background image

4

OPERATING INSTRUCTIONS

To Operate Your Heat Pump For Cooling —

1.  Set the thermostat system switch to COOL 

and the thermostat fan switch to AUTO. 

See 

Figure 1.

2.    Set the thermostat temperature selector to the 

desired cooling temperature. The outdoor unit 
fan, the indoor blower, and the compressor 
will all cycle on and off to maintain the indoor 
temperature at the desired cooling level. 

NOTE: If the thermostat temperature level is 
re-adjusted, or if the thermostat system switch 
is re-positioned, the outdoor unit fan and the 
compressor may not start immediately. A 
protective timer circuit holds the compressor and 
the outdoor fan off for approximately six minutes 
following a previous operation or the interruption 
of the main electric power 

To Operate Your Heat Pump For Heating —

1.  Set the thermostat system switch for HEAT 

and the thermostat fan switch to AUTO. 

See 

Figure 1.

2.  Set the thermostat temperature selector to the 

desired heating temperature. The outdoor unit 
fan, the indoor blower, and the compressor 
will all cycle on and off to maintain the indoor 
temperature at the desired heating level.

NOTE: If the thermostat temperature level is 
re-adjusted, or if the thermostat system switch 
is re-positioned, the outdoor unit fan and the 
compressor may not start immediately. A 
protective timer circuit holds the compressor and 
the outdoor fan off for approximately six minutes 
following a previous operation or the interruption 
of the main electrical power.

Emergency Heat — 

Some thermostats will 

include a system switch position termed EM 
HT or AUX HT, etc. This is a back-up heating 
mode to be used only if there is a suspected 
problem. With the system switch set to EM 
HT, etc., the compressor and outdoor fan will 
be locked off and supplemental heat (electric 
resistance heating) will be used as a source of 
heat. Sustained use of electric resistance heat in 
place of the heat pump will result in an increase 
in electric utility costs. 

Defrost — 

During cold weather heating operation, 

the outdoor unit will develop a coating of snow 
and ice on the heat transfer coil. This is normal 
and the unit will periodically defrost itself. During 
the defrost cycle, the outdoor fan will stop, while 
the compressor continues to run and heat the 
outdoor coil, causing the snow and ice to melt. 
During defrost, there may be some steam rise 
from the outdoor unit as the warm coil causes 
some melted frost to evaporate.

Figure 2. Thermostat Interlock System

Cooling 

Thermostat

Furnace

Thermostat

Double Throw

Double Pole Switch

To Air Conditioner

To Furnace

R

R

Figure 1. Typical Thermostat

FAN SWITCH

TEMPERATURE SELECTOR

Summary of Contents for Q4RD 060

Page 1: ...g appliances Some local codes require licensed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable national a...

Page 2: ...2...

Page 3: ...a the supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat SUMMER COOLING 1 Indoor air enters the return air duct 2 The cold heat transfer section in...

Page 4: ...oned the outdoor unit fan and the compressor may not start immediately A protectivetimercircuitholdsthecompressorand the outdoor fan off for approximately six minutes following a previous operation or...

Page 5: ...ecautionsintheliterature on tags and on labels provided with the unit and or approved field installed kits The type of hazard and severity are described on each label or tag Pressures Within The Syste...

Page 6: ...URN DUCT OPENING 23 5 1 25 Power Entry 1 75 Power Entry Capped 0 88 Control Wiring Entry 23 6 27 2 30 1 8 4 00 13 5 16 0 14 7 13 5 16 0 13 45 11 75 22 75 55 8 C SUPPLY RETURN 4 0 CONDENSING COIL 5 0 8...

Page 7: ...hat drains well See Figure 6 AIR DUCTS This unit is designed only for use with a supply and return duct Air ducts should be installed in accordance with the standards of the National Fire Protection A...

Page 8: ...ion SMACNA application standard for duct liners Duct lining must be UL classified batts or blankets with a fire hazard classification of FHC 25 50 or less Fiber duct work may be used in place of inter...

Page 9: ...achieve maximum performance Locating and Installing the Supply Damper s When locating the supply damper s carefully check floor joists and frame members that could interfere with the installation of...

Page 10: ...tionandplasticsleeve should be pulled over the connection and clamped f For homes with multiple supply ducts or for special applications a Y fitting is available to divide the supply air so it can be...

Page 11: ...stalled circuit breaker kits are used inside the control compartment Use only copper wire for the line voltagepowersupplytothisunit Usepropercode agency listed conduit and a conduit connector for conn...

Page 12: ...0 minutes 60 minutes and 90 minutes Time setting selection is dependent on the climate where the unit is being installed Example 1 Dry climate of Southern Arizona A 90 minute setting is recommended Ex...

Page 13: ...essor and fan energize and that the temperature of the discharge air is cooler than the room temperature This is available only for the single phase models System Cooling 1 Set the thermostat system s...

Page 14: ...out the availability of maintenance contracts At a minimum routine maintenance should include the following 1 Inspect and clean or replace air filters at the beginning of each heating and cooling seas...

Page 15: ...1 Stage Cool 1 Stage Electric Heat Typical Wiring Field Supplied for 2 Stage Cool 2 Stage Electric Heat with an Optional Outdoor Thermostat Figure 12 Typical Heat Pump Thermostat Connections E O G R...

Page 16: ...173 253 174 270 175 81 222 175 238 177 255 178 272 179 289 180 83 226 179 242 181 258 182 274 183 291 184 85 245 185 261 186 278 187 293 188 87 265 190 281 192 297 193 89 284 196 301 197 91 304 202 93...

Page 17: ...SETS THE INTERVAL TO 0 1 2 3 4 C R S C H F E DFTR W2 0 Y C T2 T1 DF2 DF1 C Y 0 W2 R E PRESSURE SWITCH IF EQUIPPED TO 208 230 VAC POWER SUPPLY BLOWER MOTOR T1 T3 T4 T2 G N L C 2 3 4 5 6 7 8 9 1 2 3 4 5...

Page 18: ...RESETS THE INTERVAL TO 0 1 2 3 4 C R S C H F E DFTR W2 0 Y C T2 T1 DF2 DF1 C Y 0 W2 R E PRESSURE SWITCH IF EQUIPPED TO 208 230 VAC POWER SUPPLY BLOWER MOTOR T1 T3 T4 T2 G N L C 2 3 4 5 6 7 8 9 1 2 3...

Page 19: ...19...

Page 20: ...5460 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 05 06 708546 INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE H...

Reviews: