6. Electrical Connection
Nominally, the VP60 is supplied with 24 V DC between Vs and GND. The electronics are protected against incorrect polarity of
the supply and will not be damaged.
The power supply must be isolated from the mains.
(PELV according to EN 60204-1, DIN VDE 0100-410, IEC 364-4-41,HD 384.4.41 S2, EN 60079-14).
6.1 Pin Assignment
6.1.1 Variant Analogue
6.1.2 Variant IO-Link
6.2 Power Supply
Note:
The device must be connected by a qualified person. The national and international regulations for the installation of electrical
devices must be observed.
The valve body must always be integrated into the equipotential bonding of the plant (grounding).
Pin
Colour (Typ.)
Ref.
Port size
1
white
Iin
Setpoint input current 4..20 mA (load resistance 500R)
2
brown
fault
Error output (max.15mA to GND Vs)
3
green
-Ud
Setpoint input voltage difference negative (0..10V /-5-5V)
4
yellow
+Ud
Setpoint input voltage difference positive (0..10V /-5-5V)
5
grey
I out
Current output actual value 4..20mA (Vs GND potential)
6
pink
Ub
Supply voltage Vs +24V DC
7
blue
GND
Supply mass (Vs GND)
8
red
U out
Voltage output actual value 0..10V (Vs GND potential)
Pin
Colour (Typ.)
Ref.
Port size
4
yellow
+Ud
Setpoint input voltage difference positive (0..10V /-5-5V)
5
grey
I out
Current output actual value 4..20mA (Vs GND potential)
6
pink
Ub
Supply voltage Vs +24V DC
7
blue
GND
Versorgungsmasse (Vs GND)
8
red
U out
Voltage output actual value 0..10V (Vs GND potential)
Potentials VA & VB are galvanically isolated.