appliance and 0 9m 3 from any other...

Page 15: ...in a mechanical closet provide a 600mm 24 clearance in front of the unit to the door If combustion air will be provided through a duct size the duct to provide 60 cubic feet of fresh air per minute Supply combustion air to the units as per the National Fuel Gas Code ANSI Z223 1 and in Canada in accordance with NSCNGPIC Combustion Air Openings supplying indoor air 250mm 10 250mm 10 500mm 20 500mm 2...

Page 16: ...3 1 Natural Gas Meter See next page for the pipe capacity charts Noritz Condensing Tankless Gas Water Heater 199 900 Btuh Clothes Dryer 35 000 Btuh Barbecue 50 000 Btuh Gas Range Stove 65 000 Btuh 3m 10 3m 10 1 5m 5 1 5m 5 1 5m 5 1 5m 5 3m 10 3m 10 Gas Fireplace 25 000 Btuh Instructions 1 Size each outlet branch starting from the furthest using the Btuh required and the length from the meter 2 Siz...

Page 17: ...14 75 132 194 440 1042 71 125 181 415 983 67 118 171 393 933 55 94 137 320 762 48 82 116 277 661 R Maximum Capacity of Flex TracPipe in Thousands of Btuh Liquified Petroleum 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1 2 2 325 605 971 1993 4638 232 425 661 1404 3285 191 344 528 1143 2684 166 297 449 988 2327 149 265 397 884 2082 136 241 359 805 1902 126 222 330 745 1761 118 208 30...

Page 18: ...tem or components previously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest of the system means such as a mixing valve shall be installed to temper the water to reduce the scald hazard Installation and service must be performed by a qualified plumber In the Commonwealth of Massachusetts this product must be i...

Page 19: ... wet the floor If neces sary provide drain piping or use a drain hose to remove the water Hot water piping Do not use lead PVC iron or any piping which has been treated with chromates boiler seal or other chemicals The longer the piping the greater the heat loss Try to make the piping as short as possible Use mixing valves with low water resistance Use shower heads with low pressure loss If necess...

Page 20: ...nal Sediment Filter Water Treatment Device Shutoff Valve Type of Water Hardness Level Treatment Device Flush Frequency Type of Water Hardness Level Treatment Device Flush Frequency Soft 0 1 gpg 1 3 gpg 0 17 mg L None None None None None None Slightly Hard 17 51 mg L None None Moderately Hard Hard 3 7 gpg 51 120 mg L ScaleShield Once a Year Once a Year Twice a Year Once a Year 7 10 gpg 120 171 mg L...

Page 21: ...above the water heater will require the use of a condensate pump Size the pump to allow for a maximum condensate discharge of 2 GPH from the water heater Horizontal runs must be sloped 1 4 per foot towards the drain or condensate pump The end of the drain pipe must not be submerged in water or blocked in any way Be sure to check that condensate is freely flowing from the drain piping after the sys...

Page 22: ...4 Set the flow switch to deactivate the Air Handler when the domestic hot water flow reaches 11 3 L min 3 GPM Adjust as necessary to prevent cycling 5 If the system requires water for space heating at a higher temperature than for other uses means such as a mixing valve shall be provided to temper the water for the other uses to help prevent scald ing 6 Expansion tank required if a backflow preven...

Page 23: ...he water heater Putting the redundant length of cord inside the water heater may cause electrical interference and faulty operation Ground To prevent electrical shock provide a ground with resistance less than 100 An electrician should do this work A grounding screw is provided on the back in the junction box Do not connect the ground to the city water or gas piping Do not tie the ground to a tele...

Page 24: ...nnector to 180 F tag connector as shown on the right 5 Replace the front cover of the water heater 4 screws 6 Reconnect electrical power to the water heater but do not turn it on 7 Press and hold the FLOW METER ALARM SET button until a sound is heard 2 sec and 50 C 122 F appears on the display 8 Set the upper limit of the hot water supply temperature to 55 C 130 F 60 C 65 C 70 C 75 C 140 F 149 F 1...

Page 25: ...rrode and cause problems Be sure to hand tighten when screwing to the terminal block Power tools may cause damage to the terminal block 1 Check to make sure that the remote controller cord has plenty of slack in order to reach the external connection terminal block 2 Disconnect electrical power to the water heater 3 Remove the single screw securing the terminal block cover and then remove the cove...

Page 26: ...which 120VAC will be supplied directly from a wall circuit to the pump 5 Replace the front cover Supplies Power for Circulating Pump Use a Relay for Larger Pumps Pump Wiring This feature is not available when using the Quick Con nect Multi System feature Relay connection with larger pumps 85 W 1 Locate and prepare the pump control wires as described above 2 Choose a suitable installation location ...

Page 27: ...Black 3 White 4 Green 5 Blue 6 Blue 1 White 2 Green 3 Red 4 Black 5 Blue 6 Blue Connecting the Quick Connect Cord to the two units 1 Turn off the power 2 Remove the front cover of the heater 4 screws 3 Pass the Quick Connect Cord through the wiring throughway and into the unit 4 Plug the connector on the Quick Connect Cord to the receptacle inside the unit 5 Attach the ground wire of the Quick Con...

Page 28: ...or a proper blue color and consistency If the flame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a qualified service technician Do not obstruct the flow of combustion and ventilation air The pressure relief valve must be operated once a year to ensure that it is functioning properly and there is no obstruction Turn the power off...

Page 29: ...power to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop any water demand 2 Turn off electric power 3 Turn the gas control manual valve clockwise to the off position Should overheating occur or the gas supply fail to shut off turn off the manual control val...

Page 30: ...3 3 7 70mm 2 8 98mm 3 9 99mm 3 9 214mm 8 4 255mm 10 0 264mm 10 4 348mm 13 7 60mm 2 4 109mm 4 3 155mm 6 1 71mm 2 8 120mm 4 7 135mm 5 3 155mm 6 1 36mm 1 4 70mm 2 8 100mm 3 9 140mm 5 5 170mm 6 7 36mm 1 4 70mm 2 8 100mm 3 9 140mm 5 5 170mm 6 7 6 6mm x 10mm 0 24 x 0 4 OBLONG HOLE 4 13mm 0 5 665mm 26 2 40mm 1 6 6 6mm x 10mm 0 24 x 0 4 OBLONG HOLE 4 13mm 0 5 10mm 0 4 HEIGHT OF EACH FITTING FROM BOTTOM OF...

Page 31: ...Size the water supply piping to allow for maximum flow rates of the units Hot Water 1 1 4 2 Water supply Also disconnect this connector on units 2 6 Disconnect this Connector Expansion Tank Unit 6 Unit 2 Unit 1 System Controller Size the pump to provide at least 7 6 L min 2 GPM 30kPa 10 ft of head piping losses through the system Check the maintenance monitors on the unit to make sure the pump is ...

Page 32: ... 2 pumps in parallel The system controller will stop the units from heating when the tank is up to temperature and the unit will cut the flow through it to 9 8 L min 2 6 GPM Install the plumbing so that a change in flow will not damage the pump Thermostat System select connector Connect to the Sto rage system connector Pump Control Wires use external relay Also disconnect this connector on units 2...

Page 33: ...sconnect this Connector Disconnect this Connector Disconnect for system controller Disconnect for system controller Disconnect this Connector Remote Controller Cord PCB Power PCB PCB Power PCB Disconnectforsystemcontroller Multi System Wiring Use SC 201 6M The connector location may be slightly different on the actual circuit boards than in these illustrations The remote controller terminal locati...

Page 34: ...es on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the controller Avoid locations where special chemical agents e g benzene fatty and oily deter gents are used Avoid outdoor installation or installation in an indoor location where it will be exposed to direct sunlight Connection...

Page 35: ...cord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the remote control to the wall and replace the cover Remote Controller Cord Wall Packing take off the paper Remote Control Wires Rear Side of Remote Controller ...

Page 36: ...he wall pipe containing the remote controller wires through the hole 4 Slide the junction box packing and the junction box over the remote controller wires and wall pipe protruding from the outside wall Wall packing Wall pipe Take out the pipe about 18 75mm 3 4 from the wall Junction Box Box Nut Junction Box Packing Take off the paper 5 Slide the box nut over the remote controller wires and screw ...

Page 37: ...vered by the warranty Check that the installation was done properly in accordance with this Installation Manual upon completion After completing installation please either place this Installation Manual in a plastic pouch and attach it to the side of the water heater or the inside of the pipe cover or recess box if applicable or hand it to the customer to retain for future reference Also be sure t...

Page 38: ...tional Accessories The accessories listed below are not included with the units but may be necessary for installation Owner s Guide Warranty Installation Manual this document Q ty Shape Part Part Shape Q ty 1 Remote Controller Cord 8m 26 Quick Connect Cord 1 1 Isolation Valves includes pressure relief valve System Controller 1 Bird Screen for 100mm 4 PVC VT4 PVCS Bird Screen for 75mm 3 PVC VT3 PVC...

Page 39: ...gth between the two units When connecting two units use only a single remote controller Note Connect the remote controller to only one of the units System Diagram Insulate the hot water piping to prevent heat loss Insulate and apply heating materials to the cold water supply piping to prevent heat loss and freezing of pipes when exposed to excessively cold temperatures Union Make this distance as ...

Page 40: ...can lead to unpredictable output temperatures and possibly scalding If absolutely necessary use mixing valves to ensure output temperatures do not get to scalding levels Do not use a solar pre heater with the quick connect multi system Precautions on Vent Pipe Replacement The vent system will almost certainly need to be replaced when this appliance is being installed Only use vent materials that a...

Page 41: ... as a result Avoid installation in places where special chemical agents e g hair spray or spray detergent are used Ignition failures and malfunction may occur as a result Carbon Monoxide Poisoning Hazard Do not install this water heater in a recreational vehicle or on a boat The water heater is designed for indoor installation only Never install it outdoors or in a bathroom it may be damaged or a ...

Page 42: ...st gas will not affect neighbors Before installing make sure that the exhaust flue termination will have the proper clearances according to the National Fuel Gas Code ANSI Z223 1 State of California The water heater must be braced anchored or strapped to avoid moving during an earthquake Contact local utilities for code requirements in your area or call 1 866 766 7489 and request instructions Be s...

Page 43: ...rea where an effective shield makes a clearance of 600mm 24 or more in front of the exhaust outlet Check Illustration Securing of space for repair inspection 600mm 24 or more 200mm 8 or more Outdoor Clearances to Opening into Any Building There must be no building opening within this area 300mm 12 or more Flue terminal 200mm 8 or more 300mm 12 or more 300mm 12 or more 300mm 12 or more Distance fro...

Page 44: ...meter regulator assembly I Service regulator vent outlet 0 9m 3 J Nonmechanical air supply inlet or combustion air inlet to any other appliance K Mechanical air supply inlet L Above paved sidewalk or paved driveway located on public property Under veranda porch deck or balcony M indicates clearances required in Canada Maintain clearances in accordance with local installation codes and the requirem...

Page 45: ... apply unnecessary force to the device when installing Internal parts may be damaged and may become highly dangerous Install the unit on a vertical wall and ensure that it is level Locating Screw Holes Mounting Structure When installing with bare hands take caution to not inflict injury Be careful not to hit electrical wiring gas or water piping while drilling holes Item CAUTION Be sure to do Moun...

Page 46: ... the neutralizer unit is filled with water 1 Fill the neutralizer unit by pouring approx 17 oz 500ml of water into the exhaust accessory on the top of the appliance as illustrated below Or if the vent pipe has already been installed 2 After installing the drain pipe make sure that the area around the appliance is well ventilated open a window or a door if necessary Then operate the unit and verify...

Page 47: ... vertical vent runs should be no less than 0 9m 3 Do not store hazardous or flammable sub stances near the vent termination and check that the termination is not blocked in any way Steam or condensed water may come out from the vent termination Select the location for the termination so as to prevent injury or property damage If snow is expected to accumulate take care the end of the pipe is not c...

Page 48: ... joints and fittings o All joints must be properly cleaned primed and cemented Use only cement and primer approved for use with the pipe material as outlined in the above table PVC or CPVC pipe has been approved for use on this appliance with zero clearance to combustibles All piping must be fully supported Use pipe hangers at a minimum of 0 9m 3 intervals Do not use the water heater to support th...

Page 49: ...ation drain if necessary In the Commonwealth of Massachusetts a carbon monoxide detector is required for all side wall horizontally vented gas fuel equipment Please refer to Technical Bulletin TB 010606 for full installation in structions As illustrated on the left make sure to keep a distance of 0 9m 3 or wider between the intake and exhaust when installing the vent piping Terminate at least 1 8m...

Page 50: ...0 3 9m 13 4 8m 16 9m 30 10 8m 36 12 6m 42 There must be a minimum of 25mm 1 clearance between the outside wall and the air intake section of the termination as illustrated on the left Install a securing strap to prevent movement of the termination Hanger Straps PVC CPVC Coupling Slope vent Upwards 100mm 4 pipe requires the use of a reducing coupling just prior to the termination No of Elbows 3 2 1...

Page 51: ...3 1 Natural Gas Meter See next page for the pipe capacity charts Noritz Condensing Tankless Gas Water Heater 199 900 Btuh Clothes Dryer 35 000 Btuh Barbecue 50 000 Btuh Gas Range Stove 65 000 Btuh 3m 10 3m 10 1 5m 5 1 5m 5 1 5m 5 1 5m 5 3m 10 3m 10 Gas Fireplace 25 000 Btuh Instructions 1 Size each outlet branch starting from the furthest using the Btuh required and the length from the meter 2 Siz...

Page 52: ...14 75 132 194 440 1042 71 125 181 415 983 67 118 171 393 933 55 94 137 320 762 48 82 116 277 661 R Maximum Capacity of Flex TracPipe in Thousands of Btuh Liquified Petroleum 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1 2 2 325 605 971 1993 4638 232 425 661 1404 3285 191 344 528 1143 2684 166 297 449 988 2327 149 265 397 884 2082 136 241 359 805 1902 126 222 330 745 1761 118 208 30...

Page 53: ...tem or components previously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest of the system means such as a mixing valve shall be installed to temper the water to reduce the scald hazard Installation and service must be performed by a qualified plumber In the Commonwealth of Massachusetts this product must be i...

Page 54: ... wet the floor If neces sary provide drain piping or use a drain hose to remove the water Hot water piping Do not use lead PVC iron or any piping which has been treated with chromates boiler seal or other chemicals The longer the piping the greater the heat loss Try to make the piping as short as possible Use mixing valves with low water resistance Use shower heads with low pressure loss If necess...

Page 55: ...nal Sediment Filter Water Treatment Device Shutoff Valve Type of Water Hardness Level Treatment Device Flush Frequency Type of Water Hardness Level Treatment Device Flush Frequency Soft 0 1 gpg 1 3 gpg 0 17 mg L None None None None None None Slightly Hard 17 51 mg L None None Moderately Hard Hard 3 7 gpg 51 120 mg L ScaleShield Once a Year Once a Year Twice a Year Once a Year 7 10 gpg 120 171 mg L...

Page 56: ...ove the water heater will require the use of a condensate pump Size the pump to allow for a maximum condensate discharge of 2 GPH from the water heater Horizontal runs must be sloped 1 4 per foot towards the drain or condensate pump The end of the drain pipe must not be submerged in water or blocked in any way Be sure to check that condensate is freely flowing from the drain piping after the syste...

Page 57: ...low switch to deactivate the Air Handler when the domestic hot water flow reaches 11 3 L min 3 GPM Adjust as necessary to prevent cycling 5 If the system requires water for space heating at a higher temperature than for other uses means such as a mixing valve shall be provided to temper the water for the other uses to help prevent scald ing 6 Expansion tank required if a backflow preventer is inst...

Page 58: ...he water heater Putting the redundant length of cord inside the water heater may cause electrical interference and faulty operation Disconnect Power Electrical Shock Hazard Do not turn power on until electrical wiring is finished Disconnect power before servicing Failure to do so may result in death or serious injury from electrical shock WARNING Electrostatic discharge can affect electronic compo...

Page 59: ...nector as shown on the right 5 Replace the front cover of the water heater 4 screws 6 Reconnect electrical power to the water heater but do not turn it on 7 Press and hold the FLOW METER ALARM SET button until a sound is heard 2 sec and 50 C 122 F appears on the display 8 Set the upper limit of the hot water supply temperature to 55 C 130 F 60 C 65 C 70 C 75 C 140 F 149 F 158 F 167 F or 83 C 180 F...

Page 60: ...rode and cause problems Be sure to hand tighten when screwing to the terminal block Power tools may cause damage to the terminal block 1 Check to make sure that the remote controller cord has plenty of slack in order to reach the external connection terminal block 2 Disconnect electrical power to the water heater 3 Remove the single screw securing the terminal block cover and then remove the cover...

Page 61: ...om a wall circuit to the pump 5 Replace the front cover Pump Wiring This feature is not available when using the Quick Con nect Multi System feature Relay connection with larger pumps 85 W 1 Locate and prepare the pump control wires as described above 2 Choose a suitable installation location for the relay where it will be protected from moisture 3 Connect the pump control wires from the heater to...

Page 62: ...Black 3 White 4 Green 5 Blue 6 Blue 1 White 2 Green 3 Red 4 Black 5 Blue 6 Blue Connecting the Quick Connect Cord to the two units 1 Turn off the power 2 Remove the front cover of the heater 4 screws 3 Pass the Quick Connect Cord through the wiring throughway and into the unit 4 Plug the connector on the Quick Connect Cord to the receptacle inside the unit 5 Attach the ground wire of the Quick Con...

Page 63: ...or a proper blue color and consistency If the flame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a qualified service technician Do not obstruct the flow of combustion and ventilation air The pressure relief valve must be operated once a year to ensure that it is functioning properly and there is no obstruction Turn the power off...

Page 64: ...power to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop any water demand 2 Turn off electric power 3 Turn the gas control manual valve clockwise to the off position Should overheating occur or the gas supply fail to shut off turn off the manual control val...

Page 65: ...mm 23 1 665mm 26 2 10mm 0 4 98mm 3 9 40mm 1 6 28mm 1 1 130mm 5 1 240mm 9 4 36mm 1 4 70mm 2 8 100mm 3 9 140mm 5 5 170mm 6 7 10mm 0 4 6 6mm x 10mm 0 24 x 0 4 OBLONG HOLE 4 13mm 0 5 HEIGHT OF EACH FITTING FROM BOTTOM OF CASE N 0842MC DV CONDENSATE DRAIN 24mm 0 9 HOT WATER OUTLET 44mm 1 7 COLD WATER INLET 55mm 2 2 GAS INLET 56mm 2 2 450mm 17 7 448mm 17 6 464mm 18 3 130mm 5 1 130mm 5 1 615mm 24 2 60mm ...

Page 66: ...Size the water supply piping to allow for maximum flow rates of the units Hot Water 1 1 4 2 Water supply Also disconnect this connector on units 2 6 Disconnect this Connector Expansion Tank Unit 6 Unit 2 Unit 1 System Controller Size the pump to provide at least 7 6 L min 2 GPM 30kPa 10 ft of head piping losses through the system Check the maintenance monitors on the unit to make sure the pump is ...

Page 67: ... 2 pumps in parallel The system controller will stop the units from heating when the tank is up to temperature and the unit will cut the flow through it to 9 8 L min 2 6 GPM Install the plumbing so that a change in flow will not damage the pump Thermostat System select connector Connect to the Sto rage system connector Pump Control Wires use external relay Also disconnect this connector on units 2...

Page 68: ...sconnect this Connector Disconnect this Connector Disconnect for system controller Disconnect for system controller Disconnect this Connector Remote Controller Cord PCB Power PCB PCB Power PCB Disconnectforsystemcontroller Multi System Wiring Use SC 201 6M The connector location may be slightly different on the actual circuit boards than in these illustrations The remote controller terminal locati...

Page 69: ...tes on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the controller Avoid locations where special chemical agents e g benzene fatty and oily deter gents are used Avoid outdoor installation or installation in an indoor location where it will be exposed to direct sunlight Connectio...

Page 70: ...cord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the remote control to the wall and replace the cover Remote Controller Cord Wall Packing take off the paper Remote Control Wires Rear Side of Remote Controller ...

Page 71: ...allation doit être conforme aux réglementations lo cales ou en l absence de réglementation locale au Na tional Fuel Gas Code à la norme ANSI Z223 1 NFPA 54 dernière édition et ou CSA B149 1 au Natural Gas and Propane Installation Code NSCNGPIC Noritz America se réserve le droit d arrêter ou de modifier à tout moment et sans préavis la conception et ou les spécifications de ses produits NORITZ AMER...

Page 72: ...s inclus avec l unité mais peuvent être nécessaires à l installation Guide de l utilisateur Garantie Manuel d installation ce document Bouchon d évent extérieur VC4C 1 Cordon de raccordement rapide Qté Forme Pièce Pièce Forme Qté 1 1 Cordon de télécommande 8m 26 1 Clapets d isolement comprenant une soupape de sûreté de la pression 1 Boîte de dérivation extérieure de la télécommande Régulateur du s...

Page 73: ...u raccordement de deux appareils n utilisez qu une seule télécommande Schéma du système Remarque Raccordez la télécommande à un seul des appareils Plomberie type Isolez les conduites d eau chaude pour empêcher la perte de chaleur Isolez et appliquez des matériaux chauffant à la tuyauterie de distribution d eau froide pour empêcher la perte de chaleur en cas d exposition à des températures excessiv...

Page 74: ...az correct Vérifiez que la conduite d alimentation de gaz est calibrée pour 199 900 Btuh pour cette unité Vérifiez l alimentation L alimentation requise est de 120VCA à 60Hz Pourrait provoquer un incendie ou une électrocution Prenez des précautions extrêmes en cas d utilisation avec un réchauffeur solaire L utilisation de cette unité avec un réchauffeur solaire peut entraîner des températures émis...

Page 75: ...iseur sont utilisés Des défaillances ou dysfonctionnement de l allumage pourraient en résulter Risque d empoisonnement au monoxyde de carbone N installez pas le chauffe eau dans un mobile home une caravane ou sur un bateau Interdit DANGER 5 Choix du site d installation Placez l appareil dans un endroit où une fuite de l unité ou des raccordements ne provoquera pas de dégâts à la zone adjacente à l...

Page 76: ...n ou le bouchon d évent dans une installation extérieure aura le dégagement adéquat selon le National Fuel Gas Code ANSI Z223 1 Assurez vous que l emplacement permet l installation de la conduite d évacuation comme spécifié Pour l installation extérieure utilisez le bouchon d évent extérieur S il est nécessaire de ventiler au dessus du toit dans une installation extérieure utilisez également la ba...

Page 77: ...e la vapeur contenant des graisses ou de l huile utilisez une plaque de division ou autre mesure pour assurer que l unité ne soit exposée à de l air contenant de telles impuretés La plaque de division devra être faite d un matériau incombustible d une largeur supérieure à celle du chauffe eau Fourneau Plaque de division Chauffe eau Equipement de cuisine Hotte d évacuation Au moins 600mm 24 Au moin...

Page 78: ...a porche terrasse ou balcon C D E F G H I J K L M 300mm 12 300mm 12 1 2m 4 au dessous ou sur le côté de l ouverture ou 0 3m 1 au dessus de l ouverture 900mm 36 0 9m 3 dans la limite d une hauteur de 4 5m 15 au dessus de l ensemble compteur régulateur 0 9mm 3 1 2m 4 au dessous ou sur le côté de l ouverture ou 0 3m 1 au dessus de l ouverture 900mm 36 0 9m 3 au dessus si dans la limite de 3m 10 1 8m ...

Page 79: ...entrées d air 900mm 36 Vers les entrées d air forcée 1 8m 6 Ces exigences de dégagement sont considérées exactes pour toutes les situations ci dessus Intérieur Extérieur avec bouche d évent Exigences de dégagement des bouches de l évent par rapport aux ouvertures du bâtiment 1 2m 4 dessous 1 2m 4 horizontalement à partir de ou 0 3m 1 au dessus d une porte fenêtre utilisable ou entrée d air dans un...

Page 80: ...ieure 3 Déterminez les positions des quatre vis restantes deux pour l applique supérieure et deux pour l inférieure puis déposez l unité Le poids de l appareil sera appliqué sur le mur Si la force du mur n est pas suffisante un renforcement doit être fait pour empêcher un transfert de la vibration Ne laissez pas tomber ni n usez de force inutile sur l appareil lors de l installation Les pièces int...

Page 81: ...utraliseur est rempli d eau 1 Remplissez le neutraliseur d eau en versant environ 17 oz 500 ml d eau dans l embout d échappement sur le haut de l appareil comme illustré ci dessous Ou bien si le tuyau de vidange a déjà été installé 2 Après avoir installé le tuyau de vidange assurez vous que la zone autour de l appareil est bien aérée ouvrez une fenêtre ou une porte au besoin Puis faites fonctionne...

Page 82: ... pas être inférieure à 0 9m 3 Ne stockez pas de substances dangereuses ou inflammables à proximité de la bouche de l évent et vérifiez que celle ci n est pas bloquée d une façon ou d une autre De la vapeur ou de l eau condensée peut être émise de la bouche de l évent Sélectionnez l emplacement de la bouche pour prévenir blessure corporelle ou dommage matériel Si on prévoit de l accumulation de nei...

Page 83: ...un autre fabricant Suivez toutes les directives générales de ventilation telles qu elles sont décrites en pages 12 et 14 de ce manuel d installation L utilisation d un tuyau en PVC ou CPVC avec cet appareil est approuvé si aucun dégagement vers des matières inflammables n est possible Le tuyau doit être installé de sorte que les 0 9m 3 premiers pouces du tuyau à partir de la sortie du carneau de l...

Page 84: ...contre les pannes mécaniques Lorsque l évent traverse un plancher ou un plafond et ne passe pas par une gaine coupe feu un coupe feu et support est requis Terminez le système d évent au moins 0 6m 2 au dessus mais pas plus de 1 8m 6 au dessus du niveau du toit ou selon les instructions du fabricant de tuyau d évent Terminez le système d évent au moins 0 6m 2 au dessus mais pas plus de 3m 10 au des...

Page 85: ... la circulation de l air comburant Chaque ouverture doit être de 199 pouces carrés si elles fournissent l air intérieur et 100 pouces carrés pour l air extérieur Si l unité est installée dans un placard laissez au moins 600mm 24 de dégagement devant l unité jusqu à la porte Si l air comburant est fourni via une gaine calibrez la pour fournir 60 pieds cubiques d air frais par minute Ouvertures alim...

Page 86: ...ale et en connectant un manomètre avec un tube en silicone soit en retirant la vis 1 8 NPT avec une clé six pans mâles et en connectant la jauge de pression appropriée Compteur à gaz Sélectionnez un compteur à gaz capable d alimenter l intégralité de la demande en buth de tous les appareils à gaz dans le bâtiment Raccordement de gaz N utilisez pas de conduite avec un diamètre inférieur au diamètre...

Page 87: ...pression 0 5 WC 3 4 1 1 1 4 1 1 2 2 3m 10 6m 20 9m 30 12m 40 15m 50 18m 60 21m 70 24m 80 27m 90 30m 100 45m 150 3m 10 6m 20 9m 30 12m 40 15m 50 18m 60 21m 70 24m 80 27m 90 30m 100 45m 150 60m 200 206 383 614 1261 2934 147 269 418 888 2078 121 218 334 723 1698 105 188 284 625 1472 94 168 251 559 1317 86 153 227 509 1203 80 141 209 471 1114 75 132 194 440 1042 71 125 181 415 983 67 118 171 393 933 5...

Page 88: ...njustifiée de la soupape Les conduites et pièces raccordées au chauffe eau doivent convenir à une utilisation avec de l eau potable Des produits chimiques nocifs comme ceux utilisés dans l entretien des chaudières ne doivent pas être introduits dans l eau potable Il se peut qu un chauffe eau utilisé pour distribuer de l eau potable ne pourra pas être raccordé à un système de chauffage ou des pièce...

Page 89: ...e sol Au besoin placez une tuyauterie de vidange ou utilisez un flexible de vidange pour retirer l eau Conduite d eau chaude N utilisez pas de plomb PVC acier ou de tuyaux traités au chromate scellement par plomb pour chaudière ou autres produits chimiques Plus longues sont les conduites plus grande est la perte de chaleur Formez une tuyauterie la plus courte possible Utilisez un mitigeur avec une...

Page 90: ...ype d eau Niveau de dureté Niveau de dureté Appareil de traitement Fréquence de purge Appareil de traitement Fréquence de purge Type d eau Doux 0 1 gpg 1 3 gpg 0 17 mg L Aucun Aucun Aucun Aucun Aucun Aucun Légèrement dur Légèrement dur 17 51 mg L Aucun Aucun Modérément dur Modérément dur Dur 3 7 gpg 51 120 mg L Anti tartre Anti tartre Une fois par an Deux fois par an Une fois par an Une fois par a...

Page 91: ...es Calibrez la pompe pour permettre une évacuation maximale des eaux condensées de 2 GPH du chauffe eau Les parcours d évacuation horizontale doivent être inclinés d 1 4 po vers le siphon de vidange ou la pompe de récupération des eaux condensées L extrémité du tuyau de vidange ne doit en aucun cas être immergée dans l eau ou obstruée Vérifiez rigoureusement que les eaux condensées s écoulent libr...

Page 92: ... aquastat doit être utilisé pour commander la pompe 3 Utilisez un aquastat si le chauffe eau ne commande pas la pompe Réglez l aquastat sur 5 C 10 F en dessous de la température de sortie établie 4 Noritz recommande d utiliser un kit d isolation avec l installation Ces kits comprennent un robinet de service et une soupape d arrêt intégrés avec des raccords unions et une soupape de sûreté de la pre...

Page 93: ...au moment de l installation de l appareil AVERTISSEMENT L alimentation requise par le chauffe eau est de 120VCA à 60 Hz La consommation électrique peut être supérieure ou égale à 327W lors de l utilisation d accessoires en option Utilisez un circuit approprié Ne débranchez pas l alimentation lorsque vous n utilisez pas l appareil Si l alimentation est coupée la prévention du gel dans le chauffe ea...

Page 94: ...lustré à droite 5 Remettez le couvercle avant du chauffe eau en place 4 vis 6 Rétablissez l alimentation électrique du chauffe eau mais ne l allumez pas 7 Maintenez enfoncé le bouton de réglage de l alarme du débitmètre FLOW METER ALARM SET jusqu à ce qu un bip soit émis 2 secondes et que 50 C 122 F apparaisse sur l affichage 8 Réglez la limite supérieure de la température d alimentation en eau ch...

Page 95: ...le en cuivre peut rouiller et provoquer des problèmes Veillez à serrer à la main lors du serrage sur le bornier de raccordement Des outils peuvent endommager le bornier de raccordement 1 Assurez vous que le cordon de télécommande dispose de suffisamment de jeu pour atteindre le bornier de raccordement externe 2 Coupez l alimentation électrique du chauffe eau 3 Retirez l unique vis maintenant le co...

Page 96: ...donné que le signal pour fermer un relais normalement ouvert par lequel 120VCA sera appliqué directement d un circuit mural à la pompe 5 Remettez en place le couvercle avant Etiquette du câble de commande de la pompe Fournit le courant à la pompe de circulation Utilise un relais pour les pompes plus grandes Câblage de la pompe Cette fonction n est pas disponible lorsque vous utilisez la fonction m...

Page 97: ...z un cordon de raccordement rapide vendu séparément Branchement du cordon de raccordement rapide aux deux unités 1 Mettez hors tension 2 Déposez le couvercle avant du chauffe eau 4 vis 3 Faites passer le cordon de raccordement rapide à travers l ouverture pour câbles et dans l unité 4 Insérez le connecteur du cordon de raccordement rapide dans la prise à l intérieur de l unité 5 Fixez le fil de te...

Page 98: ...rement pour une couleur bleue et une consistance adéquates Si la flamme ne semble pas normale le brûleur a peut être besoin d être nettoyé Si le brûleur a besoin d être nettoyé ce doit être effectué par un technicien de service qualifié N obstruez pas le flux d air comburant et de ventilation La soupape de sûreté de la pression doit être opérée une fois par an pour garantir qu elle fonctionne corr...

Page 99: ...devant du chauffe eau 2 Coupez complètement l alimentation électrique de l unité 3 Ne tentez pas d allumer le brûleur manuellement 4 Tournez la soupape manuelle d admission du gaz externe à l unité dans le sens horaire à la position OFF 5 Attendez 5 minutes pour vider complètement le gaz Si l odeur de gaz persiste arrêtez et suivez les instructions à la page 3 du guide de l utilisateur 6 Tournez l...

Page 100: ...9mm 3 9 214mm 8 4 255mm 10 0 264mm 10 4 348mm 13 7 60mm 2 4 109mm 4 3 155mm 6 1 71mm 2 8 120mm 4 7 135mm 5 3 155mm 6 1 36mm 1 4 70mm 2 8 100mm 3 9 140mm 5 5 170mm 6 7 36mm 1 4 70mm 2 8 100mm 3 9 140mm 5 5 170mm 6 7 665mm 26 2 40mm 1 6 10mm 0 4 4 13mm 0 5 Trou oblong 6 6 x 10mm 0 24 x 0 4 4 13mm 0 5 Trou oblong 6 6 x 10mm 0 24 x 0 4 ENTRÉE D EAU FROIDE 3 4 OUVERTURES POUR CÂBLES ENTRÉE DE GAZ 3 4 H...

Page 101: ...ez l interrupteur DIP 3 sur OFF Voir Manuel d installation SC 201 6M Tuyau de gaz Calibrez la tuyauterie d eau pour permettre les vitesses d écoulement maximales des unités Alimentation en eau 1 1 4 2 Pompe de circulation 2 Au besoin Pompe de circulation 1 Calibrez la pompe pour fournir au moins 7 6 L min 2 GPM 30kPa 10 ft de hauteur de refoulement pertes de la tuyauterie à travers le système Véri...

Page 102: ...mentation en eau chaude Télécommande Lors de l installation de deux pompes en parallèle Le régulateur du système empêchera les unités de chauffer lorsque le réservoir augmente de température et l unité y coupera le débit à 9 8 L MIN 2 6 GPM Installez la plomberie de sorte qu un changement de débit n endommage pas la pompe Thermostat Connecteur de sélection du système Raccorder au connecteur du sys...

Page 103: ...ystem controller Disconnect for system controller Cordon de télécommande PCI PCI d alimentation PCI PCI d alimentation Disconnectforsystemcontroller Bornier de raccordement de la télécommande PCI PCI d alimentation Bornier de raccordement de la télécommande Débrancher ce connecteur Débrancher ce connecteur Cordon de télécommande Bornier de raccordement de la télécommande Unité 3 6 Unité 2 Unité 1 ...

Page 104: ... détergents gras ou huileux sont utilisés Evitez de l installer à l extérieur ou encore à l intérieur dans un endroit où elle serait exposée aux rayons du soleil Ne désassemblez pas la télécommande Garniture du mur Câble de raccordement Télécommande Vis à bois à tête bombée cruciforme Raccordement du cordon de télécommande Connecteur blanc Vers la télécommande Borne en Y Vers le chauffe eau deux m...

Page 105: ...te bombée cruciforme Ancrage pour mur 3 Retirez le couvercle de la télécommande marquez l emplacement des trous de vis et percez les trous pour les ancrages pour mur 4 Insérez les ancrages pour mur vissez la télécommande au mur et remplacez le couvercle Cordon de télécommande Garniture pour mur retirer le papier Câbles de la télécommande Arrière de la télécommande ...

Page 106: ...r la garniture de la boîte de dérivation et la boîte de dérivation par dessus les câbles de la télécommande et la protubérance du tuyau du mur à partir du mur extérieur Garniture du mur Tuyau du mur Faites sortir le tuyau d environ 18 75mm 3 4 du mur Boîte de dérivation Écrou de la boîte Garniture de la boîte de dérivation Retirez le papier 5 Faites glisser l écrou de la boîte par dessus les câble...

Page 107: ...l absence de réglementation locale au National Fuel Gas Code à la norme ANSI Z223 1 NFPA 54 dernière édition et ou CSA B149 1 au Natural Gas and Propane Installation Code NSCNGPIC Selon le cas l installation doit être en conformité avec la norme américaine Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 ou la norme canadienne CAN CSA Z240 MH Maisons mobiles Série M86 Nori...

Page 108: ...tés ci dessous ne sont pas inclus avec l unité mais peuvent être nécessaires à l installation Guide de l utilisateur Garantie Manuel d installation ce document Qté Forme Pièce Pièce Forme Qté Cordon de télécommande 8m 26 Cordon de raccordement rapide 1 1 1 Clapets d isolement comprenant une soupape de sûreté de la pression Régulateur du système 1 Grillage aviaire pour tube en PVC de 100mm 4 VT4 PV...

Page 109: ...nstallation du multisystème par raccordement rapide Le multisystème à raccordement rapide permet d installer deux unités ensemble en utilisant uniquement le cordon à raccordement rapide Le cordon de raccordement rapide mesure 2m 6 de long Installez les deux unités entre 50mm 457mm 2 18 d écart chacune pour garantir que le cordon puisse relier les deux unités Si la distance entre les deux unités es...

Page 110: ...utilisation de cette unité avec un réchauffeur solaire peut entraîner des températures émises imprévisibles et de possibles brûlures En cas d absolue nécessité utilisez des mitigeurs pour s assurer que les températures émises n atteignent pas des niveaux bouillants N utilisez pas un réchauffeur solaire avec le multisystème à raccordement rapide 4 Avant l installation ATTENTION AVERTISSEMENT Précau...

Page 111: ... bains sous peine de l endommager ou de provoquer un incendie Consultez le client pour l emplacement de l installation Installez le chauffe eau dans un endroit préservant un dégagement approprié par rapport aux constructions combustibles et non combus tibles Reportez vous à la plaque signalétique sur l appareil pour les dégagements adéquats N installez pas le chauffe eau dans un endroit où des obj...

Page 112: ...ruit et le gaz d échappement n affecteront pas les voisins Avant l installation assurez vous que la bouche du carneau d évacuation aura le dégagement adéquat selon le National Fuel Gas Code ANSI Z223 1 Etat de Californie Le chauffe eau doit être calé fixé ou sanglé afin d empêcher tout mouvement pendant un séisme Prenez contact avec les autorités locales pour les exigences de code dans votre ville...

Page 113: ... applique pas dans une zone où une protection efficace maintient un dégagement d au moins 600mm 24 en face de la sortie d échappement Garantir un espace pour réparation inspection Dégagement extérieur par rapport aux ouvertures d un bâtiment Au moins 300mm 12 Au moins 300mm 12 Au moins 300mm 12 Dans cette zone il ne doit y avoir aucune ouverture de l immeuble Au moins 300mm 12 Bouche du carneau Au...

Page 114: ...st complètement ouvert sur un minimum de deux côtés sous le sol Dégagement Au dessus d une pente véranda porche terrasse ou balcon Fenêtre ou porte qui peuvent être ouvertes Fenêtre toujours fermée Dégagement vertical vers le soffite aéré situé au dessus de la bouche dans une distance horizontale de 0 6m 2 à partir du centre de la bouche Soffite non aéré Coin externe Coin interne Chaque côté de la...

Page 115: ...vis et serrez la puis accrochez l unité avec l applique de montage murale supérieure 3 Déterminez les positions des quatre vis restantes deux pour l applique supérieure et deux pour l inférieure puis déposez l unité Placer les trous de vis Illustration Vérification Placez les trous de vis Montage Structure Rubrique H IG H E L E V A T IO N D IS C O N N E C T Si vous procédez à l installation à main...

Page 116: ...ur est rempli d eau 1 Remplissez le neutraliseur d eau en versant environ 17 oz 500 ml d eau dans l embout d échappement sur le haut de l appareil comme illustré ci dessous Ou bien si le tuyau de vidange a déjà été installé 2 Après avoir installé le tuyau de vidange assurez vous que la zone autour de l appareil est bien aérée ouvrez une fenêtre ou une porte au besoin Puis faites fonctionner l appa...

Page 117: ... à 0 9m 3 Ne stockez pas de substances dangereuses ou inflammables à proximité de la bouche de l évent et vérifiez que celle ci n est pas bloquée d une façon ou d une autre De la vapeur ou de l eau condensée peut être émise de la bouche de l évent Sélectionnez l emplacement de la bouche pour prévenir blessure corporelle ou dommage matériel Si on prévoit de l accumulation de neige prenez soin que l...

Page 118: ...tie du carneau de l appareil soient facilement accessibles pour une inspection visuelle Lors de la préparation et du montage du tuyau suivez les instructions fournies par le fabricant du tuyau En général les pratiques suivantes doivent être respectées o Coupez complètement toutes les pièces du tuyau o Retirez toutes les bavures et débris des joints et raccords o Tous les joints doivent être correc...

Page 119: ...u du toit pour limiter la conden sation et protéger contre les pannes mécaniques Lorsque l évent traverse un plancher ou un plafond et ne passe pas par une gaine coupe feu un coupe feu et support est requis Terminez le système d évent au moins 0 6m 2 au dessus mais pas plus de 1 8m 6 au dessus du niveau du toit ou selon les instructions du fabricant de tuyau d évent Terminez le système d évent au ...

Page 120: ...l ou du niveau de la neige Terminez au moins 2 1m 7 au dessus d un trottoir 1 8m 6 de l entrée d air comburant d un appareil et 0 9m 3 d une ouverture d un bâtiment compteur à gaz régulateur de gaz etc Terminez au moins 0 9m 3 au dessus d une entrée d air forcée dans la limite de 3m 10 1 2m 4 en dessous 1 2m 4 horizontalement et 0 3m 1 au dessus d une porte fenêtre entrée d air dans un bâtiment d ...

Page 121: ...ale et en connectant un manomètre avec un tube en silicone soit en retirant la vis 1 8 NPT avec une clé six pans mâles et en connectant la jauge de pression appropriée Compteur à gaz Sélectionnez un compteur à gaz capable d alimenter l intégralité de la demande en buth de tous les appareils à gaz dans le bâtiment Raccordement de gaz N utilisez pas de conduite avec un diamètre inférieur au diamètre...

Page 122: ... 0 5 WC 3 4 1 1 1 4 1 1 2 2 3m 10 6m 20 9m 30 12m 40 15m 50 18m 60 21m 70 24m 80 27m 90 30m 100 45m 150 60m 200 3m 10 6m 20 9m 30 12m 40 15m 50 18m 60 21m 70 24m 80 27m 90 30m 100 45m 150 60m 200 206 383 614 1261 2934 147 269 418 888 2078 121 218 334 723 1698 105 188 284 625 1472 94 168 251 559 1317 86 153 227 509 1203 80 141 209 471 1114 75 132 194 440 1042 71 125 181 415 983 67 118 171 393 933 5...

Page 123: ...njustifiée de la soupape Les conduites et pièces raccordées au chauffe eau doivent convenir à une utilisation avec de l eau potable Des produits chimiques nocifs comme ceux utilisés dans l entretien des chaudières ne doivent pas être introduits dans l eau potable Il se peut qu un chauffe eau utilisé pour distribuer de l eau potable ne pourra pas être raccordé à un système de chauffage ou des pièce...

Page 124: ...e sol Au besoin placez une tuyauterie de vidange ou utilisez un flexible de vidange pour retirer l eau Conduite d eau chaude N utilisez pas de plomb PVC acier ou de tuyaux traités au chromate scellement par plomb pour chaudière ou autres produits chimiques Plus longues sont les conduites plus grande est la perte de chaleur Formez une tuyauterie la plus courte possible Utilisez un mitigeur avec une...

Page 125: ...u Type d eau Niveau de dureté Niveau de dureté Appareil de traitement Fréquence de purge Appareil de traitement Fréquence de purge Type d eau Doux 0 1 gpg 1 3 gpg 0 17 mg L Aucun Aucun Aucun Aucun Aucun Aucun Légèrement dur Légèrement dur 17 51 mg L Aucun Aucun Modérément dur Modérément dur Dur 3 7 gpg 51 120 mg L Anti tartre Anti tartre Une fois par an Deux fois par an Une fois par an Une fois pa...

Page 126: ...ées Calibrez la pompe pour permettre une évacuation maximale des eaux condensées de 2 GPH du chauffe eau Les parcours d évacuation horizontale doivent être inclinés d 1 4 po vers le siphon de vidange ou la pompe de récupération des eaux condensées L extrémité du tuyau de vidange ne doit en aucun cas être immergée dans l eau ou obstruée Vérifiez rigoureusement que les eaux condensées s écoulent lib...

Page 127: ...tre utilisée Si le signal de commande de la pompe n est pas utilisé un aquastat doit être utilisé pour commander la pompe 3 Utilisez un aquastat si le chauffe eau ne commande pas la pompe Réglez l aquastat sur 5 C 10 F en dessous de la température de sortie établie 4 Noritz recommande d utiliser un kit d isolation avec l installation Ces kits comprennent un robinet de service et une soupape d arrê...

Page 128: ...au moment de l installation de l appareil AVERTISSEMENT L alimentation requise par le chauffe eau est de 120VCA à 60 Hz La consommation électrique peut être supérieure ou égale à 327W lors de l utilisation d accessoires en option Utilisez un circuit approprié Ne débranchez pas l alimentation lorsque vous n utilisez pas l appareil Si l alimentation est coupée la prévention du gel dans le chauffe ea...

Page 129: ...Remettez le couvercle avant du chauffe eau en place 4 vis 6 Rétablissez l alimentation électrique du chauffe eau mais ne l allumez pas 7 Maintenez enfoncé le bouton de réglage de l alarme du débitmètre FLOW METER ALARM SET jusqu à ce qu un bip soit émis 2 secondes et que 50 C 122 F apparaisse sur l affichage 8 Réglez la limite supérieure de la température d alimentation en eau chaude sur 55 C 130 ...

Page 130: ...e en cuivre peut rouiller et provoquer des problèmes Veillez à serrer à la main lors du serrage sur le bornier de raccordement Des outils peuvent endommager le bornier de raccordement 1 Assurez vous que le cordon de télécommande dispose de suffisamment de jeu pour atteindre le bornier de raccordement externe 2 Coupez l alimentation électrique du chauffe eau 3 Retirez l unique vis maintenant le cou...

Page 131: ...donné que le signal pour fermer un relais normalement ouvert par lequel 120VCA sera appliqué directement d un circuit mural à la pompe 5 Remettez en place le couvercle avant Etiquette du câble de commande de la pompe Fournit le courant à la pompe de circulation Utilise un relais pour les pompes plus grandes Câblage de la pompe Cette fonction n est pas disponible lorsque vous utilisez la fonction m...

Page 132: ...z un cordon de raccordement rapide vendu séparément Branchement du cordon de raccordement rapide aux deux unités 1 Mettez hors tension 2 Déposez le couvercle avant du chauffe eau 4 vis 3 Faites passer le cordon de raccordement rapide à travers l ouverture pour câbles et dans l unité 4 Insérez le connecteur du cordon de raccordement rapide dans la prise à l intérieur de l unité 5 Fixez le fil de te...

Page 133: ...rement pour une couleur bleue et une consistance adéquates Si la flamme ne semble pas normale le brûleur a peut être besoin d être nettoyé Si le brûleur a besoin d être nettoyé ce doit être effectué par un technicien de service qualifié N obstruez pas le flux d air comburant et de ventilation La soupape de sûreté de la pression doit être opérée une fois par an pour garantir qu elle fonctionne corr...

Page 134: ...devant du chauffe eau 2 Coupez complètement l alimentation électrique de l unité 3 Ne tentez pas d allumer le brûleur manuellement 4 Tournez la soupape manuelle d admission du gaz externe à l unité dans le sens horaire à la position OFF 5 Attendez 5 minutes pour vider complètement le gaz Si l odeur de gaz persiste arrêtez et suivez les instructions à la page 3 du guide de l utilisateur 6 Tournez l...

Page 135: ...9 4 36mm 1 4 70mm 2 8 100mm 3 9 140mm 5 5 170mm 6 7 10mm 0 4 450mm 17 7 448mm 17 6 464mm 18 3 130mm 5 1 130mm 5 1 615mm 24 2 60mm 2 4 109mm 4 3 155mm 6 1 99mm 3 9 214mm 8 4 255mm 10 0 264mm 10 4 348mm 13 7 71mm 2 8 120mm 4 7 135mm 5 3 155mm 6 1 70mm 2 8 98mm 3 9 4 13mm 0 5 Trou oblong 6 6 x 10mm 0 24 x 0 4 4 13mm 0 5 Trou oblong 6 6 x 10mm 0 24 x 0 4 mm inch Hauteur de chaque aller de bas du coffr...

Page 136: ...ez l interrupteur DIP 3 sur OFF Voir Manuel d installation SC 201 6M Tuyau de gaz Calibrez la tuyauterie d eau pour permettre les vitesses d écoulement maximales des unités Alimentation en eau 1 1 4 2 Pompe de circulation 2 Au besoin Pompe de circulation 1 Calibrez la pompe pour fournir au moins 7 6 L min 2 GPM 30kPa 10 ft de hauteur de refoulement pertes de la tuyauterie à travers le système Véri...

Page 137: ...mentation en eau chaude Télécommande Lors de l installation de deux pompes en parallèle Le régulateur du système empêchera les unités de chauffer lorsque le réservoir augmente de température et l unité y coupera le débit à 9 8 L MIN 2 6 GPM Installez la plomberie de sorte qu un changement de débit n endommage pas la pompe Thermostat Connecteur de sélection du système Raccorder au connecteur du sys...

Page 138: ...ystem controller Disconnect for system controller Cordon de télécommande PCI PCI d alimentation PCI PCI d alimentation Disconnectforsystemcontroller Bornier de raccordement de la télécommande PCI PCI d alimentation Bornier de raccordement de la télécommande Débrancher ce connecteur Débrancher ce connecteur Cordon de télécommande Bornier de raccordement de la télécommande Unité 3 6 Unité 2 Unité 1 ...

Page 139: ...ène détergents gras ou huileux sont utilisés Evitez de l installer à l extérieur ou encore à l intérieur dans un endroit où elle serait exposée aux rayons du soleil Ne désassemblez pas la télécommande Garniture du mur Câble de raccordement Télécommande Vis à bois à tête bombée cruciforme Raccordement du cordon de télécommande Connecteur blanc Vers la télécommande Borne en Y Vers le chauffe eau deu...

Page 140: ...te bombée cruciforme Ancrage pour mur 3 Retirez le couvercle de la télécommande marquez l emplacement des trous de vis et percez les trous pour les ancrages pour mur 4 Insérez les ancrages pour mur vissez la télécommande au mur et remplacez le couvercle Cordon de télécommande Garniture pour mur retirer le papier Câbles de la télécommande Arrière de la télécommande ...

Reviews: