Nordyne T3BN User'S Information And Installation Instructions Manual Download Page 4

4

Read Your Warranty

Please read the separate warranty document 
completely. It contains valuable information 
about your system.

GENERAL INFORMATION

Read the following instructions completely before 
performing the installation.

Outdoor Unit Section —

 Each outdoor unit is 

shipped with a refrigerant holding charge.

NOTE:

 DO NOT USE ANY PORTION OF 

THE CHARGE FOR PURGING OR LEAK 
TESTING.

Matching indoor coils and air handlers may be 
shipped with a small holding charge to pressurize 
them to keep out contaminants. To release the 
pressure, read the indoor section installation 
instructions carefully.

Liquid and Suction Lines —

 Fully annealed, 

refrigerant grade copper tubing should be used 
when installing the system. Refrigerant suction 
line tubing should be fully insulated. 

Field Connections for Electrical Power 
Supply —

 All wiring must comply with current 

provisions of the “National Electrical Code” 
(ANSI/NFPA 70) and with applicable local 
codes having jurisdiction. The minimum size of 
electrical conductors and circuit protection must 
be in compliance with information listed on the 
outdoor unit data label.

SAFETY CONSIDERATIONS

Pressures within the System —

 Split 

system heat pump equipment contains liquid 
and gaseous refrigerant under pressure. 
Installation and servicing of this equipment 
should be accomplished by qualifi ed, trained 
personnel thoroughly familiar with this type of 
equipment. Under no circumstances should the 
Homeowner attempt to install and/or service 
the equipment.

Labels, Tags, Precautions —

 When working 

with this equipment, follow all precautions in the 
literature, on tags, and on labels provided with 
the equipment. Read and thoroughly understand 

the instructions provided with the equipment prior 
to performing the installation and operational 
checkout of the equipment.

Brazing Operations —

 Installation of equipment 

may require brazing operations. Safety codes 
must be complied with. Safety equipment (e.g.; 
safety glasses, work gloves, fi re extinguisher, 
etc.) must be used when performing brazing 
operations.

 WARNING:

Ensure all electrical power to the unit 
is off prior to installing or servicing the 
equipment. Failure to do so may cause 
personal injury or death. 

SITE PREPARATION

Unpacking Equipment —

 Remove the 

cardboard carton and User’s Manual from the 
equipment. Take care to not damage tubing 
connections when removing from the carton.

Inspect for Damage —

 Inspect the equipment 

for damage prior to installing the equipment at 
the job site. Ensure coil fi ns are straight and, if 
necessary, comb fi ns to remove fl attened and 
bent fi ns.

Preferred Location of the Outdoor Unit at the 
Job Site —

 Conduct a survey of the job site to 

determine the optimum location for mounting 
the outdoor unit. Overhead obstructions, 
poorly ventilated areas, and areas subject to 
accumulation of debris should be avoided. The 
outdoor unit should be installed no closer than 
18 inches from the outside walls of the facility 
and in an area free from overhead obstructions 
to ensure unrestricted airflow through the 
outdoor unit. 

Facility Prerequisites —

 Electrical power 

supplied must be adequate for proper operation 
of the equipment. The system must be wired and 
provided with circuit protection in accordance 
with local building codes and the National 
Electrical Code.

Summary of Contents for T3BN

Page 1: ...ation of heating and or air conditioning appliances Some local codes require licensed installation service personnel for this type of equipment Read all instructions carefully before starting the inst...

Page 2: ...e heat in place of the heat pump will result in an increase in electric utility costs Defrost During cold weather heating operation the outdoor unit may develop a coating of snow and ice on the heat t...

Page 3: ...defrost cycle the outdoor fanwillstop andthecompressorwillcontinue to run and heat the outdoor coil causing the snow and ice to melt After the snow and ice have melted some steam may rise from the out...

Page 4: ...his equipment follow all precautions in the literature on tags and on labels provided with theequipment Readandthoroughlyunderstand theinstructionsprovidedwiththeequipmentprior to performing the insta...

Page 5: ...bMount Thesiteselectedforaslabmount installation requires a stable foundation and one not subject to erosion The slab should be level and anchored if necessary prior to placing the equipment on the sl...

Page 6: ...ze based on N E C for 60 type copper conductors COPPER WIRE SIZE AWG 1 Voltage Drop Supply Wire Length Feet Supply Circuit 200 150 100 50 Ampacity 6 8 10 14 15 4 6 8 12 20 4 6 8 10 25 4 4 6 10 30 3 4...

Page 7: ...hermostat R Air Handler Heat Pump OD Section Typical Heat Pump with Standard Air Handler O NOTE Jumper betweenW2 and E is required when no OD T Stat is used C W2 to be connected to Electric Heat Y W2...

Page 8: ...inimumoffiveminutes increase the setpoint temperature of the thermostat to the maximumsetting Verifythattheoutdoorunitand indoor blower have energized Feel the air being circulated by the indoor blowe...

Page 9: ...delay Reciprocating compressors should only use this setting in conjunction with an approved hard start kit Scroll compressors thathavenoiseissueswhilegoingintoorcoming out of defrost should use this...

Page 10: ...7 5 Ton HP TXV Charging Chart 150 175 200 225 250 275 300 325 350 375 400 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below curve Remo...

Page 11: ...10 Ton HP TXV Charging Chart 150 175 200 225 250 275 300 325 350 375 400 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below curve Remov...

Page 12: ...Temp Press Press Temp Press Press Temp Press Press Temp Press Press Temp 19 134 135 20 140 135 21 146 136 22 152 136 32 162 157 51 199 198 61 248 179 20 141 133 21 146 133 22 151 134 23 156 134 33 169...

Page 13: ...ons for control circuit and optional Relay Transformer Kits 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de...

Page 14: ...8 2 18 Tube Dia 3 8 OD 3 8 OD 3 8 OD 3 8 OD Fan Motor Volts Phase Hz 280 230 3 60 460 3 60 280 230 3 60 460 3 60 380 420 3 50 380 420 3 50 Qty 1 1 1 1 Horsepower 3 4 3 4 3 4 3 4 Full Load Amps 3 3 1 7...

Page 15: ...15...

Page 16: ...AVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER 708538G 708538A 708538A replaces 7085380 Specifications and illustrations subject to change without notice and without incurring obligations Prin...

Reviews: