background image

3

Figure 1. Digital Thermostat

Fan

Mode

Temperature

Selector

System

Mode

ABOUT THE HEAT PUMP

Your heat pump is a unique, all weather comfort-
control appliance that will heat and cool your 
home year round and provide energy saving 
comfort. It’s an unknown fact that heat is always 
in the air, even when the outside temperature is 
below freezing. The heat pump uses this basic 
law of physics to provide energy saving heat 
during the winter months. For example, If the 
outdoor temperature is 47° F (8° C), your heat 
pump can deliver approximately 3.5 units of 
heat energy per each unit of electrical energy 
used, as compared to a maximum of only 1 
unit of heat energy produced with conventional 
heating systems.

In colder temperatures, the heat pump performs 
like an air conditioner run in reverse. Available 
heat energy outside the home is absorbed by 
the refrigerant and exhausted inside the home. 
This effi cient process means you only pay for 
“moving” the heat from the outdoors to the indoor 
area. You do not pay to generate the heat, as is 
the case with more traditional furnace designs.

During summer, the heat pump reverses the fl ow 
of the heat-absorbing refrigerant to become an 
energy-effi cient, central air conditioner. Excess 
heat energy inside the home is absorbed by the 
refrigerant and exhausted outside the home.

minutes following a previous operation or the 
interruption of the main electrical power.

Emergency Heat
Some thermostats may include a system mode 
called EM HT or AUX HT, etc. This is a back-
up heating mode that should only be used if a 
problem is suspected. With the mode set to EM 
HT, etc., the compressor and outdoor fan will 
be locked off and supplemental heat (electric 
resistance heating) will be used as a source 
of heat (if installed). Sustained use of electric 
resistance heat in place of the heat pump will 
result in an increase in electric utility costs.

Defrost
During cold weather heating operation, the 
outdoor unit will develop a coating of snow 
and ice on the heat transfer coil. This is normal 
and the unit will defrost itself. This unit features 
Demand Defrost that monitors ambient and coil 
temperatures to regulate the defrost function 
accordingly.

At the beginning of the defrost cycle, both the 
outdoor condenser fan and compressor will 
turn off. After approximately 30 seconds, the 
compressor will turn on and begin to heat the 
outdoor coil causing the ice and snow to melt. 

NOTE: 

While the ice and snow is melting, steam 

may rise from the outdoor unit as the warm coil 
causes the melting frost to evaporate. When 
defrost is completed, the outdoor fan motor will 
start, and the compressor will turn off again. In 
approximately 30 seconds the compressor will 
start up again and continue normal operation.

System Shutdown
Change the thermostat’s system mode to OFF 
and the fan mode to AUTO (See Figure 1). 

NOTE:

 The system will not operate, regardless 

of the temperature selector setting.

USER INFORMATION

Operating Instructions

Cooling Operation
1.  Set the thermostat’s system mode to COOL 

or AUTO and change the fan mode to AUTO. 
See Figure 1.

2. Set the temperature selector to the 

desired temperature level. The outdoor fan, 
compressor, and blower motor will all cycle 
on and off to maintain the indoor temperature 
at the desired cooling level.

Heating Operation
1.  Set the thermostat’s system mode to HEAT 

or AUTO and change the fan mode to AUTO. 
See Figure 1.

2. Set the temperature selector to the desired 

temperature level. The compressor, outdoor 
fan, and blower motor will cycle on and off to 
maintain the indoor temperature at the desired 
heating level.

NOTE: 

If the temperature level is re-adjusted, or 

the system mode is reset, the fan and compressor 
in the outdoor unit may not start immediately. A 
protective timer circuit holds the compressor 
and the outdoor fan off for approximately three 

Summary of Contents for Q5RD Series

Page 1: ...check the instructions and follow recommendations given If these suggestions don t eliminate your problem call your servicing contractor These instructions are primarily intended to assist qualified i...

Page 2: ...Low Pressure Switch 13 High Pressure Switch 13 Unit Maintenance 13 Figures Tables 13 Figure 9 Unit Dimensions 13 Table 4 Q5RD Physical Data 13 Charging Tables Cooling Mode 14 Table 5 Q5RD X24K 2 Ton U...

Page 3: ...f the heat pump will result in an increase in electric utility costs Defrost During cold weather heating operation the outdoor unit will develop a coating of snow and ice on the heat transfer coil Thi...

Page 4: ...tdoor coil must be maintained in order to achieve rated performance See Figure 2 page 5 for minimum clearances to obstructions Consideration should also be given to availability of electric power serv...

Page 5: ...ngto NationalFireProtectionAssociation Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of Ame...

Page 6: ...tion from under the home by cuttingasmallholeinthesub floor Determine how the floor joist location will affect cutting the opening needed for the return air box NOTE Floor joists are generally located...

Page 7: ...t a hole approximately 3 4 larger than the damper opening in the fiberboard 3 Cut a 9 1 8 x 13 1 8 hole in the duct and bend over all tabs flat on the inside of the heat duct 4 Insert the damper into...

Page 8: ...e energizing the outdoor unit See unit data label for proper incoming field wiring Any other wiring methods must be acceptable to authority having jurisdiction Providepowersupplyfortheunitinaccordance...

Page 9: ...1650 T5 High 1950 Denotes Factory Set Low Speed Cooling Heating Denotes Factory Set High Speed Cooling Heating Denotes Factory Set Electric Heating Speed Overcurrent Protection Overcurrent protection...

Page 10: ...a proper location Start Up Procedure The control circuit consists of an anti short cycle timer that will not let the compressor re start before 5 minutes have elapsed 1 Set the system mode to OFF and...

Page 11: ...above the Terminate Temperature setting Short the TEST pins for 1 second or more to force the control out of defrost and back to heating mode reversing valve de energized Compressor will start immedia...

Page 12: ...s necessary using a mild detergent and water Rinse thoroughly with water Inspecttheelectricalconnectionsfortightness at the beginning of each heating and cooling season Service as necessary CAUTION Th...

Page 13: ...Control Access Panel Blower Access Panel H 17 86 15 36 10 10 3 4 NPT Drain Connection 1 12 13 1 38 3 2 3 2 5 29 FIGURES TABLES Q5RD Length L Width W Height H A B 024K 49 35 22 2 40 15 7 61 030K 49 35...

Page 14: ...mp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 139 258 115 141 260 121 281 121 143 262 126 283 126 304 126 145 266 129 285 131 306...

Page 15: ...mp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 134 269 129 136 271 135 293 134 138 274 140 295 139 316 138 140 279 139 297 144 318...

Page 16: ...s Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 124 126 274 101 128 276 112 295 111 130 277 124 298 121 318 119 132 279 129 300...

Page 17: ...ated design values The suction pressure will vary from design value if outdoor air fl ow entering dry bulb or entering wet bulb temperatures vary 1 All pressures are listed psig and all temperatures i...

Page 18: ...ated design values The suction pressure will vary from design value if outdoor air fl ow entering dry bulb or entering wet bulb temperatures vary 1 All pressures are listed psig and all temperatures i...

Page 19: ...137 73 305 142 87 334 154 103 365 173 119 396 192 35 231 126 48 257 131 61 283 135 74 309 140 88 341 151 104 372 168 120 403 186 36 238 124 49 263 129 62 288 133 75 313 138 89 348 148 105 379 164 121...

Page 20: ...D HIGH PRESSURE SWITCH LOW PRESSURE SWITCH SELECT MODELS ONLY BLUE BLUE RED RED RED RED RED ORANGE YELLOW WHITE WHITE WHITE WHITE GREY BROWN BLACK BLACK GREEN BROWN ORANGE BLUE BLACK BROWN BROWN RED R...

Page 21: ...CK BLUE BLACK GREY BLACK ORANGE WHITE RED GREEN YELLOW RED BLUE ORANGE YELLOW GREY BROWN RED BROWN Z H 0 6 T L O V 0 3 2 8 0 2 4 For replacement wires use conductors suitable for 105 C 5 On models w n...

Page 22: ...Accessory Heat Plug Outdoor Thermostat Factory Option Typical Wiring Field Supplied for 1 Stage Cool 1 Stage Electric Heat INDOOR T STAT SUB BASE Green DEFROST BOARD 1 2 3 4 5 6 7 8 9 Brown Orange Ac...

Page 23: ...23...

Page 24: ...ndusingcommonsenseplays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failuretofollowsafe...

Reviews: