background image

4

Before You Install this Unit

  The cooling load of the area to be conditioned 

must be calculated and a system of the proper 
capacity selected. It is recommended that the 
area to be conditioned be completely insulated 
and vapor sealed.

 Check the electrical supply and verify the 

power supply is adequate for unit operation. 
If there is any question concerning the power 
supply, contact the local power company.

  All units are securely packed at the time of 

shipment and upon arrival should be carefully 
inspected for damage prior to installing the 
equipment at the job site. Verify coil fi ns are 
straight. If necessary, comb fi ns to remove 
fl attened or bent fi ns. Claims for damage 
should be fi led immediately with the carrier.

  Please consult your dealer for maintenance 

information and availability of maintenance 
contracts. Please read all instructions before 
installing the unit.

Locating the Heat Pump

•  Survey the job site to determine the best 

location for mounting the outdoor unit. Select 
a solid, level position, preferably on a concrete 
slab, slightly above the grade level, and parallel 
to the home. If possible, select a site for the unit 
that is as close as possible to the proposed 
return grille location. 

DO NOT PLACE UNIT 

UNDER THE  HOME.

•  The unit should be located with consideration of 

minimizing the length of the supply and return 
ducts. If practical, place the heat pump and 
its ducts in an area where they will be shaded 
from the afternoon sun, when the heat load is 
greatest.

•  The length of the supply and return ducts 

should be kept to a minimum with no sharp 
radius bends.

•  Overhead obstructions, poorly ventilated 

areas, and areas subject to accumulation of 
debris should be avoided. The hot condenser 
air must be discharged up and away from the 
home, and if possible, in a direction with the 
prevailing wind. Do not place the unit in a 
confi ned space. See Figure 9 & Table 4 (page 
13) for unit dimensions.

•  Suffi cient clearance for unobstructed airfl ow 

through the outdoor coil must be maintained 
in order to achieve rated performance. See 
Figure 2 (page 5) for minimum clearances to 
obstructions.

•  Consideration should also be given to 

availability of electric power, service access, 
noise, and shade.

INSTALLER INFORMATION

IMPORTANT SAFETY INFORMATION

 WARNING:

The information listed below 
must be followed during the 
installation, service, and operation 
of this unit. Unqualifi ed individuals 
should not attempt to interpret 
these instructions or install this 
equipment. Failure to follow safety 
recommendations could result in 
possible damage to the equipment, 
serious personal injury or de

ath.

•  The installer must comply with all local 

codes and regulations which govern the 
installation of this type of equipment. Local 
codes and regulations take precedence over 
any recommendations contained in these 
instructions. Consult local building codes 
and the National Electrical Code (ANSI CI) 
for special installation requirements.

•  This equipment contains liquid and gaseous 

refrigerant under high pressure. Installation or 
servicing should only be performed by qualifi ed 
trained personnel thoroughly familiar with this 
type equipment.

•  All electrical wiring must be completed in 

accordance with local, state and national 
codes and regulations and with the National 
Electric Code (ANSI/NFPA 70) or in Canada 
the Canadian Electric Code Part 1 CSA C22.1.

•  Follow all precautions in the literature, on tags, 

and on labels provided with the equipment. 
Read and thoroughly understand the 
instructions provided with the equipment prior 
to performing the installation and operational 
checkout of the equipment.

GENERAL INFORMATION

Single packaged heat pumps are ready for easy 
and immediate installation and can be readily 
connected into the high static duct system of a 
home. This unit is completely assembled, wired, 
and run tested at the factory.

 This heat pump 

is designed for outdoor installation only. 

The 

only connections needed for installation are the 
supply and return ducts, the line voltage, and 
thermostat wiring. Use of components other than 
those specifi ed may invalidate ARI Certifi cation, 
Code Agency Listing, and limited warranty on 
the air conditioner.

Summary of Contents for Q5RD Series

Page 1: ...check the instructions and follow recommendations given If these suggestions don t eliminate your problem call your servicing contractor These instructions are primarily intended to assist qualified i...

Page 2: ...Low Pressure Switch 13 High Pressure Switch 13 Unit Maintenance 13 Figures Tables 13 Figure 9 Unit Dimensions 13 Table 4 Q5RD Physical Data 13 Charging Tables Cooling Mode 14 Table 5 Q5RD X24K 2 Ton U...

Page 3: ...f the heat pump will result in an increase in electric utility costs Defrost During cold weather heating operation the outdoor unit will develop a coating of snow and ice on the heat transfer coil Thi...

Page 4: ...tdoor coil must be maintained in order to achieve rated performance See Figure 2 page 5 for minimum clearances to obstructions Consideration should also be given to availability of electric power serv...

Page 5: ...ngto NationalFireProtectionAssociation Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of Ame...

Page 6: ...tion from under the home by cuttingasmallholeinthesub floor Determine how the floor joist location will affect cutting the opening needed for the return air box NOTE Floor joists are generally located...

Page 7: ...t a hole approximately 3 4 larger than the damper opening in the fiberboard 3 Cut a 9 1 8 x 13 1 8 hole in the duct and bend over all tabs flat on the inside of the heat duct 4 Insert the damper into...

Page 8: ...e energizing the outdoor unit See unit data label for proper incoming field wiring Any other wiring methods must be acceptable to authority having jurisdiction Providepowersupplyfortheunitinaccordance...

Page 9: ...1650 T5 High 1950 Denotes Factory Set Low Speed Cooling Heating Denotes Factory Set High Speed Cooling Heating Denotes Factory Set Electric Heating Speed Overcurrent Protection Overcurrent protection...

Page 10: ...a proper location Start Up Procedure The control circuit consists of an anti short cycle timer that will not let the compressor re start before 5 minutes have elapsed 1 Set the system mode to OFF and...

Page 11: ...above the Terminate Temperature setting Short the TEST pins for 1 second or more to force the control out of defrost and back to heating mode reversing valve de energized Compressor will start immedia...

Page 12: ...s necessary using a mild detergent and water Rinse thoroughly with water Inspecttheelectricalconnectionsfortightness at the beginning of each heating and cooling season Service as necessary CAUTION Th...

Page 13: ...Control Access Panel Blower Access Panel H 17 86 15 36 10 10 3 4 NPT Drain Connection 1 12 13 1 38 3 2 3 2 5 29 FIGURES TABLES Q5RD Length L Width W Height H A B 024K 49 35 22 2 40 15 7 61 030K 49 35...

Page 14: ...mp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 139 258 115 141 260 121 281 121 143 262 126 283 126 304 126 145 266 129 285 131 306...

Page 15: ...mp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 134 269 129 136 271 135 293 134 138 274 140 295 139 316 138 140 279 139 297 144 318...

Page 16: ...s Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 124 126 274 101 128 276 112 295 111 130 277 124 298 121 318 119 132 279 129 300...

Page 17: ...ated design values The suction pressure will vary from design value if outdoor air fl ow entering dry bulb or entering wet bulb temperatures vary 1 All pressures are listed psig and all temperatures i...

Page 18: ...ated design values The suction pressure will vary from design value if outdoor air fl ow entering dry bulb or entering wet bulb temperatures vary 1 All pressures are listed psig and all temperatures i...

Page 19: ...137 73 305 142 87 334 154 103 365 173 119 396 192 35 231 126 48 257 131 61 283 135 74 309 140 88 341 151 104 372 168 120 403 186 36 238 124 49 263 129 62 288 133 75 313 138 89 348 148 105 379 164 121...

Page 20: ...D HIGH PRESSURE SWITCH LOW PRESSURE SWITCH SELECT MODELS ONLY BLUE BLUE RED RED RED RED RED ORANGE YELLOW WHITE WHITE WHITE WHITE GREY BROWN BLACK BLACK GREEN BROWN ORANGE BLUE BLACK BROWN BROWN RED R...

Page 21: ...CK BLUE BLACK GREY BLACK ORANGE WHITE RED GREEN YELLOW RED BLUE ORANGE YELLOW GREY BROWN RED BROWN Z H 0 6 T L O V 0 3 2 8 0 2 4 For replacement wires use conductors suitable for 105 C 5 On models w n...

Page 22: ...Accessory Heat Plug Outdoor Thermostat Factory Option Typical Wiring Field Supplied for 1 Stage Cool 1 Stage Electric Heat INDOOR T STAT SUB BASE Green DEFROST BOARD 1 2 3 4 5 6 7 8 9 Brown Orange Ac...

Page 23: ...23...

Page 24: ...ndusingcommonsenseplays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failuretofollowsafe...

Reviews: