background image

10

Electric Heat Package (optional)

This heat pump is shipped without an auxiliary 
electric heat kit installed. If electric heat is desired, 
an accessory Heater Kit must be fi eld installed. 
Refer to Table 2 (page 9) for blower speeds.
•  Select the correct size heat package for 

the installation. See specifi cations sheet 
for available kits and application. Install the 
heater kit according to the to the installation 
instructions provided with the kit.

•  Installation is most easily accomplished before 

making duct or electrical connections.

Grounding

 WARNING:

The unit cabinet must have 
an uninterrupted or unbroken 
electrical ground to minimize 
personal injury if an electrical 
fault should occur. Do not use gas 
piping as an electrical ground!

This unit must be electrically grounded in 
accordance with local codes or, in the absence 
of local codes, with the National Electrical Code 
(ANSI/NFPA 70) or the CSA C22.1 Electrical 
Code. Use the grounding lug provided in the 
control box for grounding the unit.

STARTUP & ADJUSTMENTS

Pre-Start Checklist

The following check list should be observed prior 
to starting the unit.

  Is the unit level? Unit should be level or slightly 

slanted toward the drain for proper condensate 
drainage.

  Is the unit installed with the proper clearances 

as listed in Figure 2 (page 5)?

  Is the wiring correct according to the wiring 

diagram and electrical codes?

  Are all the wiring connections tight? Check 

the condenser fan to make sure it turns freely. 

  Is the overcurrent protection properly sized?

  Is the thermostat wired correctly? Is it installed 

in a proper location?

Start-Up Procedure

The control circuit consists of an anti-short cycle 
timer that will not let the compressor re-start 
before 5 minutes have elapsed.
1. Set the system mode to OFF and the 

temperature mode to its highest setting.

2.  Turn power on at the disconnect switch.
3.  Set the system mode to ON or COOL.
4. Set the temperature mode below room 

temperature. Verify that the indoor blower, 
outdoor fan, and compressor energize and 
the cooling function starts.

5. Verify the discharge air grilles are adjusted 

and the system air is balanced.

6.  Verify the duct work has no air leaks.
7. Verify the condensate drain is installed 

correctly and functions properly.

8. Set the temperature mode above room 

temperature. The unit should stop.

9.  Instruct the homeowner on unit and thermostat 

operation and fi lter servicing.

Air Circulation
Leave the thermostat system mode on OFF, 
and set the fan mode to ON. Blower should 
run continuously. Check the air delivery at the 
supply registers and adjust register openings 
for balanced air distribution. Examine ducts for 
leaks or obstruction if insuffi cient air is detected.

Set the thermostat fan mode to AUTO. The blower 
should stop running.

System Heating
Set the thermostat system mode to HEAT and 
the fan mode to AUTO. Change the thermostat 
temperature selector above the existing room 
temperature and check for the discharge of warm 
air at the supply registers.

System Cooling
Set the thermostat’s system mode to COOL and 
the fan mode to AUTO. Change the thermostat 

Defrost Cycle Control

The Demand Defrost controls the defrost cycle in 
response to an adaptive demand algorithm that 
uses coil temperature and ambient temperature. 
It provides user selectable defrost termination 
temperatures (50° F - 80° F coil temperature).

Summary of Contents for Q5RD Series

Page 1: ...check the instructions and follow recommendations given If these suggestions don t eliminate your problem call your servicing contractor These instructions are primarily intended to assist qualified i...

Page 2: ...Low Pressure Switch 13 High Pressure Switch 13 Unit Maintenance 13 Figures Tables 13 Figure 9 Unit Dimensions 13 Table 4 Q5RD Physical Data 13 Charging Tables Cooling Mode 14 Table 5 Q5RD X24K 2 Ton U...

Page 3: ...f the heat pump will result in an increase in electric utility costs Defrost During cold weather heating operation the outdoor unit will develop a coating of snow and ice on the heat transfer coil Thi...

Page 4: ...tdoor coil must be maintained in order to achieve rated performance See Figure 2 page 5 for minimum clearances to obstructions Consideration should also be given to availability of electric power serv...

Page 5: ...ngto NationalFireProtectionAssociation Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of Ame...

Page 6: ...tion from under the home by cuttingasmallholeinthesub floor Determine how the floor joist location will affect cutting the opening needed for the return air box NOTE Floor joists are generally located...

Page 7: ...t a hole approximately 3 4 larger than the damper opening in the fiberboard 3 Cut a 9 1 8 x 13 1 8 hole in the duct and bend over all tabs flat on the inside of the heat duct 4 Insert the damper into...

Page 8: ...e energizing the outdoor unit See unit data label for proper incoming field wiring Any other wiring methods must be acceptable to authority having jurisdiction Providepowersupplyfortheunitinaccordance...

Page 9: ...1650 T5 High 1950 Denotes Factory Set Low Speed Cooling Heating Denotes Factory Set High Speed Cooling Heating Denotes Factory Set Electric Heating Speed Overcurrent Protection Overcurrent protection...

Page 10: ...a proper location Start Up Procedure The control circuit consists of an anti short cycle timer that will not let the compressor re start before 5 minutes have elapsed 1 Set the system mode to OFF and...

Page 11: ...above the Terminate Temperature setting Short the TEST pins for 1 second or more to force the control out of defrost and back to heating mode reversing valve de energized Compressor will start immedia...

Page 12: ...s necessary using a mild detergent and water Rinse thoroughly with water Inspecttheelectricalconnectionsfortightness at the beginning of each heating and cooling season Service as necessary CAUTION Th...

Page 13: ...Control Access Panel Blower Access Panel H 17 86 15 36 10 10 3 4 NPT Drain Connection 1 12 13 1 38 3 2 3 2 5 29 FIGURES TABLES Q5RD Length L Width W Height H A B 024K 49 35 22 2 40 15 7 61 030K 49 35...

Page 14: ...mp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 139 258 115 141 260 121 281 121 143 262 126 283 126 304 126 145 266 129 285 131 306...

Page 15: ...mp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 134 269 129 136 271 135 293 134 138 274 140 295 139 316 138 140 279 139 297 144 318...

Page 16: ...s Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 124 126 274 101 128 276 112 295 111 130 277 124 298 121 318 119 132 279 129 300...

Page 17: ...ated design values The suction pressure will vary from design value if outdoor air fl ow entering dry bulb or entering wet bulb temperatures vary 1 All pressures are listed psig and all temperatures i...

Page 18: ...ated design values The suction pressure will vary from design value if outdoor air fl ow entering dry bulb or entering wet bulb temperatures vary 1 All pressures are listed psig and all temperatures i...

Page 19: ...137 73 305 142 87 334 154 103 365 173 119 396 192 35 231 126 48 257 131 61 283 135 74 309 140 88 341 151 104 372 168 120 403 186 36 238 124 49 263 129 62 288 133 75 313 138 89 348 148 105 379 164 121...

Page 20: ...D HIGH PRESSURE SWITCH LOW PRESSURE SWITCH SELECT MODELS ONLY BLUE BLUE RED RED RED RED RED ORANGE YELLOW WHITE WHITE WHITE WHITE GREY BROWN BLACK BLACK GREEN BROWN ORANGE BLUE BLACK BROWN BROWN RED R...

Page 21: ...CK BLUE BLACK GREY BLACK ORANGE WHITE RED GREEN YELLOW RED BLUE ORANGE YELLOW GREY BROWN RED BROWN Z H 0 6 T L O V 0 3 2 8 0 2 4 For replacement wires use conductors suitable for 105 C 5 On models w n...

Page 22: ...Accessory Heat Plug Outdoor Thermostat Factory Option Typical Wiring Field Supplied for 1 Stage Cool 1 Stage Electric Heat INDOOR T STAT SUB BASE Green DEFROST BOARD 1 2 3 4 5 6 7 8 9 Brown Orange Ac...

Page 23: ...23...

Page 24: ...ndusingcommonsenseplays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failuretofollowsafe...

Reviews: