Nordyne T3BN User'S Information And Installation Instructions Manual Download Page 6

6

Electrical Power Wiring —

 Electrical power 

wiring must comply with the current provisions 
of the “National Electrical Code” (ANSI/NFPA 
70) and with applicable local codes having 
jurisdiction. Use of rain tight conduit is 
recommended. Electrical conductors shall have 
minimum circuit ampacity in compliance with the 
outdoor unit rating label. The facility shall employ 
electrical circuit protection at a current rating no 
greater than that indicated on the outdoor unit 
rating label. Refer to the unit wiring diagram for 
connection details.

Minimum Circuit Ampacity —

 Electrical wiring 

to the equipment must be compatible and in 
compliance with the minimum circuit ampacity 
listed on the outdoor unit data label.

Maximum Fuse/Circuit Breaker Size —

 Circuit 

protection for the outdoor unit must be compatible 
with the maximum fuse/circuit breaker size listed 
on the outdoor unit data label. 

Disconnect Switch —

 An electrically compatible 

disconnect switch must be within line of sight of 
the outdoor unit. This switch shall be capable of 
electrically de-energizing the outdoor unit.

Optional Equipment —

 Optional equipment 

requiring connection to the power or control 
circuits must be wired in strict accordance with 
current provisions of the “National Electrical 
Code” (ANSI/NFPA 70), with applicable local 
codes having jurisdiction, and the installation 
instructions provided with the equipment. 

Wire Size based on N.E.C. for 60° type copper 
conductors.

COPPER WIRE SIZE — AWG

(1% Voltage Drop)

Supply Wire Length-Feet

Supply Circuit

200

150

100

50

Ampacity

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

Optional Equipment (e.g.: liquid line solenoid 
valves, refrigerant compressor crankcase heater, 
etc.) should be installed in strict accordance with 
the manufacturer’s installation instructions. 

STARTUP AND CHECKOUT

 WARNING:

Ensure electrical power to the unit is 
off prior to performing the following 
steps. Failure to do so may cause 
personal injury or death.

Air Filters —

 Ensure air fi lters are clean and in 

place prior to operating the equipment. 

Thermostat —

 Set the room thermostat function 

switch to OFF, fan switch to AUTO, and adjust the 
temperature setpoint to its highest setting.

Prior to applying electrical power to the outdoor 
unit, ensure that the unit has been properly and 
securely grounded, and that power supply 
connections have been made at both the facility 
power interface and outdoor unit.

Outdoor Unit —

 Ensure the outdoor coil and 

top of the unit are free from obstructions and 
debris, and all equipment access/control panels 
are in place.

Using extreme caution, apply power to the unit 
and inspect the wiring for evidence of open, 
shorted, and/or improperly wired circuits.

Functional Checkout:

 CAUTION:

If equipped with a compressor 
crankcase heater, wait 24 hours prior 
to performing a function checkout to 
allow for heating of the compressor 
crankcase. Failure to comply may 
result in damage and could cause 
premature failure of the system.

Summary of Contents for T3BN

Page 1: ...ation of heating and or air conditioning appliances Some local codes require licensed installation service personnel for this type of equipment Read all instructions carefully before starting the inst...

Page 2: ...e heat in place of the heat pump will result in an increase in electric utility costs Defrost During cold weather heating operation the outdoor unit may develop a coating of snow and ice on the heat t...

Page 3: ...defrost cycle the outdoor fanwillstop andthecompressorwillcontinue to run and heat the outdoor coil causing the snow and ice to melt After the snow and ice have melted some steam may rise from the out...

Page 4: ...his equipment follow all precautions in the literature on tags and on labels provided with theequipment Readandthoroughlyunderstand theinstructionsprovidedwiththeequipmentprior to performing the insta...

Page 5: ...bMount Thesiteselectedforaslabmount installation requires a stable foundation and one not subject to erosion The slab should be level and anchored if necessary prior to placing the equipment on the sl...

Page 6: ...ze based on N E C for 60 type copper conductors COPPER WIRE SIZE AWG 1 Voltage Drop Supply Wire Length Feet Supply Circuit 200 150 100 50 Ampacity 6 8 10 14 15 4 6 8 12 20 4 6 8 10 25 4 4 6 10 30 3 4...

Page 7: ...hermostat R Air Handler Heat Pump OD Section Typical Heat Pump with Standard Air Handler O NOTE Jumper betweenW2 and E is required when no OD T Stat is used C W2 to be connected to Electric Heat Y W2...

Page 8: ...inimumoffiveminutes increase the setpoint temperature of the thermostat to the maximumsetting Verifythattheoutdoorunitand indoor blower have energized Feel the air being circulated by the indoor blowe...

Page 9: ...delay Reciprocating compressors should only use this setting in conjunction with an approved hard start kit Scroll compressors thathavenoiseissueswhilegoingintoorcoming out of defrost should use this...

Page 10: ...7 5 Ton HP TXV Charging Chart 150 175 200 225 250 275 300 325 350 375 400 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below curve Remo...

Page 11: ...10 Ton HP TXV Charging Chart 150 175 200 225 250 275 300 325 350 375 400 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below curve Remov...

Page 12: ...Temp Press Press Temp Press Press Temp Press Press Temp Press Press Temp 19 134 135 20 140 135 21 146 136 22 152 136 32 162 157 51 199 198 61 248 179 20 141 133 21 146 133 22 151 134 23 156 134 33 169...

Page 13: ...ons for control circuit and optional Relay Transformer Kits 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de...

Page 14: ...8 2 18 Tube Dia 3 8 OD 3 8 OD 3 8 OD 3 8 OD Fan Motor Volts Phase Hz 280 230 3 60 460 3 60 280 230 3 60 460 3 60 380 420 3 50 380 420 3 50 Qty 1 1 1 1 Horsepower 3 4 3 4 3 4 3 4 Full Load Amps 3 3 1 7...

Page 15: ...15...

Page 16: ...AVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER 708538G 708538A 708538A replaces 7085380 Specifications and illustrations subject to change without notice and without incurring obligations Prin...

Reviews: